Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Quick Links

Operating Instructions

MEW01349
Revision -
Fire Alarm System EBL512 G3
V1.1.x
Author:
Jan Pettersson
Date of issue: 2011-02-18
Date of rev:
Table of Contents
loading

Summary of Contents for Panasonic MEW01349

  • Page 1: Operating Instructions

    Operating Instructions MEW01349 Revision - Fire Alarm System EBL512 G3 V1.1.x Author: Jan Pettersson Date of issue: 2011-02-18 Date of rev:...
  • Page 2 This page has deliberately been left blank.
  • Page 3: Table Of Contents

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Table of contents Introduction________________________________ 6 Definitions / Explanations ____________________ 8 PEWN AB ________________________________________ 8 Alarm points ______________________________________ 8 2.2.1 Smoke detector ________________________________ 8 2.2.2 Sensor _______________________________________ 8 2.2.3...
  • Page 4 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x LED indicators and push buttons _____________ 17 The display (LCD) _________________________ 21 Areas in the display ________________________________ 21 The symbol area __________________________________ 21 The information area priority order ____________________ 22 System information in the LCD ______________________ 23 6.4.1...
  • Page 5 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 16.2 Fire alarm reset ___________________________________ 49 16.2.1 All _________________________________________ 49 16.2.2 Single_______________________________________ 49 16.2.3 Single with automatic disablement ________________ 50 16.2.4 Acknowledged and Isolated alarm ________________ 50 16.3...
  • Page 6 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.9 Disable / re-enable routing equipment (H2/B9) _________ 102 25.10 De-activate Alert Annunciation function (H2/B10) ____ 103 Set calendar and clock (H3) _________________ 104 Present system status (H4) __________________ 105 27.1...
  • Page 7 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x How to change paper in the printer __________ 152 Replacing a TLON connection board and/or the Main board____________________________________ 153 Battery maintenance _______________________ 154 How to avoid unnecessary (nuisance) fire alarms 155...
  • Page 8: Introduction

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Introduction EBL512 G3 Operating Instructions is a document intended to be used by the end-user and the fire brigade personnel as well as service / commissioning engineers.
  • Page 9 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  sometimes additional information, such as Convention (different functions / facilities), Language, Number of addresses, etc. PC S/W A PC S/W is a program used for programming, commissioning, etc. It...
  • Page 10: Definitions / Explanations

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. PEWN AB Panasonic Electric Works Nordic AB Alarm points Units, which can generate a fire alarm (in the control unit), i.e.
  • Page 11: Output Unit

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 2.2.8 Conventional zone line input / External line Input intended for one or more conventional alarm points. End-of-line device in the last alarm point.
  • Page 12: System

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 2.11 System Several control units connected via a TLON network (co-operating control units). ® ® 2.12 Network / TLON / LonWorks / Echelon / Node / TLON Conn.
  • Page 13: Site Specific Data (Ssd)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 2.17 Site Specific Data (SSD) The SSD is unique for each installation. All alarm points, presentation numbers, user definable text messages, programmable outputs, etc. are created in the PC program WinG3 and also downloaded in EBL512 G3 with WinG3.
  • Page 14: Overview

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Overview The EBL512 G3 system EBL512 G3 is a microprocessor controlled intelligent fire alarm system, intended for analog addressable smoke detectors, as well as conventional detectors and manual call points.
  • Page 15: S/W Versions

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x is space for two 27 Ah batteries. Larger batteries (up to 65 Ah) have to be placed outside the c.i.e. The batteries and the power supply are connected to the Main board (5010), which handles the charging of the batteries, etc.
  • Page 16: Tlon Manager

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 3.5.2 TLON Manager TLON Manager is used for the TLON Network programming. 3.5.3 WebG3 Config tool A PC tool, WebG3 Config tool is used for configuration of the Web-...
  • Page 17: Control Unit

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Control Unit Figure 1. Left: The EBL512 G3 Control Unit 5000, with printer. The look might vary according to configuration, country, etc. Right: The EBL512 G3 Control Unit 5001.
  • Page 18 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x P4 – P7 L7, L8 L9, L10 L11, L12 L13, L14 Figure 2. The EBL512 G3 front with display; The Fire Brigade Panel (FBP) is the upper part and the Control Panel (CP) is the lower part.
  • Page 19: Led Indicators And Push Buttons

