Open Door; Disable Routing Equipment With Door Switch; Silence Buzzer With Door Switch - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents
EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

17. OPEN DOOR

A special key is used to open the control unit door to get access to the front / system.
If any door in the system is open the following symbol is shown in the c.i.e display's symbol area:
See also section
30.3. OPEN DOORS (H4/U3)
There will not be an indication in the c.i.e display for the door in Display unit 5055.

17.1. DISABLE ROUTING EQUIPMENT WITH DOOR SWITCH

Via EBLWin the following can be programmed: Disable routing equipment by door switch
None (selected by default): Open door in a C.U. will not disable the output(s) for routing equipment (Fire brigade tx and fault tx).
Any control unit door: Open door in any C.U. will disable the output(s) for routing equipment (Fire brigade tx and fault tx) in all
C.U:s. This is a violation against EN54-2.
Any door: Open door in any C.U. will disable the output(s) for routing equipment (Fire brigade tx and fault tx) in all C.U:s. This is
a violation against EN54-2.
These functions are not valid for the Display unit 5055.
Disabled outputs for routing equipment are indicated by the LEDs Fault / Disablements "General disablements" and "Fire brigade tx"
and listed in menu H4/U1.

17.2. SILENCE BUZZER WITH DOOR SWITCH

Via EBLWin can be set that the built-in c.i.e. buzzer will be silenced when the c.i.e. door is open.
See chapter
13. SILENCE BUZZER
on page 97.
on page 31.