Thermistor Resistance Check - Daikin Super Multi NX C-Series Service Manual

Super multi nx c-series
Table of Contents
SiE12-411

6.1.5 Thermistor Resistance Check

Check No.6
Remove the connectors of the thermistors on the PCB, and measure the resistance of each
thermistor using tester.
The relationship between normal temperature and resistance is shown in the graph and the
table below.
Temperature (°C)
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
Service Diagnosis
Thermistor R25°C=20kΩ B=3950
211.0 (kΩ)
150
116.5
88
67.2
51.9
40
31.8
25
20
16
13
10.6
8.7
7.2
(R25 = 20k , B=3950)
(k )
Tester
Resistance range
(°C)
Check
207