Climate 5000 vrf building management system gateway card (bacnet)
Detailed infromation of corresponding objects refer to under-table
1) Device infromation
Attribute Identifier
Object Identifier
Object Name
Object Type
Device Status
Producer Name
Producer Identifier
Model Name
Firmware Edition
Application Software Edition
Protocol Edition
Protocol Correspondency Type
Protocol Service Support
Protocol Object Types Support
Object Array
Max length of APDU support
Segmentation support
Local Time
Local Date
APDU Segmentation Timeover
APDU Timeover
APDU Resend Times
Device Address Binding
Operation instruction
2) Running mode
Attribute Identifier
Object Identifier
Object Name
Object Type
Description
Current value
Status Flags
Event states
Take off service
States number
States text
Priority Array
Release default
Time delay
Publicly type
Feedback value
CLIMATE 5000 VRF
Data mode
Attribute value
BACnetObjectIdentifier
Device + Acnumber
CharacterString
Indoor * *
BACnetObjectType
Device
BACnetDeviceStatus
Operational
CharacterString
AC Inc
Unisgned16
1 1 1 (Unsigned)
CharacterString
Get one of these from protocolanalysis: Wall Mounted Tpye Floor Tpye Embedded
Tpye Duct Tpye Floor&ceiling Tpye AC Auxiliary Machine Tpye Digital Mutil-
connection Tpye Frequency Conversion Tpye Digital Rotation Tpye
CharacterString
1.0
CharacterString
1.0
Unsigned
1
Unsigned
3
BACnetServiceSupport
ReadProperty
BACnetObjectTypesSupport
AnalogInput
BACnetArray[n]
Array all object
Unsigned
1476
BACnetSegmentation
Segmented both(0)
Time
Date
Unsigned
2000
Unsigned
3000
Unsigned
3
AddressBinding
ASN.1 ''
The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT (it's unsettable). The
MINIMAL VALUE stands for the MINIMUM ELECTRIC CURRENT, while the MAXMUN VALUE stands for the MAXIMUM ELECTRIC
CURRENT.
Data mode
Attribute value
BACnetObjectIdentifier
Multistate-output 1
CharacterString
AC_OModeSetting
BACnetObjectType
Multistate-output
CharacterString
Operation mode setting
Unsigned
BACnetStatusFlags
F F F F
BACnet EventStates
Normal
BOOLEAN
F
Unsigned
6
BACnet ARRAY[N]
Auto
CharacterString
Cool
Heat
Dehumidify
FanOnly
Stop
BACnetPriorityArra
NULL
Unsigned
0
Unsigned
2
Unsigned
1701
Unsigned
6
OBJECT TABEL | 5
Read/write
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
O
R
R
R
Read/write
R
R
R
O
W
R
R
R
R
O
R
R
O
O