Emerson Firetrol XG FTA550 Series Assembly, Installation And Operation Instructions

Jockey pump controller

Quick Links

Installation and Operation Instructions
FTA550 Series
Jockey XG Pump Controllers
NS550-01
ECN 237139
Table of Contents
loading

Summary of Contents for Emerson Firetrol XG FTA550 Series

  • Page 1 Installation and Operation Instructions FTA550 Series Jockey XG Pump Controllers NS550-01 ECN 237139...
  • Page 2: Table Of Contents

    Table of Contents INTRODUCTION ...........................1 MOUNTING CONTROLLER ......................1 MAKING ELECTRICAL CONNECTIONS ...................2 MAKING SYSTEM PRESSURE CONNECTIONS .................2 GENERAL START UP OPERATION ....................3 PROGRAMMING THE JOCKEY XG User Interface and Display ....................4 User Menu Structure......................5 Programming Notes ......................6 MAIN MENU - SETTINGS System Setup Display Brightness ........................7...
  • Page 3 Motor & Power Phase Margin ......................9 Feature Settings Low Pressure Audible ....................9 Pump Run Alarm ......................9 User Input ........................10 Cycle Interval ......................10 Operators Choice 1 ....................10 Operators Choice 2 ....................10 Reset Cycle Counts ....................10 Option Settings .......................11 MAIN MENU - EVENT LOG ......................11 MAIN MENU - DATA HISTORY ......................11 MAIN MENU - FACTORY Confi...
  • Page 4: Introduction

    DANGER RISK OF ELECTROCUTION Personal injury or death could occur. Ensure all power is disconnected before installing or servicing this equipment. DANGER DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED! DEATH, PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE MAY RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.
  • Page 5: Making Electrical Connections

    2. Drill and put anchors into the wall for the lower mounting brackets. 3. Mark on the wall, the location of the holes in the upper mounting brackets. 4. Drill and put anchors into wall for the upper mounting brackets. 5.
  • Page 6: General Start Up Operation

    GENERAL START UP OPERATION Voltage Check— 1. Put the HAND-OFF-AUTO Selector Switch in the “OFF” Position. 2. Energize the incoming power feeder. WARNING RISK OF ELECTRICAL SHOCK Personal injury could occur. Service must be done with door open and power on.
  • Page 7: User Interface And Display

    Jockey User Interface and Display Directional Arrows Informational Display Used to go up and down in menu Status and System Pressure screens and change user defi ned User Choice 1 values User Choice 2 Switch Position Silence Alarm Button Active Alarms - Primary Status Notifi cation Used to silence audible alarm Date-Time or Active Timer System Status LED’s...
  • Page 8: User Menu Structure

    Mark II User Menu Structure Main Menu Settings System Setup Date & Time Timers Feat. Settings Opt. Settings Pressure Phase Margin Low Press. Aud. Display Time On Delay Time Units (As ordered Setting Pump Run with controller) Language/Units Date Min. Run Time Start User Input Passwords...
  • Page 9: Programming Notes

    Programming Notes The Firetrol Jockey is multi-level password protected. User programmable functions are protected by a Level 1 password. LEVEL 1 PASSWORD 2 - 1 - 1 - 2 Indicates the level of password required to modify a setting. Note: Many menu settings feature an “enable/disable” option. These options are indicated by a “”...
  • Page 10: System Setup Display Brightness

    Jockey User Menu Settings Note: Many menu settings feature an “enable/disable” option. These options are indicated by a "” for enabled or a “x” for disabled. Indicates the level of password required to modify setting. System Setup - Display SYSTEM SETUP SETTINGS DISPLAY BRIGHTNESS...
  • Page 11: Daylight Saving

    SETTINGS DATE & TIME DAYLIGHT SAVING arrows to enable or disable automatic Daylight Saving time adjustments. Press to confi rm. arrows to set number of minutes to adjust for at the beginning or end of Daylight Saving (+/-) time. Press to confi...
  • Page 12: Overpressure Alarm

    SETTINGS PRESSURE OVERPRESSURE ALARM arrows to enable or disable the overpressure alarm feature. Press to confi rm. Limit arrows to set the pressure limit for the overpressure alarm. Press to confi rm. PRESSURE SETTINGS RECORDING - DELTA arrows to set pressure delta recording limit. Press to confi...
  • Page 13 USER INPUT SETTINGS FEATURE SETTINGS ENABLE arrows to enable or disable the user defi ned alarm. Press to confi rm. ON DELAY arrows to select an on delay time before the alarm is acknowledged (0-99 seconds). Press to confi rm. AUDIBLE arrows to select if the user input activates the audible alarm.
  • Page 14 Option Settings SETTINGS OPTION SETTINGS NOTE: The list of available options and the settings associated with them will vary with each controller. Below are the most common user defi ned settings that may appear. AUDIBLE arrows to enable or disable the audible alarm for selected option. Press to confi...
  • Page 15 PHASE SEQUENCE to select required phase sequence (1~, abc, cba). Press to confi rm. PRESSURE SENSOR to enable or disable the use of a pressure sensor (transducer). Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed. USER INPUT NUMBER to select input used for user defi...
  • Page 16 PHASE FAIL arrows to enable the phase failure test. Press to begin test. The phase failure should be indicated. arrows to disable the phase failure test. Press to end test. The phase failure should clear. PHASE REVERSE arrows to enable the phase reversal test. Press to begin test.