General Specifications - GE AF-600 FP Operating Instructions Manual

Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

General Specifications

7 General Specifications
Mains supply (L1, L2, L3):
Supply voltage
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100k RMS symmetrical Amperes, 480/600V
maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Accel/Decel Times
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to AF-600 FP Drive's nominal torque.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mains and brake *
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Maximum cross section to control terminals, cable with enclosed core
Minimum cross section to control terminals
* See Mains Supply tables for more information!
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
AF-600 FP High Power Operating Instructions
380-480V ±10%
525-600 V ±10%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
maximum once/2 min.
overvoltage category III / pollution degree 2
0 - 100% of supply voltage
maximum 110% for 1 min.
maximum 135% up to 0.5 sec.
maximum 110% for 1 min.
2
1.5 mm
/16 AWG (2 x 0.75 mm
1 mm
0.5 mm
18, 19, 27
50/60Hz ±5%
(> 0.98)
7
7
0 - 800* Hz
Unlimited
1 - 3600 sec.
*
*
*
150 m
300 m
2
)
2
/18 AWG
2
/20 AWG
2
0.25 mm
4 (6)
1)
, 29, 32, 33,
PNP or NPN
0 - 24V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ
113