To Connect The Refrigerant Piping To The Outdoor Unit - Daikin R32 Series Installer's Reference Manual

Hide thumbs Also See for R32 Series:
Table of Contents
To handle the stem cap
To handle the service cap

6.4.8 To connect the refrigerant piping to the outdoor unit

3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1B – 2020.05
Counterclockwise to open
Clockwise to close
3 When the stop valve CANNOT be turned any further, stop turning.
4 Install the stop valve cover.
Result: The valve is now open/closed.
The stem cap is sealed where indicated with the arrow. Do NOT damage it.
After handling the stop valve, tighten the stem cap, and check for refrigerant
leaks.
Piping Ø (mm)
Width across flats (mm)
6.4
9.5
12.7
15.9
ALWAYS use a charge hose equipped with a valve depressor pin, since the service
port is a Schrader type valve.
After handling the service port, tighten the service port cap, and check for
refrigerant leaks.
Item
Service port cap
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical damage.
1 Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
a
Liquid stop valve
b
Gas stop valve
c
Service port
17
19
22
27
b
c
6
Installation
|
Tightening torque (N∙m)
15~17
18~20
22~27
48~59
Tightening torque (N∙m)
11~14
a
c
Installer reference guide
39