Example: Input Channel As Test Pulse From Test Output - Allen-Bradley SmartGuard 600 User Manual

Table of Contents
52
Configure Local I/O
Publication 1752-UM001A-EN-P - October 2006
TIP
9. Specify an On Delay time and an Off Delay time.
The valid range is 0...126 ms, but the delay time must be a
multiple of the cycle time.
The optimum value for controller cycle time is
IMPORTANT
automatically calculated based on the parameter settings
and the application programs. Therefore, set the on- and
off-delay times last.

Example: Input Channel as Test Pulse from Test Output

For the following wiring diagram, the channel mode must be
configured as Test pulse from test out, as shown.
I0
I1
11 21
12 22
S1
V1
V2
E2
E1
The controller supports function blocks with
functionality equivalent to Dual Channel mode.
If Dual Channel mode is set in a function
block, the safety input terminal can be set to
Single Channel mode.
I2
I4
I6
I8
I10
I5
I7
I9
I3
I11
S2
G1
T0
T2
O0
O2
G2
T1
T3
O1
O3
I12
I14
KM1-NC
I13
I15
KM2-NC
KM1
O4
O6
KM2
O5
O7
KM2
KM1
M