70 | Menu settings INSTALLER SETTINGS (for installers only)
Factory setting of parameters for
heating curve
Heating surface exponent (fixed
value), curvature of heating curve
Minimum outdoor temperature
Base line
Design Temp
Design supply temp.
Maximum heating supply
temperature
Room temperature offset
Heating OFF at outdoor
temperature
Tab. 7
Base line: Use this menu option to set the
base point of the heating curve according to
the traditional base point/end point method
Heating circuit 1 and/or Heating circuit 2.
Design Temp: Use this menu option to set the
base point of the heating curve according to
the traditional base point/end point method
Heating circuit 1 and/or Heating circuit 2.
Design supply temp.: Use this menu option to
adapt the supply temperature setting to the
heating type for the Heating circuit 1 and/or
Heating circuit 2.
– For Radiant Floor e.g. 114 °F (45 °C)
supply temperature setting.
– For Radiators e.g. 168 °F (75 °C) supply
temperature setting.
– For Baseboard e.g. 176 °F (80 °C) supply
temperature setting.
Maximum heating supply temperature: Use
this menu option to adapt the supply
temperature setting to the heating type for the
Heating circuit 1 and/or Heating circuit 2.
– For Radiant Floor e.g. 132 °F (55 °C)
maximum supply temperature.
– For Radiators e.g. 176 °F (80 °C)
maximum supply temperature.
– For Baseboard e.g. 176 °F (80 °C)
maximum supply temperature.
6 720 643 256 (2010/05)
Baseline/Design
temp
6 °F ( – 15 °C)
78 °F (25 °C)
168 °F (75 °C)
114 °F (45 °C)
176 °F (80 °C)
132 °F (55 °C)
0 °F (0.0 °C)
68 °F (20 °C)
Radiant Floor
Radiators
1.1
6 °F ( – 15 °C) 6 °F ( – 15 °C)
168 °F (75 °C) 176 °F (80 °C)
176 °F (80 °C) 176 °F (80 °C)
0 °F (0.0 °C)
0 °F (0.0 °C)
68 °F (20 °C)
68 °F (20 °C)
Room influence: This menu option only
appears if the controls are wall-mounted.
Use this menu option to set the room
temperature influence on the heating curve
for the Heating circuit 1 and/or Heating
circuit 2.
– 0%: No room temperature influence
– 100%: Maximum room temperature
influence
Room influence enabled for modes: Use this
menu option to select the operating modes
where the room temperature influence is to
be active for Heating circuit 1 and/or Heating
circuit 2.
– Eco/Frost: Room temperature influence is
only active in these operating modes.
– Comfort/Eco/Frost: Room temperature
influence is always active.
Room temperature offset: Use this menu
option to set the permanent increase in
required room temperature for the Heating
circuit 1 and/or Heating circuit 2, e.g. to
correct system-related variations.
US/CA
Baseboard
1.3
1.4
0 °F (0.0 °C)
68 °F (20 °C)