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x LED indicators and push buttons LEDs and push buttons can vary according to type and configuration (convention / country / language). See also Figure 2, page 16.
  • Page 20 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Push buttons on the Fire Brigade Panel (FBP) Push button Operation/function Silence buzzer (yellow) Used to silence the buzzer in the c.i.e. Silence Alarm devices Used to silence alarm devices / sounders (i.e.
  • Page 21 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x LED indicators on the Control Panel (CP) LED indicator Indicating System fault (yellow) EBL512 G3 is not running because of S/W, CPU or memory fault.
  • Page 22 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Push buttons / Keypad on the Control Panel (CP) Key/push button Operation/function ↵ (Enter) Used to log on, i.e. to get access to the menu tree (via an access code) and to accept a menu and accept input of data.
  • Page 23: The Display (Lcd)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x The display (LCD) Areas in the display Symbol area Information area Menu Next zone Re-enable Evacuate Soft key area The display is divided in three areas: ...
  • Page 24: The Information Area Priority Order

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x The information area priority order When the control unit / system is in normal operation (quiescent state), i.e. no fire alarms, no faults, no disablements, no service...
  • Page 25: System Information In The Lcd

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x System information in the LCD EBL512 G3, control unit number, date and time are displayed. The exact look is convention / language dependent. One example:...
  • Page 26: Access Levels

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Access levels EBL512 G3 has different access levels (1-4) for different kind of users. Access levels 2 and 3 are divided in sub levels (A-B).
  • Page 27: Access Level 1

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Access level 1 With the door closed , anybody has access to the push button "Alarms queued" (P8) to scroll / browse through the queued alarms.
  • Page 28: Access Level 2B

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Access level 2B After the door has been opened ("Door open" symbol in the symbol field), the building occupier has access to level 2A and after...
  • Page 29: Access Level 3A

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Access level 3A After the door has been opened ("Door open" symbol in the symbol field), the service / maintenance personnel have access to...
  • Page 30: "Silence Alarm Devices

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "Silence Alarm devices" In the control unit front (the FBP part) there is a push button "Silence alarm devices" (P2). When the alarm devices are activated (sounding) and the push button "Silence alarm devices"...
  • Page 31: New Zealand Fb Silence Switch (Outside Switch)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  Alarm devices disabled All programmable outputs of type "Alarm devices" are disabled, i.e. they cannot be activated.  Alarm devices not disabled All programmable outputs of type "Alarm devices" are enabled, i.e.
  • Page 32 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x (presented in the display) will " " be changed to " ". Two examples: ISO Point: 123-46 LAST: 234-56 No.: 001 This is a user defined alarm text.
  • Page 33: Disable / Re-Enable Alarm Devices

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Disable / Re-enable alarm devices Outputs programmed for sounders (i.e. type "Alarm devices") can via menu H2/B8 be collective disabled for all control units. This is indicated by LED Fault / Disablements "General disablements"...
  • Page 34: 10 "Silence Buzzer

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "Silence buzzer" The buzzer in the control unit will sound for:  Fire alarm (0.4 / 0.4 sec.)  Co-incidence alarm (2-zone or 2-unit dependent fire alarm): When only one zone or one zone / address (alarm point) is in alarm status (0.8 / 5 sec.)
  • Page 35: Disable / Re-Enable All Control, Extinguishing, Ventilation And Interlocking Outputs

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Disable / Re-enable all control, extinguishing, ventilation and interlocking outputs All control outputs programmed as type:  Control (general)  Extinguishing  Fire ventilation ...
  • Page 36: Evacuate

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Evacuate When the soft key "Evacuate" (P7) is pressed , all outputs programmed for sounders (i.e. type "Alarm devices"), will be collective turned ON (steady). This is indicated in the LCD:...
  • Page 37: Open Door

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Open door A special key is used to open the control unit door to get access to the front / system. The same type of key is also used to open the ext. FBP door.
  • Page 38: Technical Number / Presentation Number

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Technical number / Presentation number 14.1 Technical number for COM loop units The technical number, NNNNNN, is used when programming all units connected to the COM loops.
  • Page 39: Presentation Number

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 14.2 Presentation number For each fire alarm point / input / zone, a presentation number, NNN-NN, has to be programmed. The presentation number is shown in the c.i.e.
  • Page 40: Alarm Types

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Alarm types In case of a fire, analog detectors (sensors), conventional smoke and/or heat detectors, manual call points and programmable inputs can activate fire alarm. If somebody illegally breaks into a key cabinet, this will also activate a "fire alarm"...
  • Page 41: Fire Alarm

