LG AMNW07GSJL0 Engineering Product Data Book page 211

Total hvac solution provider multi/single indoor unit r32 heat pump 50 / 60hz 0cti5-02a replaces 0cti5-01c
Hide thumbs Also See for AMNW07GSJL0:
MULTI/SINGLE
7. Installation
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
If the temperature rise above 30
or use additional insulation to the indoor unit body.
– "Dew Protective kit" is sold separately.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
Top view
(Unit: mm)
600
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Chassis code
L1
L2
L3
14
Indoor unit
Air conditioner or
Ducted air diffuser
Take enough
distance
or the humidity rise above RH 80%, the dew-protective kit should be equipped
Control box
600
Inspection hole
(600 x 600)
H=20 or more
Ceiling concealed duct - Low static pressure
※ According to type of indoor unit, external appearance
or installed structure could be different.
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
A(Min)
A [mm]
800
800
800
B(Min)
Ceiling
Service Space
A
B [mm]
800
1,000
1,200
loading