10.4.2 2-points curve

Installer reference guide
142
Types of weather-dependent curve
There are 2 types of weather-dependent curves:
2-points curve
Slope-offset curve
Which type of curve you use to make adjustments, depends on your personal
preference. See
"10.4.4 Using weather-dependent
Availability
The weather-dependent curve is available for:
Main zone - Heating
Main zone - Cooling
Additional zone - Heating
Additional zone - Cooling
Tank
INFORMATION
To operate weather dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See
Define the weather-dependent curve with these two setpoints:
Setpoint (X1, Y2)
Setpoint (X2, Y1)
Example
Y2
Y1
X1
curves" [
"10.4.4 Using weather-dependent
a
X2
4
 144].
4
curves" [
 144].