Warnings and Alarms
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state running)
2816
Stack overflow Control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
keypad Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-51
Parameter value is outside its limits
22
5123
Option in slot A: Hardware incompatible with Control
board hardware
5124
Option in slot B: Hardware incompatible with Control
board hardware
5125
Option in slot C0: Hardware incompatible with Control
board hardware
5126
Option in slot C1: Hardware incompatible with Control
board hardware
8
8
5376-62
Out of memory
31
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-51 Terminal 27 Mode.
WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-52 Terminal 29 Mode.
WARNING 42, Overload of Digital Output on X30/6 or
Overload of Digital Output on X30/7
For X30/6, check the load connected to X30/6 or remove
short-circuit connection. Check E-56 X30/6 Digital Out
(OPCGPIO).
For X30/7, check the load connected to X30/7 or remove
short-circuit connection. Check E-57 Term X30/7 Digital
Out (OPCGPIO).
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24V, 5V,
+/- 18V. When powered with 24V DC with the OPC24VPS
option, only the 24V and 5V supplies are monitored. When
powered with three phase mains voltage, all three
supplied are monitored.
132
AF-600 FP High Power Operating Instructions
WARNING 47, 24 V supply low
The 24V DC is measured on the control card. The external
24V DC backup power supply may be overloaded,
otherwise contact your GE supplier.
WARNING 48, 1.8 V supply low
The 1.8V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card.
WARNING 49, Speed limit
When the speed is not within the specified range in par.
F-18 and par. F-17. the drive will show a warning. When
the speed is below the specified limit in H-36 Trip Speed
Low [RPM] (except when starting or stopping) the drive will
trip.
ALARM 50, Auto tune calibration failed
Contact your GE supplier.
ALARM 51, Auto tune check Unom and Inom
The setting of motor voltage, motor current, and motor
power is presumably wrong. Check the settings.
ALARM 52, Auto tune low Inom
The motor current is too low. Check the settings.
ALARM 53, Auto tune motor too big
The motor is too big for the Auto tune to be carried out.
ALARM 54, Auto tune motor too small
The motor is too small for the Auto tune to be carried out.
ALARM 55, Auto tune Parameter out of range
The parameter values found from the motor are outside
acceptable range.
ALARM 56, Auto tune interrupted by user
The Auto tune has been interrupted by the user.
ALARM 57, Auto tune timeout
Try to start the Auto tune again a number of times, until
the Auto tune is carried out. Please note that repeated
runs may heat the motor to a level where the resistance Rs
and Rr are increased. In most cases, however, this is not
critical.
ALARM 58, Auto tune internal fault
Contact your GE supplier.
WARNING 59, Current limit
The current is higher than the value in F-43 Current Limit.
WARNING 60, External interlock
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
external interlock and reset the frequency converter (via
serial communication, digital I/O, or by pressing reset
button on keypad).
WARNING 62, Output frequency at maximum limit
The output frequency is higher than the value set in
F-03 Max Output Frequency 1
WARNING 64, Voltage limit
The load and speed combination demands a motor
voltage higher than the actual DC link voltage.
Table of Contents