To Connect The Refrigerant Piping To The Outdoor Unit - Daikin 3MXM40N2V1B8 Installer's Reference Manual

Hide thumbs Also See for 3MXM40N2V1B8:
Table of Contents
To open/close the stop valve
To handle the stem cap
To handle the service cap

7.2.8 To connect the refrigerant piping to the outdoor unit

2MXM68+3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1C – 2020.08
1 Remove the stop valve cover.
2 Insert a hexagon wrench (liquid side: 4  mm, gas side: 6  mm) into the valve
stem and turn the valve stem:
Counterclockwise to open
Clockwise to close
3 When the stop valve CANNOT be turned any further, stop turning.
4 Install the stop valve cover.
Result: The valve is now open/closed.
The stem cap is sealed where indicated with the arrow. Do NOT damage it.
After handling the stop valve, tighten the stem cap, and check for refrigerant
leaks.
Piping Ø (mm)
Width across flats (mm)
6.4
9.5
12.7
15.9
ALWAYS use a charge hose equipped with a valve depressor pin, since the service
port is a Schrader type valve.
After handling the service port, tighten the service port cap, and check for
refrigerant leaks.
Item
Service port cap
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical damage.
1 Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
7
Tightening torque (N∙m)
17
19
22
27
Tightening torque (N∙m)
Piping installation
|
15~17
18~20
22~27
48~59
11~14
Installer reference guide
43