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x In case of a pre-warning, the following happens:  The buzzer in the c.i.e. sounds 0.8 sec. each 5 sec. (0.8 / 5 sec.).
  • Page 42 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x are activated, no more fire alarms will be shown until one or more of the first 512 fire alarms are reset. It is possible to have Selective alarm presentation, i.e. only fire alarms from selected control units will be presented Set in WinG3.
  • Page 43 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x More than one alarm point activating fire alarm. Example; fire alarm in zone 002, address 03 (within zone 002) and nine other fire alarms (of which the latest alarm is 003-11) in four...
  • Page 44: Enter The Menu During Fire Alarm

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x The printer (if available) will print each fire alarm, e.g.: ** Fire Alarm ** Zone 002 Address 03 SMOKE YYYY-MM-DD hh:mm User definable alarm text (if progr.)
  • Page 45: Acknowledged And Isolated Alarm

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 15.2.2 Acknowledged and Isolated alarm Acknowledged and Isolated alarm is a fire alarm function only used in New Zealand. Acknowledged alarm A fire alarm presented in the display can be acknowledged by pressing the soft key "Acknowledge"...
  • Page 46: Alert Annunciation Alarm (Aa Alarm)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  Outputs programmed for heavy smoke / heat alarm are activated.  Each heavy smoke / heat alarm is presented with a "title", i.e. "Heavy smoke" or "Heavy heat" will be added to the...
  • Page 47: Key Cabinet Alarm

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x brigade tx) will be activated. See EBL512 G3 Planning Instructions for more information regarding the AA function. Acknowledgement and reset of the AA alarm can be done on an AA unit 1735 / 1736 or an AA controller 1740.
  • Page 48: Co-Incidence Alarm (2-Address / -Zone Dependence)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 15.5.2.1 Restoring the key after a fire alarm When all fire alarms in the system are reset (see chapter "Alarm reset", page 49), the key has to be restored into the key cabinet within 5 minutes.
  • Page 49: Alarm Acknowledgement Facility (Aaf)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 15.7 Alarm Acknowledgement Facility (AAF) One or more Alarm Acknowledgement Facility Controls are used in the system. See EBL512 G3 Planning Instructions chapter "Alarm Acknowledge- ment Facility (AAF)"...
  • Page 50 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Quiet alarm Zone Address 123-45 SMOKE User definable alarm text for 123-45. Menu Programmable outputs for quiet alarm, e.g. 3361 outputs controlling supply air fans and standard fans, i.e. any output with a control expression containing the trigger conditions "Quiet Alarm Zone"...
  • Page 51: Alarm Reset

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Alarm reset 16.1 Pre-warning reset Pre-warning is automatically reset. 16.2 Fire alarm reset NOTE! The detectors having activated fire alarm shall, after reset, be inspected, tested and replaced when required.
  • Page 52: Single With Automatic Disablement

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x All outputs (for fire alarm) are reset, i.e. de-activated. If a key cabinet is installed, the key (to the building) has to be put back into the key cabinet within 5 minutes.
  • Page 53: Key Cabinet Alarm Reset

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 16.5 Key cabinet alarm reset A key cabinet alarm has to be reset like the normal fire alarms. After reset a fault message is shown in the display to inform the user that the key cabinet has been opened.
  • Page 54: Fault

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Fault All faults are delayed in order not to generate any unnecessarily faults, e.g. for COM loop and zone line input faults the delay time is approx.
  • Page 55 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  In the c.i.e. display can up to three fault messages be shown simultaneously. In the display, down to the left, is displayed the number of not acknowledged faults.
  • Page 56: Fault Messages

