Panasonic EBL512 Operating Instructions Manual
Panasonic EBL512 Operating Instructions Manual

Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Quick Links

Operating Instructions
MEW00748
Revision 1
Fire Alarm System EBL512
V2.3.x
Author:
Jan Pettersson
Date of issue: 2006-03-22
Date of rev:
2006-10-12
Table of Contents
loading

Summary of Contents for Panasonic EBL512

  • Page 1 Operating Instructions MEW00748 Revision 1 Fire Alarm System EBL512 V2.3.x Author: Jan Pettersson Date of issue: 2006-03-22 Date of rev: 2006-10-12...
  • Page 2 This page has deliberately been left blank.
  • Page 3: Table Of Contents

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Table of contents Introduction________________________________ 7 Definitions / Explanations ____________________ 8 PEWF&STE AB ___________________________________ 8 Alarm points ______________________________________ 8 2.2.1 Smoke detector _______________________________ 8 2.2.2...
  • Page 4 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Control Unit ______________________________ 14 LED indicators and push buttons _____________ 16 Normal operation __________________________ 20 Alphanumeric display in the control unit _______________ 20...
  • Page 5 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 15.2.5 Co-incidence alarm ___________________________ 43 15.3 Heavy smoke / heat alarm reset_______________________ 43 15.4 Key cabinet alarm reset _____________________________ 43 Fault _____________________________________ 44 16.1...
  • Page 6 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.5.1 Reset of a week average sensor value _____________ 94 26.5.2 Algorithm setting via menu H4/U5 _______________ 95 26.6 Sensors activating SERVICE signal (H4/U6) ___________ 100 26.7...
  • Page 7 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Replacing a TLON connection board and/or a main board 141 Battery maintenance_______________________ 142 How to avoid unnecessary (nuisance) fire alarms143 Information regarding radioactive radiation source145...
  • Page 8 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x...
  • Page 9: Introduction

    2.3.x. On the date / rev date of the document x = 1. Since the EBL512 control unit (c.i.e.) is produced for many countries the look, the texts, the functions, etc. might vary. Products Consists of one or more parts (HW) according to a Product Parts List.
  • Page 10: Definitions / Explanations

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. PEWF&STE AB Panasonic Electric Works Fire &...
  • Page 11: Addressable

    It starts in the C.U. and it returns back to the C.U. BS4 loop Loop = a cable, with two wires, to which all the addressable Autronica (BS100) units can be connected. It starts in the C.U. (EBL512) and it returns back to the C.U.
  • Page 12: Control Unit (C.u.) / C.i.e

    Control Unit (C.U.) / C.I.E. Control Unit = C.U. = Control and Indicating Equipment = Unit to which the alarm points are connected, e.g. EBL512. Indicates fire alarm, fault condition, etc. Fire Brigade Panel & Control Panel (see below) included or not included. Printer included or not included.
  • Page 13: Led

    Normally alphanumeric characters and backlight. 2.17 Door open / Key Switch In most EBL512 configurations there is a door Switch which is activated when the control unit door is opened. In some configurations does a key Switch replace this door Switch.
  • Page 14: Overview

    TLON network, a "system", with up to 30 control units. Each control unit has access to all information. EBL512 is designed according to the European standard EN54, part 2 and 4. The front conforms with SS3654.
  • Page 15: S/W Versions

    Win512 shall have the same (or higher) version number as the EBL512 S/W version number (e.g. 2.2). Backup require the same version number (in Win512 and EBL512). Old files can be opened and saved in a higher version of Win512 and thereafter downloaded.
  • Page 16: Control Unit

    Operating Instructions Fire alarm system EBL512 V2.3.x Control Unit Figure 1. The EBL512 Control Unit (1548 / 1549). The look might vary according to configuration, country, etc. The control unit (c.i.e.) is housed in a grey metal cabinet. The door has a Plexiglas ahead of the FBP part, see Figure 1.
  • Page 17 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x The fire brigade personnel use the FBP to see which alarm point / zone(s) having generated fire alarm. In the alphanumeric display...
  • Page 18: Led Indicators And Push Buttons

