Removal Of Shunt - Daikin Super Multi NX C-Series Service Manual

Super multi nx c-series
Table of Contents
SiE12-411
1.8

Removal of Shunt

Procedure
Step
1
Remove 6 screws of
the tie wire presser
plate.
Remove 4 screws of
2
the right side panel.
3
Remove the putty.
" Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
4
Disconnect the 5
brazed points of the
shunt.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Tie wire pressure plate
Right side panel
Shunt
Putty
Outdoor Unit (80 / 90 Class)
" Fasten the rubber packing
with double-faced adhesive
tape when mounting.
Rubber
packing
Brazed points
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
Warning
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)
Points
235

Hide quick links:

Table of Contents
loading

Table of Contents