Using The Stop Valve And Service Port - Daikin 3MXM40N2V1B8 Installer's Reference Manual

Hide thumbs Also See for 3MXM40N2V1B8:
Table of Contents
7
|
Piping installation

7.2.7 Using the stop valve and service port

To handle the stop valve
Installer reference guide
42
e
Inter-unit piping
Coat the threaded connection port of the outdoor unit where the flare nut comes
in with refrigeration oil.
Flare nut for (mm)
Ø9.5
Ø12.7
Ø15.9
NOTICE
Use an appropriate wrench to avoid damaging the connection thread by
overtightening the flare nut. Be careful NOT to overtighten the nut, or the smaller
pipe may be damaged (about 2/3-1× the normal torque).
Take the following guidelines into account:
The stop valves are factory closed.
The following figure shows the stop valve parts required when handling the
valve.
a
b
c
d
a
Service port and service port cap
b
Valve stem
c
Field piping connection
d
Stem cap
Keep both stop valves open during operation.
Do NOT apply excessive force to the valve stem. Doing so may break the valve
body.
ALWAYS make sure to secure the stop valve with a spanner, then loosen or
tighten the flare nut with a torque wrench. Do NOT place the spanner on the
stem cap, as this could cause a refrigerant leak.
a
b
a
Spanner
b
Torque wrench
When it is expected that the operating pressure will be low (e.g. when cooling
will be performed while the outside air temperature is low), sufficiently seal the
flare nut in the stop valve on the gas line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
Tightening torque (N•m)
33~39
50~60
62~75
2MXM68+3(A)MXM+3(A)MXF+4MXM+5MXM
4P600463-1C – 2020.08
R32 Split series