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x LED indicators and push buttons LEDs and push buttons can vary according to type and configuration (convention / country / language).
  • Page 19 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Push buttons on the Fire Brigade Panel (FBP) Push button Operation/function Alarms queued (black) Used, when LEDs "Alarms queued" (L2) are lit, to scroll/browse through the queued alarms (zones).
  • Page 20 Blinking: One or more supervised outputs (type 3 = alarm device) have generated fault(s). System fault (yellow) EBL512 is not running (because of S/W / CPU / memory fault). Fault / Disablements Output(s) for fire brigade tx (routing equipment)
  • Page 21 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Push buttons / Keypad on the Control Panel (CP) Key/push button Operation/function Fault acknowledge Used to acknowledge the faults shown in menu H6. Also used (yellow) to acknowledge SERVICE signal, see menu H8/S4.
  • Page 22: Normal Operation

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Normal operation When the control unit / system is in normal operation, i.e. no fire alarms and normally no faults, no disablements, no service signal, no zones in test mode, no activated interlocking in / outputs and/or no open doors, only the LED "Operation"...
  • Page 23: Access Levels

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Access levels The control unit has six access levels for different kind of users. Access level 0 Door closed Anybody Scroll / browse through...
  • Page 24: Access Level 2

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x NOTE! In conjunction with a fire alarm, the fire brigade personnel can use "P8" (without any access code) to get access to the menu X1 to scroll through all the fire alarms (e.g.
  • Page 25: Access Level 3

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x H9 Interlocking outputs and inputs C1 Activated interlocking outputs/inputs C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output C5 Re-enable interlocking output H10 Change access code for daily duties (access level 2).
  • Page 26: Access Level 4

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Access level 4 From access level 2 , the user can logon to access level 4, which gives access to the following menus, normally used by Service /...
  • Page 27: "Silence Alarm Devices

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x "Silence Alarm devices" In the control unit (on the FBP) there is a push button (P3) "Silence Alarm devices". If the push button "Silence Alarm devices" is pressed during a pre-...
  • Page 28: "Silence Buzzer

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x "Silence buzzer" The buzzer in the control unit will sound for: • pre-warning (0.8 / 5 sec.) • 2-zone dependent or 2-unit dependent fire alarm: When only one zone or one zone / address (alarm point) is in alarm status (0.8 / 5...
  • Page 29: Disable / Re-Enable All Control, Extinguishing And Ventilation Outputs

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Disable / Re-enable all control, extinguishing and ventilation outputs All control outputs programmed as type: 0 = control (general) 1 = fire ventilation 2 = extinguishing system …...
  • Page 30: Evacuate

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Evacuate This function is only valid for the Belgian, British Standard, Hungarian and Ukrainian conventions (S/W version > 2.2.3). A front with the push button "Evacuate"...
  • Page 31: Door Open

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Door open A special key is used to open the control unit door to get access to the front / system, see chapter "Access levels", page 21. The same type of key is also used to open the ext.
  • Page 32: Technical Number / Presentation Number

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Technical number / Presentation number 13.1 Technical number for COM loop units The technical number, NNNNNN, is used when programming all units connected to the COM loops.
  • Page 33: Technical Number For Bs4 Loop Units

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 13.2 Technical number for BS4 loop units Autronica interface board 1584 (four BS4 loops) is required in the control unit. The technical number, NNNNNN, is used when programming all units connected to the BS4 loops.
  • Page 34: Presentation Number

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 13.3 Presentation number For each fire alarm point / input / zone, a presentation number, NNN-NN, has to be programmed. The presentation number is shown in the c.i.e.
  • Page 35: Alarm Types

    Example; pre-warning zone 123, address 45 (within zone 123): Pre-warning detector 123/45 (user definable text message) See EBL512 Planning Instructions. Any programmable input can also be used to activate a pre-warning. Regarding the BS4 exp. board 1584 for Autronica devices (BS4 loops), pre- warning can also be generated by detector(s) connected to address units.
  • Page 36: Fire Alarm

