Sanyo SAP-CMRV1424EH Technical & Service Manual page 36

Dc inverter multi-system air conditioner
Table of Contents
Control/conditions
COOL
The ON/OFF operation
button on the remote
controller is pressed.
The room temperature
has reached the
desired temperature.
The thermostat turns
OFF.
The thermostat turns
ON again.
Freeze prevention
Stop
Operation is restarted
within 4 hours (only when
AUTO mode is selected
with the remote
controller).
Operation starts after 4
hours or more have
passed.
Frequency control
Unit operation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches
frequency increases are stopped for a period
of
seconds. (Refer to Table 2.)
The frequency then increases.
The indoor temperature and the desired
temperature are approximately equal.
After the thermostat turns ON again, the
outdoor unit will not operate for 3 minutes,
even if the room temperature increases
above the desired temperature.
When the temperature of the indoor heat
exchanger drops to approximately 2 °C
or below, the compressor turns OFF, the
outdoor fan turns OFF, and the indoor fan
continues operating with no changes.
Approximately 3 minutes later, if the
temperature of the indoor heat exchanger
is adove 8 °C, the system returns to its
original conditions.
All indicator lamps turn OFF. The indoor and
outdoor units stop.
Starts operating in the same operating mode
(COOL) and with the same temperature
settings as before operation was stopped.
New operating mode is determined based on
the temperature conditions at the time the
ON/OFF operation button is pressed.
(Hz)
Outdoor air temperature is below 0 °C.
(25) Hz
(35) Hz
(45) Hz
(55) Hz
The outdoor unit does not operate for 3 minutes
even after the breaker is turned ON.
Hz,
This is in order to stabilize the return of oil to the
compressor.
If the indoor and outdoor temperatures are high,
the current peak cut-off activates, stopping
any increases in frequency.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The outdoor unit stops. (It does not stop if the
thermostart for another indoor unit is ON.)
After 3 minutes, the outdoor unit begins operating
automatically.
During these 3 minutes, a pressure balance is
achieved, allowing the compressor to start
more easily.
In order to protect against freezing, the
compressor stops temporarily, until the
temperature of the indoor heat exchanger has
risen.
Within 4 hours after operation was stopped, it is
assumed that there has been no significant
change in the indoor and outdoor temperatures,
and the previous conditions (COOL) are stored.
(senconds)
Outdoor air temperature is 0 °C or higher.
(120) seconds
(60) seconds
(60) seconds
(180) seconds
Table 2
36
Explanation
The frequency is increased at the rate of 0.5
Hz every 1 seconds.
(60) seconds
(30) seconds
(30) seconds
(90) seconds