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 17.1 Fault messages Below follows a list of all fault messages, in alphabetical order. There is also an explanation to each fault. FAULT: 24V for external equipment output x, control unit xx x = 1-4.
  • Page 57 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: Battery, technical number xxxxxx The charging function in the external power supply 3366 connected on the COM loop is not OK. The p.c.b. has to be replaced.
  • Page 58 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Network 1: In a redundant network is Network 1normally in a supervised quiescent state until there is a fault (cut-off or short circuit) on Network 0.
  • Page 59 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x messages. If there are several breaks on the loop the message shows the last isolator before the break in the A-direction (incl. the following isolator).
  • Page 60 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x COM loop x (0-3) in the control unit no. xx. There is some internal fault on the board, which has to be replaced. FAULT: External fuses, control unit xx...
  • Page 61 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x supervised input in the EBL512 G3 system, in control unit no. xx. Check the input connections as well. (Normally used for German routing equipment connected to an expansion board 4583 input 0.)
  • Page 62 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x fire alarms in the system. FAULT: L-C mixed COM-loop x, control unit xx The two wires L (SA) and C (SB) for COM-loop no. x (0-3), in control unit no.
  • Page 63 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: Low voltage, output unit xxxxxx System voltage < 21 V DC in the external power supply unit 3366. Check the power supply (rectifier) 1537 output voltage, which shall be 24 V DC.
  • Page 64 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x control unit xx Break (cut-off) / short-circuit in more than one segment on the COM loop, in control unit no. xx. FAULT: Network cables mixed control unit xx In a redundant TLON Network the Network 0 cables and Network 1 cables are mixed.
  • Page 65 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: No reply, external presentation unit xx, control unit xx FAULT: No reply, fire brigade panel xx, control unit xx Alert Annunciation Unit 1735 / 1736.
  • Page 66 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x calibrated via menu H5/A1.  Some external influence has caused a fault in the SSW. This is very serious. Call for service personnel/engineer. FAULT: Restart control unit nn, code xx, address yyyyyyyyyy Control unit restart has occurred in control unit no.
  • Page 67 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x There will also be a "FAULT: No reply ….." message for each unit not found by the c.i.e. If there are several short-circuits on the loop the message shows the isolator just before the break in the A-direction (incl.
  • Page 68 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x A fault on the supervised input x on the expansion board 4583 with address x, in control unit no. xx. Check the cables / connections (cut-off or short-circuit).
  • Page 69 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  Connected equipment might be "missing".  End-of-line resistor(s) missing or not correct value, 1-5 resistors (33K). NOTE! The calibrated value has to be in the range 4K7-50K.
  • Page 70 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: Wrong type, expansion board x, control unit xx Valid for the 8 zones exp. board 4580, the 8 relay outputs exp. board 4581 and the Inputs and outputs exp. board 4583, mounted in control unit no.
  • Page 71: Fault Acknowledge

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 17.2 Fault acknowledge The LEDs Routing equipment "Fault tx activated" (L13) and Fault / Disablements "General fault" (L9) are turned on (LEDs Fault / Disablements "Alarm devices" (L11), "System fault"...
  • Page 72 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x  All faults have to be individually acknowledged one by one by the key pad button  . Use  or  to scroll.
  • Page 73: Commissioning An Installation

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Commissioning an installation Before you connect the power supply to a control unit, all other cable connections shall be made. Check once more that they are correct.
  • Page 74: Control Units In A Tlon Network

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 18.2 Control Units in a TLON network The EBL512 G3 system can be build up as a single TLON Network or as a redundant TLON Network, i.e. two networks.
  • Page 75: Add A Control Unit In A Tlon Network

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x control unit (main board 5010). Open the project in TLON Manager and install (download) the project, see separate TLON network documentation. In case of a redundant TLON system a PC is connected to the modular connector "J11"...
  • Page 76 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Open the SSD for the current system via WinG3. Delete the control unit (and the units connected to it) and download the new SSD...
  • Page 77: Programming (Ssd Download)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Programming (SSD download) The PC program WinG3 is used for programming of the site specific data (SSD) and to download it into the EBL512 G3 control unit(s) and/or 1728, 1735, 1736, 1826 &...
  • Page 78: Control Units In A Tlon Network

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: Site specific data (SSD), CU nn YYYY-MM-DD HH:MM This text message means that the SSD have not been downloaded properly, i.e. a new download has to be performed.
  • Page 79: New System Program (S/W) Version Download

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x New system program (S/W) version download The latest software (S/W) version of the EBL512 G3 system program is factory downloaded before the delivery. Due to continual development and improvement, different S/W versions can be found.
  • Page 80 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Progress bar 2. Set the Main board 5010 in "boot" mode, i.e. hold the "Boot" button (SW2) down and push the "RESET" button (SW1) momentarily until the Main board 5010 is in "boot"...
  • Page 81: Control Units In A Tlon Network

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Click "Yes" and the control unit will restart. Regarding the restart, see also chapter "Restart", page 81. 6. LED "Operation" (L5) will be turned on and the other LEDs will be turned off.
  • Page 82: Upgrade Number Of Alarm Points

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Upgrade number of alarm points All EBL512 G3 settings are normally factory downloaded before delivery. It is however, possible to do the following on site: ...
  • Page 83: Restart