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Example; pre-warning zone 123: Pre-warning zone 123 (user definable text message) If more than one pre-warning are generated, the LEDs "Alarms queued"...
  • Page 37: Fire Alarm Menu (X1-X7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Only one alarm point in each zone POINT: 123-45 LAST: 789-01 No.:003 User definable text message for 123-45 LAST = The most recent zone-address that has activated fire alarm.
  • Page 38 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x The original presentation (the user definable text message) will be automatically displayed again, 20 seconds after the latest time any of the push buttons "A", "...
  • Page 39: Alert Annunciation (Aa Alarm)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x ZONE: 123 LAST: 789 No.: 003 Disable zone: 000 ACCEPT? Write zone number and press "A". If more zones are to be disabled, repeat the procedure.
  • Page 40: 2-Zone / Address Dependence (Co-Incidence Alarm)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x information regarding the AA function. Acknowledgement and reset of the AA alarm can be done on a Display unit 2235 , an AA unit 1735 / 1736 or an AA controller 1740.
  • Page 41: Key Cabinet Alarm

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x • Outputs programmed for heavy smoke / heat alarm are activated. • Each heavy smoke / heat alarm is printed , e.g.:...
  • Page 42: Key Cabinet Opened In Conjunction With A Fire Alarm

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x This alarm will also generate a fault message, see chapter "Key cabinet alarm reset", page 43. It is indicated by LED "Fault" (L8).
  • Page 43: Alarm Reset

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Alarm reset 15.1 Pre-warning reset Pre-warning is automatically reset. 15.2 Fire alarm reset NOTE! The detectors having activated fire alarm shall, after reset, be inspected, tested and replaced when required.
  • Page 44: Single Encapsulated Reset (Zone/Detector Not Reset)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x display, on the first row to the left. It has to be reset the same way as the first one. When all fire alarms are reset, LEDs "Fire" (L1) and "Alarms queued"...
  • Page 45: Co-Incidence Alarm

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 15.2.5 Co-incidence alarm Co-incidence alarm is automatically reset (i.e. when the zone / alarm point is no longer in alarm status). See also chapter "2-zone / address dependence (co-incidence alarm)", page 38.
  • Page 46: Fault

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Fault In case of a fault condition, the following has happened / will happen in the control unit: • The buzzer in the c.i.e. sounds continuously (steady ON).
  • Page 47: Fault Messages

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 16.1 Fault messages Below follows a list of all fault messages, in alphabetical order: FAULT: 1580 8 zones board x, CU xx (8 zones expansion board, DET8) Fault on / no communication to 1580 board No.
  • Page 48 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT: 1587-board x, CU xx (External Fire Brigade Panel / DU interface board) Fault on / no communication to 1587 board No. x in control unit No.
  • Page 49 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x blown. • Other battery fuse is blown (e.g. when the batteries are placed outside the control unit). FAULT: Battery output unit xxxxxx Check the output unit battery / connections / fuse F3 (on the power supply board) in the output unit.
  • Page 50 (n)" FBP will not work. FAULT: Configuration control unit xx Fault in the SSI = EBL512 settings downloaded from Win512. FAULT: CU xx has no contact with CU xx Can be shown in conjunction with new S/W download.
  • Page 51 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x This is indicating a single break on the loop. Communication has to be performed in both directions, to find all the units.
  • Page 52 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT:Cut-off loop x, CU xx,ASF 2<->CU FAULT:Cut-off loop x, CU xx,ASF 1<->CU FAULT:Cut-off loop x, CU xx,ASF 0<->CU This is indicating a single break on the COM loop "x" when one or more short circuit isolators 2370, ASF, are connected on the loop.
  • Page 53 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT: External FBP x, board x, CU xx The control unit (i.e. the 1582 board) can not communicate with the ext. FBP (or data converter).
  • Page 54 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT: Fuse, 1587-board x, CU xx (External Fire Brigade Panel / DU interface board 1587) Check for blown fuses on the 1587 board.
  • Page 55 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x fire alarms in the system. FAULT: L-C mixed COM-loop x, CU xx The two wires L (SA) and C (SB) have been mixed (alternated). Check so that the wire connections are correct according to drawing 512-41.
  • Page 56 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT: Low voltage, output unit xxxxxx The external power supply's system voltage < 21 V DC. Check / adjust so that the rectifier output voltage is 24 V DC.
  • Page 57 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x • Check the unit's address. (DIL-Switch in some unit or with programming tool 3314 in some units). • Faulty unit. • Detector removed from its base.
  • Page 58 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT: Sensor techn. no. xxxxxx • The sensor 22xx / 23xx is removed from its sensor base 2210 / 2312. • Faulty sensor.
  • Page 59 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x FAULT:Sh-circ. loop x, CU xx, ASF5<->CU FAULT:Sh-circ. loop x, CU xx, ASF4<->CU FAULT:Sh-circ. loop x, CU xx, ASF3<->CU FAULT:Sh-circ. loop x, CU xx, ASF2<->CU FAULT:Sh-circ.
  • Page 60 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x If the output is programmed for fire brigade tx (type 4 = routing equipment), it is also indicated by LED "Fault / Disablements Fire brigade tx"...
  • Page 61 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Zone interface 2226: No ext. power supply. Multi purpose I/O unit 3361, monitored zone line (input Z): break on a wire or wrong / no end-of-line capacitor / short circuit (if not programmed for fire alarm at short circuit).
  • Page 62: Fault Acknowledge

