Using Modbus Rtu Communication - Allen-Bradley Micro830 Manual

Hide thumbs Also See for Micro830:
Table of Contents
Chapter 2
About Your Controller
18

Using Modbus RTU Communication

To use RMCC with the Modbus RTU communication protocol, the serial port
must be set to the Modbus slave role. A CIP Generic message is sent from within
a program with the following parameters.
CIP Generic Message Parameters for RMCC using Modbus RTU
Parameter
Value
Service
16
Class
70
Instance
2 – Embedded serial port
5, 6, 7, 8, or 9 – Plug-in modules
Attribute
100
ReqData
New node address, 1
ReqLen
2
RMCC Modbus Example – Set the Parameters
RMCC Modbus Example – Set the New Node Address
The first byte indicates the new node address for the controller. For this example,
the new node address is "3". The second byte must always be "1", this indicates
that the Modbus role is configured as Slave.
RMCC Modbus Example – Set the Message Length
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

Micro850Micro870

Table of Contents