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Restart A restart will delete or not delete the data in EBL512 G3. Here follows an explanation of the different data, abbreviations and a table showing how the data respectively is affected (cold or warm restart).
  • Page 84 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Action Data, etc. Data, etc. Restart which will be which will be code deleted not deleted Power down (de-energize) SSD, then power up again. ("Cold restart")
  • Page 85 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x And after a few seconds (if everything is all right, else see Memory fault below): Booting..A fault will be generated and the following text message will be...
  • Page 86 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT: Restart control unit nn, code xx, address yyyyyyyyy FAULT: Site specific data (SSD) This means that the SSD have not been (correctly) downloaded.
  • Page 87: Access

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Access To use the key pad in the control unit (to get access to the menu tree), it is necessary to logon with an access code for level 2B or 3A. See also chapter "Access levels", page 24.
  • Page 88 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Explanations: ↵ Action (in the table) = use push button / key (e.g. " "). Text in display (in the table) = what is shown in the control unit (c.i.e.) display.
  • Page 89: Perform Monthly Test (H1)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Perform monthly test (H1) The control unit and the installation shall be tested on a regular basis. If one twelfth of the alarm points are tested each month, the whole installation will be tested after one year.
  • Page 90 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Write zone numbers Zones to be set in test mode Press "↵ " to start the test (e.g. 001, 002, 003, 001 002 003 004 mode.
  • Page 91 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x H1 Perform monthly test press "ESC". H2 ..NOTE_1! During the test, the following information will be shown in all other c.i.e. displays: Zones in test mode: 001, 002, 003, 004 NOTE_2! If an alarm point (e.g.
  • Page 92: Disable Or Re-Enable (H2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Disable or re-enable (H2) A whole zone, one or more alarm points within a zone and/or control outputs can be disabled via menus H2/B1-B3. This possibility can be used when a temporary disablement is wanted (e.g.
  • Page 93: Disable Zone (H2/B1)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.1 Disable zone (H2/B1) When a whole zone is disabled, all alarm points within the zone are disabled except the addressable manual call points. (This function can depend on convention / country.)
  • Page 94: Disable Zone / Address (H2/B2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.2 Disable zone / address (H2/B2) Addressable alarm points (also addressable manual call points), connected to the COM loop, can be individually disabled. Disabled alarm points, zone / addresses, are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 95 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "↵ " Disable zone: 000 address: 00 LED Fault / (press ↵) Disablements "General disablements" (L10) will light up. Disable another zone or press "ESC". Scroll to another menu or press "ESC".
  • Page 96: Disable Output (H2/B3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.3 Disable output (H2/B3) All outputs (except outputs type "Alarm device") can be individually disabled. Disabled output will stay in (or return to) the normal condition for the output respectively.
  • Page 97: Re-Enable Zone (H2/B4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.4 Re-enable zone (H2/B4) Disabled zones are listed in menu H4/U1 from which it is also possible to get a print-out. Re-enabling via this menu has higher priority than automatic re- enabling.
  • Page 98: Re-Enable Zone / Address (H2/B5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.5 Re-enable zone / address (H2/B5) Disabled alarm points, zone / addresses, are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 99: Re-Enable Output (H2/B6)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.6 Re-enable output (H2/B6) Disabled outputs are listed in menu H4/U1 from which it is possible to get a print-out. When all outputs have been re-enabled, The LED Fault / Disablements "General disablements"...
  • Page 100: Disable / Re-Enable Output Type (H2/B7)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.7 Disable / re-enable output type (H2/B7) All outputs programmed as type control (general), fire ventilation and extinguishing system can for the type respectively be disabled all at the same time or all outputs of these types can be disabled all at the same time.
  • Page 101 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "↵ " Select output type control Use "▼" or "▲" to select extinguishing the output type in the list ventilation and press "↵ ".
  • Page 102: Disable / Re-Enable Alarm Devices (H2/B8)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.8 Disable / re-enable alarm devices (H2/B8) Outputs programmed as type alarm device (sounder) can be disabled all at the same time. Disabled alarm devices means that even if the control expression (trigger condition) for the output respectively is fulfilled (true), the output will not be activated.
  • Page 103 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "↵ " Select control unit 00 Write the CU number or press "►" and select "All" [Blank space] (all CUs) Press "Disable" or "Re- enable".
  • Page 104: Disable / Re-Enable Routing Equipment (H2/B9)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.9 Disable / re-enable routing equipment (H2/B9) Disabled outputs are listed in menu H4/U1 from which it is possible to get a print-out. Outputs for routing equipment (fire brigade tx / fault tx) can be disabled and re-enabled via this menu.
  • Page 105: De-Activate Alert Annunciation Function (H2/B10)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 25.10 De-activate Alert Annunciation function (H2/B10) Normal function: For alarm points / zones programmed for Alert Annunciation (via WinG3) is normally the AA function enabled via a time channel, e.g.
  • Page 106: Set Calendar And Clock (H3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Set calendar and clock (H3) The RTC component has a capacitor as a backup power supply. Normally, date, day of the week and time only have to be set when the power is turned on the control unit for the first time.
  • Page 107: Present System Status (H4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Present system status (H4) If printer 5058 - an option for control unit 5000 – is mounted, it is possible to get a print-out from some of the menus. In this case, the soft key "Print"...
  • Page 108: Disablement By Time Channel (H4/U2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x NOTE! During printing "Print" will be replaced with "Abort printing". 27.2 Disablement by time channel (H4/U2) A static list (4 items per page) of all disablements by time channel(s) in the system.
  • Page 109: Open Doors (H4/U3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.3 Open doors (H4/U3) If any door in the system is open the following symbol is shown in the display's symbol area: See also chapter "Open door", page 35.
  • Page 110: Sensor Values (H4/U4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.4 Sensor values (H4/U4) The very first week average sensor value is calculated within 2 minutes after SSD download & restart. During these 2 minutes can no fire alarm be activated and the sensor value "000"...
  • Page 111 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Regarding the Performance factor: The Performance factor can be 0.00 – 2.55. How the Performance factor (Pf) 14400 Σ | is calculated is shown to the left.
  • Page 112: Reset Of A Week Average Sensor Value