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 16.2 Fault acknowledge The LEDs "Fault tx activated" (L11) and "General fault" (L7) are turned ON (LEDs "Fault / Disablements Alarm devices" (L13), "System fault"...
  • Page 63: Commissioning An Installation

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Commissioning an installation Before you connect the power supply to a control unit, all other cable connections shall be made. Check once more that they are correct.
  • Page 64: Tlon Network Programming (Configuration)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x See also chapter "Calibration of supervised outputs (H5/A1)", page 105. When all control units are running (power supplied) , the TLON network programming (configuration) has to be done before the site specific data (SSD) can be downloaded, see chapter "Programming...
  • Page 65: Programming (Ssd Download)

    Programming (SSD download) The PC program Win512 is used for programming the site specific data (SSD) and to download it into the EBL512 control unit(s) and/or 1728, 1735 / 1736 & 1826 / 1828 units connected to an Ext. FBP/DU interface board 1587.
  • Page 66: Control Units In A Tlon Network

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Now, an automatic reset/restart will take place (see chapter "Restart", page 69. If the download was not okey the following text message will be shown: Checksum fault in downloaded data.
  • Page 67 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x See also chapter "Fire alarm", page 34. Unique user definable text messages for each alarm point and each zone line input can also be shown in Display units (2235 / 2236) connected on the COM loops.
  • Page 68: New System Program (S/W) Version Download

    Operating Instructions Fire alarm system EBL512 V2.3.x New system program (S/W) version download The latest version of the EBL512 S/W (system program) is factory downloaded before the delivery. Due to continual development and improvement, different S/W versions can be found.
  • Page 69: Control Units In A Tlon Network

    S/W and text file respectively. Close the dialog box. 7. Open the "Tools" menu and open the "EBL512 settings" dialog box. See "3" & "4" above. Click "Read". In the log view will be shown: "System information has been uploaded".
  • Page 70: Ebl512 Settings Download

    Date (normally not changed) • Adhesive type (Type 1 = "old", Type 2 = "new"; acc. to EN54) If you wish to download new EBL512 settings, a PC and Win512 are used. Before download, the PC has to be connected to the "D"...
  • Page 71: Restart

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Restart A restart will delete or not delete the data in the control unit. Here follow an explanation of the different data, abbreviations and a table showing how the data respectively is affected.
  • Page 72 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x The "restart" begins and will last for up to 2 minutes. During this 2 minutes period, no fire alarm can be activated and the following text messages will be show in the alphanumeric display: Checking program memory..
  • Page 73: Boot Menu

    Clear memory menu be shown again. Press "Return" go back to the Boot menu. NOTE! After clearing the SSW, perform a "Power off / power on" reset / restart directly. Can also be done in Win512, EBL512 settings dialog box, "Clear SSD".
  • Page 74: Access

