Quick Start Guide 00825-0100-4057, Rev EB July 2023 Rosemount 3051G Pressure ™ Transmitter with 4-20mA HART Protocol (Revision ® 5 and 7)
Page 2
(IS) installations. Refer to Rosemount 3051 Pressure Transmitter Manual for more information. This manual is available electronically on Emerson.com. WARNING Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
July 2023 Quick Start Guide WARNING Physical access Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against. Physical security is an important part of any security program and fundamental in protecting your system.
Page 4
Quick Start Guide July 2023 Rosemount 3051G...
HART devices. To access new functionality, download the new device driver. Emerson recommends downloading new device driver files to ensure full functionality. HART Revision 5 and 7 selectable, safety certified, local operator interface, process alerts, scaled variable, configurable alarms, and expanded engineering units.
Figure 2-1: Transmitter mounted in an in-line liquid application 2.1.2 Mount the transmitter in a gas application Procedure 1. Place taps in the top or side of the line. 2. Mount the transmitter beside or above the taps. Rosemount 3051G...
Page 7
July 2023 Quick Start Guide Figure 2-2: Transmitter mounted in an in-line gas application 2.1.3 Mount the transmitter in a steam application Procedure 1. Place taps to the side of the line. 2. Mount the transmitter beside or below the taps. 3.
Page 8
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away. Figure 2-5: In-line gauge low side pressure port Low side pressure port (atmospheric reference) Rosemount 3051G...
Page 9
July 2023 Quick Start Guide 2.3 Set the switches Set Alarm and Security switch configuration before installation as shown in Figure 2-6. • The Alarm switch sets the analog output alarm to high or low. — Default alarm is High. • The Security switch allows (unlocked symbol) or prevents (locked symbol) any configuration of the transmitter.
Page 10
Use shielded twisted pair cable for best results. Use 24 AWG or larger wire that does not exceed 5,000 feet (1500 meters) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing. Rosemount 3051G...
Page 11
July 2023 Quick Start Guide NOTICE Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051 case is properly grounded. Power could damage the test diode in the terminal block. Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Page 12
These grounds are used when the transient protection terminal blocks are installed. Emerson recommends using an 18 AWG or larger wire to connect housing ground to earth ground (internal or external). If the transmitter is currently not wired for power up and...
Page 13
DD are shown in Table 2-1. For Fast Key sequences using legacy DDs, contact your local Emerson representative. NOTICE Emerson recommends installing the latest DD to access the complete functionality. Visit FieldComm Group for information on updating the DD Library.
Page 14
To activate the LOI push any button. LOI button functionality is shown on the bottom corners of the display. See Table 2-1 Figure 2-10 for button operation and menu information. Rosemount 3051G...
Page 15
July 2023 Quick Start Guide Figure 2-9: Internal and External LOI Buttons Internal buttons External buttons Note Figure 2-10 to confirm external button functionality. Table 2-2: LOI Button Operation Button SCROLL Left ENTER Right Quick Start Guide...
Page 16
Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage pressure transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons. Rosemount 3051G...
Page 17
July 2023 Quick Start Guide For instructions using AMS Device Manager, see the Rosemount 3051 HART 7 Reference Manual. Note When performing a zero trim, ensure that the equalization valve is open and all wet legs are filled to the correct level. Procedure Choose your trim procedure.
Page 18
2. Press and hold the zero button for two seconds to perform an analog zero trim. Perform trim with digital zero (option DZ) Procedure 1. Set the transmitter pressure. 2. Press and hold the zero button for two seconds to perform a digital zero trim. Rosemount 3051G...
July 2023 Quick Start Guide 3 Safety instrumented systems installation For Safety Certified installations, please refer to Reference Manual installation procedure and system requirements. Quick Start Guide...
European Directive information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com. 4.2 Ordinary Location Certification...
Page 21
Care must be taken during installation and use to prevent impact and friction. 2. The Rosemount 3051G with the transient terminal block (Option code T1) will not pass the 500VRMS dielectric strength test; this must be considered during installation.
Page 22
CAN/CSA C22.2 No. 213-17 +UPD1 (2018) +UPD2 (2019) +UPD3 (2021), CAN/CSA C22.2 No. 60079-0:19, CAN/CSA C22.2 No. 60079-1:16, ANSI-ISA-12.27.01–2021 XP: CL I, DIV 1, GP B, C, D T5 Markings Ex db IIC T5 Gb SEAL NOT REQUIRED Rosemount 3051G...
Page 23
July 2023 Quick Start Guide DIP: CL II, DIV 1, GP E, F, G; CL III T5; T5:-50 °C ≤ Ta ≤ 85 °C NI: CL I DIV 2 GP ABCD T4 T4: -60 °C ≤ Ta ≤ +70 °C; SINGLE SEAL - TEMP LIMITS PER 03031-1053 TYPE 4X, IP 68 Specific Conditions for Use: 1.
Page 24
10. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking. I1 ATEX Intrinsic Safety BAS00ATEX1166X Certificate: EN60079-0:2012+A11:2013, EN60079-11:2012 Standards: Markings: II 1 G Ex ia IIC T4 Ga (-55 °C ≤ T ≤ +70 °C) Rosemount 3051G...
Page 25
July 2023 Quick Start Guide Table 4-2: Input Parameters HART Voltage U Current I 200 mA Power P 0.9 W Capacitance 0.012 µF Inductance L 0 mH Special Conditions for Safe Use(X): 1. When fitted with a transient suppression terminal block, the equipment is not capable of withstanding the 500V insulation test.
Page 26
I7 IECEx Intrinsic Safety IECEx BAS 12.0071X Certificate: Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: ia IIC T4 Ga (-55 °C ≤ T ≤ +70 °C) Table 4-4: Input Parameters Voltage U Current I 200 mA Rosemount 3051G...
Page 27
July 2023 Quick Start Guide Table 4-4: Input Parameters (continued) Power P 0.9 W Capacitance 0.012 µF Inductance L 0 mH Special Conditions for Safe Use(X): 1. If the apparatus is fitted with optional 90V transient suppressor, it is not capable of withstanding the 500V insulation test required by IEC60079-11.
Page 28
6. End users is not permitted to change any components insides, but to settle the problem in conjunction with manufacturer to avoid damage to the product. 7. When installation, use and maintenance of this product, observe following standards: Rosemount 3051G...
Page 29
July 2023 Quick Start Guide GB3836.13-2013 “Explosive atmospheres-Part 13: Equipment repair, overhaul and reclamation" GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)" GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection an maintenance of electrical installation(other than mines)"...
Page 30
“e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure. 2. The blanking plug shall not be used with an adapter. Rosemount 3051G...
Page 31
July 2023 Quick Start Guide 3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G½ thread forms are only acceptable for existing (legacy) equipment installations. Quick Start Guide...
Quick Start Guide July 2023 6 China RoHS Rosemount 3051G...