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.4.1 Reset of a week average sensor value If a sensor (analog smoke detector) is replaced without having generated SERVICE signal, its week average sensor value has to be cleared, i.e.
  • Page 113: Sensors Activating Service Signal (H4/U5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.5 Sensors activating SERVICE signal (H4/U5) When SERVICE signal is generated in the system, following symbol is shown in the display's symbol area: Regarding the SERVICE signal levels, see Planning Instructions, chapter "SERVICE signal".
  • Page 114: Event Log (H4/U6)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.6 Event log (H4/U6) Three event logs are available: 1. Alarm log (alarm events, e.g. fire alarm, fire alarm reset, etc.) 2. Interlocking log (only interlocking events) 3.
  • Page 115: Show Information (H4/U7)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 27.7 Show information (H4/U7) Menu H4/U7 can be used to show the following information for the specific control unit you currently use: Main board version The S/W (system program) version of the Main board 5010.
  • Page 116 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Scroll to menu U7. U7 Information "↵ " Main board version: vvvvvvvvvvvv If printer is mounted the MMI board version: vvvvvvvvvvvv soft key "Print" will be Alarm counter: nnn visible, else not.
  • Page 117: Service (H5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Service (H5) When commissioning an installation and by maintenance (e.g. when you power on and when you are programming a control unit / system), menu H5 can be used for certain information and help.
  • Page 118: Access Code For Service / Maintenance (H5 And H8)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.1 Access code for service / maintenance (H5 and H8) Access code to level 3A is required. If login to level 2B was made with code for level 3A, no code is required here.
  • Page 119: Calibration Of Supervised Outputs (H5/A1)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.2 Calibration of supervised outputs (H5/A1) Supervised (monitored) outputs The voltage outputs (S0-S3) in each control unit. The voltage outputs (VO0-VO1) in the COM loop output unit 3364.
  • Page 120: Sensitive Fault Detection Mode (H5/A2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.3 Sensitive fault detection mode (H5/A2) To increase the possibilities to detect faults during the commissioning, it is possible to use the "Sensitive fault detection mode". The time delay for each fault will then be reduced, i.e.
  • Page 121: Service Mode For Com-Loop (H5/A3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.4 Service mode for COM-loop (H5/A3) This mode can be used when commissioning an installation and by maintenance. The COM loop communication (polling) will be turned off but there is still voltage (24 V DC) on the loop in the A-direction only, in the B-direction only or in both directions at the same time.
  • Page 122 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x ↵ E.g. COM-loop 3, Service mode for control unit 03 COM-loop 3 Press " ", "ESC" or "Esc CU 03 and "A- Supplied from A-direction only menu"...
  • Page 123: Display Current Consumption In Unit (H5/A4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.5 Display current consumption in unit (H5/A4) The resolution is not very high, i.e. the displayed values give only a rough idea of the current consumption.
  • Page 124: Display Current Consumption Com-Loop (H5/A5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.6 Display current consumption COM-loop (H5/A5) The resolution is not very high, i.e. the displayed values give only a rough idea of the current consumption.
  • Page 125: Display Statistics For Communication (H5/A6)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.7 Display statistics for communication (H5/A6) The statistics can be used during commissioning, service, etc. Number of pollings is the number of pollings / "questions" sent out by the control unit to all the units connected on the COM loop.
  • Page 126 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Number of pollings: nnnnnnn Note! The values are not Parity fault: 000000 00.0% live updated. Number of bit faults: 000000 00.0% No answer: 000000 00.0% Bit length fault: 000000 00.0%...
  • Page 127: Activate Address Setting Mode For Du (H5/A7)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 28.8 Activate address setting mode for DU (H5/A7) This function can be used by commissioning / service engineer to activate the address setting mode in the following Display Units connected to the c.i.e.:...
  • Page 128: Fault Acknowledge (H6)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x FAULT Acknowledge (H6) Regarding fault indication, etc., see chapter "Fault", page 52. See also chapter "Fault acknowledge", page 69. All faults and the status / action are stored in the event log and can be listed, see chapter "Event log (H4/U6)", page 112.
  • Page 129: Perform Zone Test (Test Mode) (H7)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Perform ZONE TEST (Test mode) (H7) Normally, zones are tested during the monthly test via menu H1. Via this menu (H7) it is possible to perform the zone test solely.
  • Page 130 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "Esc Menu" End test: ↵ 001 002 003 004 H7 but still in test mode. NOTE! See chapter "The information area priority order", page 22 regarding priority order.) ↲...
  • Page 131: Maintenance (H8)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Maintenance (H8) 31.1 Access code for service / maintenance Access code to level 3A is required for menu H8. 31.2 Disconnect loop (H8/S1) Before physical connection / disconnection of loop units, etc. the loop (or zone line) shall be disconnected (disabled), i.e.
