6
|
Installation
6.3.3 To provide the installation structure
6.3.4 To install the outdoor unit
6.3.5 To provide drainage
Installer reference guide
30
Check the strength and level of the installation ground so that the unit will not
cause any operating vibration or noise.
Use a vibration-proof rubber (field supply) in cases where vibrations may be
transmitted to the building.
The unit may be installed directly on a concrete veranda or another solid surface as
long as it provides proper drainage.
Fix the unit securely by means of foundation bolts in accordance with the
foundation drawing.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply).
(mm)
a
100 mm above expected level of snow
▪
Make sure that condensation water can be evacuated properly.
4× M8/M10
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1B – 2020.05