Connecting Indoor Units - Sanyo SAP-CMRV1424EH Technical & Service Manual

Dc inverter multi-system air conditioner
Table of Contents
G
Install the indoor unit more than 1 meter away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G
install in a sturdy manner to avoid increased operating
noise.
Table 3
Max. Allowable
Model
Tubing Length
per unit (m)
CMRV1424
20

2-2. Connecting Indoor Units

(1) Connecting indoor unit for SAP-CMRV1424
Outdoor unit
B
ø9.52
A
ø9.52
Max. Allowable
Total Tubing Length
at Shipment (L1+L2) (m)
30 (L1+L2)
ø9.52
ø6.35
ø9.52
ø6.35
Fig. 4
Limit of
Limit of Elevation
Total Tubing Length
(L1+L2) (m)
30 (L1+L2)
Indoor unit
(SAP-KMRV74EH,KMRV94EH,KMRV124EH)
(SAP-KMRV74EH,KMRV94EH,KMRV124EH)
5
Required Amount
Difference
of Additional
(H1, H2) (m)
Refrigerant (g/m)*
15
unit: mm