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Access To be able to use the key pad in the control unit (to get access to the menu tree), it is necessary to login with an access code for level 2 ,3 or 4.
  • Page 75: Perform Monthly Test (H1)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Perform monthly test (H1) The control unit and the installation shall be tested on a regular basis. If one twelfth of the alarm points are tested each month, the whole installation will be tested after one year.
  • Page 76 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press "Return"...
  • Page 77: Disable Or Re-Enable (H2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Disable or re-enable (H2) A whole zone, one or more alarm points within a zone and/or control outputs can be disabled via menus H2/B1-B3. This possibility can be used when a temporary disablement is wanted (e.g.
  • Page 78: Disable Zone (H2/B1)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.1 Disable zone (H2/B1) When a whole zone is disabled, all alarm points within the zone are disabled except the addressable manual call points.
  • Page 79: Disable Zone / Address (H2/B2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.2 Disable zone / address (H2/B2) Addressable alarm points (also addressable manual call points), connected to the COM loop, can be individually disabled.
  • Page 80: Disable Control Output (H2/B3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.3 Disable control output (H2/B3) Control outputs can be individually disabled. Disabled output will stay in (or return to) the normal condition for the output respectively.
  • Page 81 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x "A" If more disablements Disable output control unit: 00 Type: 0 shall be done, continue 0=Loopunit 1=S 2=R 3=RE 4=ES ACCEPT? like above.
  • Page 82: Re-Enable Zone (H2/B4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.4 Re-enable zone (H2/B4) Disabled zones are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 83: Re-Enable Zone / Address (H2/B5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.5 Re-enable zone / address (H2/B5) Disabled alarm points, zone / addresses, are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 84: Re-Enable Control Output (H2/B6)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.6 Re-enable control output (H2/B6) Disabled outputs are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 85 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x "A" If more re-enablements Re-enable control output type: 0 shall be done, continue like 0=Loopunit 1=S 2=R 3=RE 4=ES ACCEPT? above. If not, press "Return"...
  • Page 86: Re-Enable Non-Reset Zone / Address (H2/B7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.7 Re-enable non-reset zone / address (H2/B7) See chapter "Single encapsulated reset (Zone/Detector not reset)", page 42. LED "Disablements" (L8) blinking is indicating that one or more alarm points have been "encapsulated"...
  • Page 87: Disable / Re-Enable All Control, Exting. And Ventilation Outputs (H2/B8)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.8 Disable / Re-enable all control, exting. and ventilation outputs (H2/B8) Outputs programmed as type 0 = control (general), type 1 = fire...
  • Page 88: Disable / Re-Enable Alarm Devices (H2/B9)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 24.9 Disable / Re-enable alarm devices (H2/B9) Outputs programmed as type 3 = alarm device (sounder) can be disabled all at the same time. Disabled alarm devices means that even if the control expression (trigger condition) for output respectively is fulfilled, the output will not be activated.
  • Page 89: Set Calendar And Clock (H3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Set calendar and clock (H3) The RTC component has a built-in battery. Normally, date, day of the week and time don't have to be set, except when the control unit is powered for the first time but if required, the clock might be corrected, so that the "time stamps"...
  • Page 90: Present System Status On Display And Printer (H4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Present system status on display and printer (H4) A printer is factory mounted in control unit 1549. Printer 1558 is an option for control unit 1548.
  • Page 91: Disablement By Time Channel (H4/U2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.2 Disablement by time channel (H4/U2) A list of all disablements by time channel(s) in the system. From this menu, it is also possible to get a print-out.
  • Page 92: Doors Open (H4/U3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.3 Doors open (H4/U3) The LED "Door open" (L10) is lit, to indicate that one or more doors are open. See chapter "Door open", page 29.
  • Page 93: Activated 2-Zone/Address Dependent Zone/Address (H4/U4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.4 Activated 2-zone/address dependent zone/address (H4/U4) ("Two unit dependent" in Win512): When only one zone or one zone / address (alarm point) is in alarm status , the LEDs "Fire"...
  • Page 94: Sensor Values (H4/U5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.5 Sensor values (H4/U5) The very first week average sensor value is calculated within 2 minutes after SSD download & restart. During these 2 minutes can no fire alarm be activated and the sensor value "000"...
  • Page 95 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Sensor: 00000N " " Current algorithm: nnnnnn Sensor: 00000N Min: XX°C " " Momentary: XX°C Max: XX°C Sensor: 00000N " "...
  • Page 96: Reset Of A Week Average Sensor Value

