Power supply units

Safety notes
V
CAUTION!
Do not disassemble the power supply unit. Doing so may cause
electric shock.
Areas around the power supply unit may remain extremely hot after
shutdown. After shutting down the server, wait for hot components to
cool down before removing the power supply unit.
When installing a power supply unit, ensure that the connector of the
power supply unit is not damaged or bent.
If the power supply unit is hard to remove, do not pull it out by force.
The power supply unit is heavy, so handle it carefully. If you drop it by
mistake, injuries may result.
For further safety information, please refer to chapter
information" on page
6.1

Basic information

The PRIMERGY RX300 S8 server can be equipped:
– with up to two power supply units that automatically adjust to any mains
voltage in the range of 100 VAC to 240 VAC
– or with up to two DC power supply units that adjusts automatically to any
power voltage in the range from -40.5 V to -57 V.
I
Power redundancy is possible in with two power supply units . The
effective power of the power supply units may not differ.
V
CAUTION!
The server supports a mains voltage in the range of 100 VAC to 240 VAC
or a direct current source in the range of -40.5 V to -57 V. You may only
operate the server if its rated voltage range corresponds to the local
mains voltage.
RX300 S8