Bosch BMS-BAC User Manual
Bosch BMS-BAC User Manual

Bosch BMS-BAC User Manual

Climate 5000 vrf building management system gateway card (bacnet)

Quick Links

CLIMATE 5000 VRF
Building Management System Gateway Card (Bacnet)
BMS-BAC
User manual
Before using your bacnet, please read this manual carefully and keep it for future reference.
loading

Summary of Contents for Bosch BMS-BAC

  • Page 1 CLIMATE 5000 VRF Building Management System Gateway Card (Bacnet) BMS-BAC User manual Before using your bacnet, please read this manual carefully and keep it for future reference.
  • Page 2 2 | CONTENTS CONTENTS CONNECTING DIAGRAM ..........3 FUNCTION DESCRIPTION ..........3 CONFIGURATION ILLUSTRATION ........3 OBJECT TABEL ...............4 6720862469 (16/04) CLIMATE 5000 VRF...
  • Page 3: Connecting Diagram

    Default administrator name is “admin” and the password is “12345”. CAUTION CAUTION For safety, passwords should be changed from the factory set 1) BMS-BAC net can connect to the centralised controller, or the ones. outdoor master unit. The address on the centralised controller 3.4. Network setting must be (0) and the outdoor master unit must be set to (16).
  • Page 4 4 | OBJECT TABEL OBJECT TABEL 3.5. BACnet setting The BACnet network code represents only one of the BACnet This device provides with different objects tables for the different centralised controllers in the range between 0 to 65535. Once the types of outdoor units which are in using for the VRF system.
  • Page 5 OBJECT TABEL | 5 Detailed infromation of corresponding objects refer to under-table 1) Device infromation Attribute Identifier Data mode Attribute value Read/write Object Identifier BACnetObjectIdentifier Device + Acnumber Object Name CharacterString Indoor * * Object Type BACnetObjectType Device Device Status BACnetDeviceStatus Operational Producer Name...
  • Page 6: Preset Temperature

    6 | OBJECT TABEL Event enable BACnetEventTransitionBits T T T Affirm transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType alarm Operation instruction The CURRENT VALUE attribute of the selected object reflects the current OPERATION MODE (it’s writeable and settable). Thereinto, the CURRENT VALUE 1 means HEATING MODE; the CURRENT VALUE 2 means COOLING MODE; the CURRENT VALUE 3 means DEHUMIDIFIED MODE;...
  • Page 7 OBJECT TABEL | 7 Low valve value REAL High valve value REAL Width valve value REAL Enable valve value BACnetLimitEnable Event enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType alarm Publicly type Unsigned 1701 Time delay Unsigned Affirm transform BACnetEventTransitionBits T T T Operation instruction The CURRENT VALUE attribute of the selected object reflects the current SETTNG TEMPERATURE (it’s writable and settable).
  • Page 8 8 | OBJECT TABEL Maximum REAL Distinguishability REAL 0.25 Priority Array BACnetPriorityArra NULL Default release REAL COV INCREMENT REAL 0.25 Low valve value REAL High valve value REAL Width valve value REAL Enable valve value BACnetLimitEnable Event enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType alarm...
  • Page 9 OBJECT TABEL | 9 Object Type BACnetObjectType Binary-output Current value BACnetBinaryPV inactive Discription CharacterString Swing Setting Status Flags BACnetStatusFlags F F F F Event states BACnet EventStates Normal Take off service BOOLEAN Polarity BACnetPolarity Normal Inactive text CharacterString Turn off Active text CharacterString Turn on...
  • Page 10 10 | OBJECT TABEL 10) Malfunction states Attribute Identifier Data mode Attribute value Read/write Object Identifier BACnetObjectIdentifier Multistate-input 1 Object Name CharacterString AC _IMalfunction Object Type BACnetObjectType Multistate-input discription CharacterString Malfunction State current value Unsigned Status Flags BACnetStatusFlags F F F F Event states BACnet EventStates Normal...
  • Page 11 OBJECT TABEL | 11 Time delay Unsigned Publicly type Unsigned 1701 Event enable BACnetEventTransitionBits T T T Affirm transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType alarm Operation instruction The CURRENT VALUE attribute of the selected object reflects the current PROTECTION status (it’s read only). In case of the CURRENT VALUE shows as No P, that means the system without protection, while other information displaying means the other relevant protection.
  • Page 12 12 | OBJECT TABEL 4.2. Outdoor Air Conditioner Objects This equipment provides with ten types of BACnet object, show as the following table, for connecting with Inverter AC or Digital AC using in the Building Management System (BMS) or other system which suitable for BACnet Protocol. Number Content Device Information...
  • Page 13 OBJECT TABEL | 13 Event states BACnet EventStates Normal Take off service BOOLEAN States number Unsigned States text BACnet ARRAY[N] Cool CharacterString Heat Stop Time delay Unsigned Publicly type Unsigned 1701 Event enable BACnetEventTransitionBits T T T Affirm transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType...
  • Page 14 14 | OBJECT TABEL High valve value REAL Width valve value REAL Enable valve value BACnetLimitEnable Event enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType event Operation instruction The CURRENT VALUE attribute of the selected object reflects the current ROOM TEMPERATURE (it could not be set). The MINIMAL VALUE stands for the minimum temperature, while the MAXMUN VALUE stands for the maximum Temperature.
  • Page 15 OBJECT TABEL | 15 Operation instruction The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT (it’s unsettable). The MINIMAL VALUE stands for the MINIMUM ELECTRIC CURRENT, while the MAXMUN VALUE stands for the MAXIMUM ELECTRIC CURRENT. 7) Compressor 2 current Attribute Identifier Data mode...
  • Page 16 16 | OBJECT TABEL Attribute Identifier Data mode Attribute value Read/write Object Identifier BACnetObjectIdentifier Multistate-input 3 Object Name CharacterString AC _IOutmalfunction Object Type BACnetObjectType Multistate-input Discription CharacterString Malfunction State Current value Unsigned Status Flags BACnetStatusFlags F F F F Event states BACnet EventStates Normal Take off service...
  • Page 17 OBJECT TABEL | 17 States text BACnet ARRAY[N] CharacterString No P Time delay Unsigned Publicly type Unsigned 1701 Event enable BACnetEventTransitionBits T T T Affirm transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType alarm Operation instruction The CURRENT VALUE attribute of the selected object reflects the current PROTECTION STATUS (it’s read only). In case of the CURRENT VALUE shows as No P, that means the system without protection, while other information displaying means the other relevant protection.
  • Page 18 18 | NOTES NOTES 6720862469 (16/04) CLIMATE 5000 VRF...
  • Page 19 NOTES | 19 CLIMATE 5000 VRF 6720862469 (16/04)
  • Page 20 Bosch Thermotechnology Ltd. CotswoldWay, Warndon, Worcester WR4 9SW All Enquiries: 0330 123 3004 www.bosch-industrial.co.uk...