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Algorithm Short name (nnnnnn) Normal sensitivity & Normal detection (15 s) N-15 High sensitivity & Normal detection (15 s) H-15 Low sensitivity & Normal detection (15 s) L-15 Normal sensitivity &...
  • Page 97: Algorithm Setting Via Menu H4/U5

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.5.2 Algorithm setting via menu H4/U5 NOTE! Algorithm setting via menu H4/U5 is only valid for the "British Standard Marine Application" convention.
  • Page 98 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Show sensor values and setting alarm algorithm for the Analog photo electric detector 3304: Text in display Comments "Access" According to chapter "Access", see page 72.
  • Page 99 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Algorithm for sensor 000001 is changed "A" from N-15 to N-35 Enter technical number: 000000 "Return" Write the sensor's techn. number and/or press "A"...
  • Page 100 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Sensor values and setting alarm algorithm for the Analog heat detector 3308 / 3309: Text in display Comments "Access" According to chapter "Access", see page 72.
  • Page 101 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Enter technical number: 000000 "Return" Write the sensor's techn. number and/or press "A" to accept or press "Return" to carry out the change of algorithm(s).
  • Page 102: Sensors Activating Service Signal (H4/U6)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.6 Sensors activating SERVICE signal (H4/U6) Service signal is indicated by LED "Service" (L12). The sensor week average value is below or over the service level respectively for one or more sensors.
  • Page 103: Event Log (H4/U7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.7 Event log (H4/U7) This is a list of events. Type and number of events in the list, etc. can be set in Win512 (see Planning Instructions and Win512 help).
  • Page 104: Configuration (H4/U8)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 26.8 Configuration (H4/U8) In a control unit the menu H4/U8 can be used to see the following settings (made in Win512, "Tools" menu) for that specific control unit: Number of addresses that can be used, i.e.
  • Page 105: Service (H5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Service (H5) When commissioning an installation and by maintenance (power on and programming a control unit / a system), menu H5 is used to get certain information and help.
  • Page 106: Access Code For Service (H5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.1 Access code for service (H5) Access code to level 4 is required. If login to level 2 was made with code for level 4, no code is required here.
  • Page 107: Calibration Of Supervised Outputs (H5/A1)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.2 Calibration of supervised outputs (H5/A1) The voltage outputs (S0-S3) in each control unit are supervised (monitored), as well as the outputs (0-3) in each output unit type 2262 and 2263.
  • Page 108: Sensitive Fault Detection Mode (H5/A2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.3 Sensitive fault detection mode (H5/A2) To increase the possibilities to detect faults during the commissioning, it is possible to use the "Sensitive fault detection mode. (The time delay for each fault will be reduced).
  • Page 109: Direction For Communication On Com-/Bs4-Loop (H5/A3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.4 Direction for communication on COM-/BS4- loop (H5/A3) The communication direction is normally automatically changed every minute, to ensure that the wires are okay all the way. To make trouble shooting easier (e.g.
  • Page 110: Show Information About Site Specific Data (H5/A4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.5 Show information about Site Specific Data (H5/A4) Information regarding the current site specific data (SSD) is shown. New SSD can be downloaded via a PC and Win512.
  • Page 111: Display Current Consumption In Unit (H5/A5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.6 Display current consumption in unit (H5/A5) The resolution is not very high, i.e. the displayed values give only a rough idea of the current consumption.
  • Page 112: Display Current Consumption Com-/Bs4-Loop (H5/A6)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.7 Display current consumption COM-/BS4- loop (H5/A6) The resolution is not very high, i.e. the displayed values give only a rough idea of the current consumption.
  • Page 113: Display Statistics For Com-Loop (H5/A7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.8 Display statistics for COM-loop (H5/A7) The statistics can be used during commissioning, service, etc. Pollings are the number of pollings ("questions") sent out by the control unit to the units connected on the COM loop.
  • Page 114: Select Unit On Com-Loop To Use For Trigging (H5/A8)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.9 Select unit on COM-loop to use for trigging (H5/A8) This function is used by service engineer and by R&D for troubleshooting.
  • Page 115: Activate Address Setting Mode For Du (H5/A9)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.10 Activate address setting mode for DU (H5/A9) This function can be used by commissioning / service engineer to activate the address setting mode in the following Display Units connected to an Ext.
  • Page 116: Change Access Code For Pc-Communication (H5/A10)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.11 Change access code for PC- communication (H5/A10) As a protection against unauthorised personnel programming the system (via Win512), an access code (level 5) for PC-connection is required.
  • Page 117: Change Access Code For Service (H5/A11)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 27.12 Change access code for service (H5/A11) For security reasons, the default code should be changed. Action Text in display Comments "Access"...
