Adjustment of detection settings

Notice!
i
Camera settings should preferably be made in the Configuration Manager, as advanced
functionalities are available there.
Notice!
i
For further parameters and ambient conditions to be considered, see the planning manual.
Notice!
i
Settings for Tamper detection are only available in the Configuration Manager and only in
VCA profiles Fire #1 and Fire #2.
The standard settings of the video-based fire detection are tested and optimized for
environments that aim to cover most customer applications. Nevertheless, there are many
ways to adapt the flame and smoke detection to the requirements of the customer. The
detection settings of the fire detection can be changed in the configuration menu. The
following steps apply to the web browser menu:
1.
2.
There are three profiles for Fire detection. These different Fire detection profiles can also
be used in a scheduled and event triggered configuration:
General and special settings for Fire detection are selectable. Anytime you change the
settings, confirm with Set to apply these changes.
If you want to abort, just click on another menu option, for example Audio Alarm.
7.1

General settings

Notice!
i
To ensure that the system can reliably detect under ambient lighting of less than 1 lux, the
Illuminator function must be set to Auto and the Intensity level must be set to 30 (default
values).
Flames
The default setting of the flame size is 1.1% of the picture width.
Verification time [s] of the flame detection can be set from 4 to 20 seconds in 1 s steps.
The default value is 10 seconds. Small values cause faster detection (higher risk of false
alarms), larger values decrease false alarms.
Sensitivity
In case of false alarms, you can use a software slider to adapt the value Sensitivity for flame
and smoke to your specific needs. The following table shows the different settings:
Bosch Sicherheitssysteme GmbH
Go to Configuration and navigate to Alarm.
Select Fire detection.
Fire
Fire#1 (renameable in Configuration Manager )
Fire#2 (renameable in Configuration Manager )
User manual
Adjustment of detection settings | en
2023.10 | 02 | F.01U.414.168