  • Page 132 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Scroll to another menu or press "ESC". Don’t forget to re-connect the loop / zone line again, via menu H8/S2.
  • Page 133: Re-Connect Loop (H8/S2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.3 Re-connect loop (H8/S2) Disconnected (disabled) loops / zone lines (via menu H8/S1) are indicated by LED "General disablements" (L10) Fault / Disablements and listed in menu H4/U1.
  • Page 134: Acknowledge Service Signal (H8/S3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.4 Acknowledge SERVICE signal (H8/S3) When SERVICE signal is generated in the system, following symbol is shown in the display's symbol area: See also chapter "Sensors activating SERVICE signal (H4/U5)", page 111.
  • Page 135 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "↵ " (The service signal for the selected sensor is now Continue like above or acknowledged and the next sensor will be shown.) press "ESC" to menu S3.
  • Page 136: Clear Weekly Average (H8/S4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.5 Clear weekly average (H8/S4) If a sensor (analog smoke detector) is replaced without having generated SERVICE signal, its week average sensor value has to be cleared and set to the default value otherwise the new / clean sensor will inherit the old sensor's value.
  • Page 137: Test Of Alarm Devices (H8/S5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.6 Test of alarm devices (H8/S5) The programmable outputs of type "Alarm device" can be collectively activated via this menu (H8/S5), which makes it possible to test the alarm devices.
  • Page 138 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "↲ " Test of alarm devices in progress. The test will continue for End test? one hour if not stopped via this menu (S5) or if a fire alarm is activated in the system.
  • Page 139: Safe Shut Down Of Control Unit (H8/S6)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.7 Safe shut down of control unit (H8/S6) It's not recommended to power off a control unit (i.e. no 230 V AC and no battery) without first doing a safe shut down of control unit.
  • Page 140 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Power off / Power on FAULT: Restart control unit nn, code xx After a restart / power on address yyyyyyyyyy (see page 81), there will after 5 min.
  • Page 141: Activate Address In Alarm Mode (H8/S7)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.8 Activate address in alarm mode (H8/S7) One alarm point (zone-address), not a whole zone, can be set in alarm. The built-in LED in the alarm point (detector) will be turned on to indicate the alarm.
  • Page 142 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x First alarm: 123-45 Alarm number 1(of 1) "↲ " This manually activated fire alarm will be Test mode presented in all control Zone Address unit displays and all ext.
  • Page 143: Synchronize The Control Units (H8/S8)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.9 Synchronize the control units (H8/S8) After any control unit restart, synchronization will start automatically. Synchronization can also be started via WinG3 and via this menu (H8/S8).
  • Page 144 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x "▼" Synchronization in progress... During the synchronization "↲ " the progress symbol for each control unit is shown. CU00 ↻ CU10 ↻ CU20 ↻...
  • Page 145: Change Code For Service / Maintenance (H8/S9)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.10 Change code for service / maintenance (H8/S9) For security reasons, the default code should be changed. Action Text in display Comments "Menu" Procedure according to chapter "Access code for...
  • Page 146: Change Code For Pc-Communication (H8/S10)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 31.11 Change code for PC-communication (H8/S10) As a protection against unauthorised personnel programming the system (via WinG3), an access code (level 3B & 4) for PC-connection is required.
  • Page 147: Interlocking Outputs And Inputs (H9)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Interlocking outputs and inputs (H9) 32.1 Activated interlocking outputs / inputs (H9/C1) Action Text in display Comments "Menu" According to chapter "Access", see page 85.
  • Page 148: Activate Interlocking Output (H9/C2)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 32.2 Activate interlocking output (H9/C2) The output in each interlocking combination (area / point) can be manually activated via this menu. The corresponding interlocking input will be "monitored"...
  • Page 149: Reset Interlocking Output (H9/C3)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 32.3 Reset interlocking output (H9/C3) All activated interlocking outputs are listed in this menu. - If the interlocking output is activated via its programmed control expression and with latching output selected (in WinG3), the output has to be reset via this menu.
  • Page 150: Disable Interlocking Output (H9/C4)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 32.4 Disable interlocking output (H9/C4) Interlocking outputs (Type = Interlocking) can be individually disabled via this menu but not via menu H2/B3. All interlocking outputs can be collectively disabled via menu H2/B7.
  • Page 151: Re-Enable Interlocking Output (H9/C5)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x 32.5 Re-enable interlocking output (H9/C5) Disabled interlocking outputs are listed in menu H4/U1 from which it is also possible to get a print-out. Interlocking outputs (Type = Interlocking) can be re-enabled via this menu but not via menu H2/B6.
  • Page 152: Change Access Code For Daily Duties (H10)