  • Page 118: Acknowledge Faults (H6)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Acknowledge FAULTS (H6) Regarding fault indication, etc., see chapter "Fault", page 44. See also chapter "Fault acknowledge", page 60. All faults (i.e. not acknowledged faults, acknowledged faults and corrected faults) are stored in the event log and can be listed, see chapter "Event log (H4/U7)", page 101.
  • Page 119: Perform Zone Test (Test Mode) (H7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Perform ZONE TEST (test mode) (H7) Normally, zones are tested during the monthly test via menu H1. Via this menu (H7) it is possible to perform the zone test solely.
  • Page 120 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x After 60 minutes or You are no longer in menu Zones in test mode: 001, 002, 003, 004 "Return" H7 but still in test mode.
  • Page 121: Maintenance (H8)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Maintenance (H8) 30.1 Access code for maintenance Access code for access level 3 is required for menu H8. NOTE! If login to level 2 was made with code for level 3 or 4, no code to access level 3 is required here.
  • Page 122 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.2 Disable or re-enable outputs for routing equipment (H8/S1) Outputs for routing equipment (fire brigade tx / fault tx) can be disabled via this menu.
  • Page 123: Disconnect Loop (H8/S2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.3 Disconnect loop (H8/S2) Before physical connection / disconnection of loop units, etc. the loop (or zone line) shall be disconnected (disabled), i.e. there will be no voltage on the "loop"...
  • Page 124: Re-Connect Loop (H8/S3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Don’t forget to re-connect the loop / zone line again, via menu H8/S3. 30.4 Re-connect loop (H8/S3) Disconnected (disabled) loops / zone lines (via menu H8/S2) are indicated by LED "Disablements"...
  • Page 125: Acknowledge Service Signal (H8/S4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.5 Acknowledge SERVICE signal (H8/S4) See chapter "Sensors activating SERVICE signal (H4/U6)", page 100. When service signal from a sensor is acknowledged, the sensor is given a default sensor value (for a new / clean sensor), i.e.
  • Page 126: Clear Weekly Average (H8/S5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.6 Clear weekly average (H8/S5) If a sensor (analog smoke detector) is replaced without having generated SERVICE signal, its week average sensor value has to be set to the default value otherwise the new / clean sensor will inherit the old sensor's value.
  • Page 127: Activate Alert Annunciation Function (H8/S6)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.7 De-activate alert annunciation function (H8/S6) Normal function (1): For alarm points / zones programmed for Alert Annunciation (via Win512) is normally this function enabled via a time channel, e.g.
  • Page 128: Test Alarm Devices (H8/S7)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.8 Test alarm devices (H8/S7) The programmable outputs type "Alarm device" can be collectively activated via this menu (H8/S7), which make it possible to test the alarm devices.
  • Page 129: Safe Shut Down Of Control Unit (H8/S8)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.9 Safe shut down of control unit (H8/S8) It's not recommended to power off a control unit (i.e. no 230 V AC and no battery) without first doing a safe shut down of control unit.
  • Page 130: Activate Address In Alarm Mode (H8/S9)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.10 Activate address in alarm mode (H8/S9) One alarm point (address), not a whole zone, can be set in alarm status. The built-in LED in the alarm point (detector) will be turned on to indicate the alarm.
  • Page 131 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Alternative a) Scroll or press "Return" to Activate address in alarm mode menu H8. Scroll or press ACCEPT? "Reset" "Return" to log off.
  • Page 132: Synchronize The Control Units (H8/S10)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.11 Synchronize the control units (H8/S10) Synchronization can also be done via Win512. The control units have to be synchronized when: •...
  • Page 133 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x "A" Press "Return" to menu Shall synchronization be started? 0 S10. (Or press "1" and (1 = Yes, 0 = No) ACCEPT? "A"...
  • Page 134: Change Access Code For Maintenance (H8/S11)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 30.12 Change access code for maintenance (H8/S11) For security reasons, the default code should be changed. Action Text in display Comments "Access"...
  • Page 135: Interlocking Outputs And Inputs (H9)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Interlocking outputs and inputs (H9) 31.1 Activated interlocking outputs/inputs (H9/C1) (In the Chinese convention the information is shown in Kanji characters. In the Chinese convention, the LED "Input" is indicating one or more activated interlocking inputs.
  • Page 136: Activate Interlocking Output (H9/C2)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 31.2 Activate interlocking output (H9/C2) The output in each interlocking combination (area / point) can be manually activated via this menu. The corresponding interlocking input will be "monitored"...
  • Page 137: Reset Interlocking Output (H9/C3)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 31.3 Reset interlocking output (H9/C3) All activated interlocking outputs are listed in this menu. Interlocking output activated via its control expression and with latching output selected (in Win512): The output has to be reset via this menu.
  • Page 138: Disable Interlocking Output (H9/C4)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 31.4 Disable interlocking output (H9/C4) Interlocking outputs (Type = Interlocking) can be disabled via this menu but not via menu H2/B3.
  • Page 139: Re-Enable Interlocking Output (H9/C5)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x 31.5 Re-enable interlocking output (H9/C5) Disabled interlocking outputs are listed in menu H4/U1 from which it is also possible to get a print-out.
  • Page 140: Change Access Code For Daily Duties (H10)

