Defrost Module Function Set; Digital Scroll Controller (Zxd) - Emerson Copeland Scroll User Manual

Zx condensing unit for refrigeration applications
Hide thumbs Also See for Copeland Scroll:
Table of Contents
For ZX-MT Unit:
OFF: Evaporator ON/OFF logic is same as compressor and this is the factory
default setting
ON: Evaporator fan will be ON for all time irrespective of whether the
compressor is turned ON or OFF
For ZXL-LT & ZXB-MT Units:
OFF: SH target value set at 5K and this is the factory default setting
for R404A, R134A and R22
ON: SH target value set at 10K, for R407F
Not applicable for ZX/ZXL/ZXB units
Note:
The settings given in the table are pre-set at the factory for new units

Defrost Module Function Set

Time of Defrost
Rotary
Time
Switch1
(min)
0
0
1
5
2
10
3
15
4
20
5
25
6
30
7
35

Digital Scroll Controller (ZXD)

The controller has been pre-programmed with a number of parameter values that are set for typical application. Individual
installation requirements, however, may make it necessary to alter parameter settings. The control target of the digital scroll
available compressor capacity. The set-point can be altered using the SEtC parameter. Factory setting SEtC is -6
The control target of the fan speed controller is to maintain the average condenser mid-coil temperature and hence the
the SEtF parameter. Factory setting SEtF is 25
located in the SEtC position as shown in the diagram below:
Press for more than 2 seconds
SEtC value
Flashing
or
to change set value within 30 seconds
press to memorize new set value.
Use setting in the table
Time of Defrost Interval
Rotary
Time
Switch2
(hours)
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
C. Initial setting of set point for saturated suction temperature.Pre-set value is
o
ON
1 2 3
Defrost Duration (in Minutes)
Manual Defrost
Button
Remote Connector
For Manual Defrost
Figure 6. Defrost Module
Then SEtF (fan speed control set point) will be displayed
automatically.
SEtC value
Flashing
Or
to change set value within 30 seconds
press to memorize new value and Exit, or wait for
30 seconds without pressing any key to memorize value
and exit.
Defrost Interval
(in Hours)
E2 Connector
C.
o
9