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Change access code for daily duties (H10) For security reasons, the default code should be changed. Action Text in display Comments "Access" According to chapter "Access", see page 85.
  • Page 153: Annual Control

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Annual control The building occupier is highly recommended, once a year, to do some tests, beside the monthly tests. To avoid the Fault tx output(s) to be activated, they can be disabled via menu H2/B9 (or via an open door, se chapter "Open door", page 35.).
  • Page 154: How To Change Paper In The Printer

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x How to change paper in the printer When the paper roll is almost empty, a red line appears on one edge of the paper. Change the paper roll before it is completely empty! Always have a spare paper roll on site (paper width 58 mm).
  • Page 155: Replacing A Tlon Connection Board And/Or The Main Board

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Replacing a TLON connection board and/or the Main board By the TLON network programming, some unique data will be stored in a memory on the 1590 TLON connection board and some will be stored in a memory on the 5010 main board.
  • Page 156: Battery Maintenance

    Operating Instructions Fire alarm system EBL512 G3, V1.1.x Battery maintenance The batteries - 2 x 12 V, 28 Ah (e.g. Panasonic LC-P1228AP) - are placed inside the control unit. Larger batteries (< 65 Ah) have to be placed outside the control unit, e.g. in a separate battery cabinet, etc.
  • Page 157: How To Avoid Unnecessary (Nuisance) Fire Alarms

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x How to avoid unnecessary (nuisance) fire alarms We all realise, when life, buildings, production facilities, etc. shall be saved, it is of utmost importance that an initial fire is detected as soon as possible.
  • Page 158 Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Exhausts Exhausts from cars / trucks, lift trucks, lawn mowers, etc. influences smoke detectors (sensors). If windows and doors are open, exhausts can "slip in" that way.
  • Page 159: Information Regarding Radioactive Radiation Source

    Operating Instructions Fire alarm system EBL512 G3, V1.1.x Information regarding radioactive radiation source Today, Panasonic have no ionization smoke detectors but old detectors connected to the EBL512 G3 installation might contain old smoke sensors / detectors of the ionization type. They contain a small radioactive radiation source, normally Americium 241.
  • Page 160: Revision History

    Panasonic Electric Works Nordic AB MEW01349 Rev: - Operating Instructions Fire alarm system EBL512 G3, V1.1.x Revision history...
  • Page 161 This page has deliberately been left blank.
  • Page 162 Panasonic Electric Works Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 [email protected] • www.panasonic-fire-security.com...

This manual is also suitable for: