3. GENERAL DESCRIPTION

EBL512 G3 is a microprocessor controlled intelligent fire alarm system, intended for analog addressable detectors, as well as
conventional detectors and manual call points. It is possible to connect four loops for addressable units. On each COM loop it is
possible to connect up to four SUB-loops. Programmable control outputs and output units are available.
G3 can have up to 1012 addresses, of which up to 512 can be alarm points - according to EN54-2.
EBL512 G3 can be used as a stand-alone control unit or connected to a network. A network can have up to 30 control units.
EBL512 G3 is available in several types, versions and configurations.
TECHNICAL NUMBER
The technical number, NNNNNN, is used when programming all units connected to the COM loops. Technical number is also used
to identify which unit has generated a fault.
PRESENTATION NUMBER
Each fire alarm point / input / zone has a presentation number, NNN-NN. The presentation number is shown in the c.i.e. display to
identify the point / zone activating fire alarm.
COM LOOP UNITS
Addressable COM loop units are connected directly to a COM loop.