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Change access code for daily duties (H10) For security reasons, the default code should be changed. Action Text in display Comments "Access"...
  • Page 141: Annual Control

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Annual control The building occupier is highly recommended, once a year, to do some tests, beside the monthly tests. To avoid the Fault tx output(s) to be activated, they can be disabled via menu H8/S1 (or via an open door, se chapter "Door open", page 29.).
  • Page 142: How To Change Paper In The Printer

    Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x How to change paper in the printer When the paper roll is almost empty, a red line appears on one edge of the paper.
  • Page 143 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Replacing a TLON connection board and/or a main board By the TLON network programming, some unique data will be stored in a memory on the 1590 TLON connection board and some unique data will be stored in a memory on the 1556 main board.
  • Page 144 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Battery maintenance The batteries (2 x 12 V, 24 Ah) are normally placed in the control unit. Larger batteries (< 60 Ah) are placed outside the control unit.
  • Page 145 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x How to avoid unnecessary (nuisance) fire alarms We all realise, when life, buildings, production facilities, etc. shall be saved, it is of utmost importance that an initial fire is detected as soon as possible.
  • Page 146 Lack of maintenance Smoke detectors (sensors) are influenced by their environment and become "dirty". In an analog system (like EBL512) a Service signal is given when it is time to clean or exchange the smoke detectors (sensors). The alternative is to exchange detectors at even intervals, to be on the safe side.
  • Page 147 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Information regarding radioactive radiation source The installation might contain old smoke sensors / detectors of the ionization type. They contain a small radioactive radiation source, Americium 241.
  • Page 148 Panasonic Electric Works Fire & Security Technology Europe AB MEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x Revision history Revision 1 Information added / revised in the following chapters / paragraphs: New picture. 16.1 FAULT: Low battey capacity: Info added.
  • Page 149 This page has deliberately been left blank.
  • Page 150 Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 [email protected] • www.panasonic-fire-security.com...