Emerson Rosemount 3051 Series Quick Start Manual

Pressure transmitter/flow meter with profibus pa protocol
Hide thumbs Also See for Rosemount 3051 Series:
Quick Start Guide
00825-0100-4797, Rev FD
February 2019
Rosemount
3051 Pressure Transmitter
and Rosemount 3051CF Series Flow
Meter
®
with PROFIBUS
PA Protocol
Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051 Series

  • Page 1 Quick Start Guide 00825-0100-4797, Rev FD February 2019 ™ Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flow Meter ® with PROFIBUS PA Protocol...
  • Page 2 Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries. Contents Mount the transmitter........3 Basic configuration........18 Consider housing rotation......12 Trim the transmitter........21 Set jumpers and switches......13 Product Certifications........22 Connect wiring and power up...... 14 Emerson.com/Rosemount...
  • Page 3 February 2019 Quick Start Guide Mount the transmitter Figure 1-1: Panel Mount Coplanar Flange 5/16 x 1½ panel bolts are customer supplied. Figure 1-2: Pipe Mount Coplanar Flange Quick Start Guide...
  • Page 4 Quick Start Guide February 2019 Figure 1-3: Panel Mount Traditional Flange Figure 1-4: Pipe Mount Traditional Flange ™ Figure 1-5: Panel Mount Rosemount 3051T Emerson.com/Rosemount...
  • Page 5 February 2019 Quick Start Guide Figure 1-6: Pipe Mount Rosemount 3051T Mount the transmitter in liquid applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. Figure 1-7: Mounting the Transmitter in Liquid Applications Coplanar In-line...
  • Page 6: Mounting Options

    1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Fill impulse lines with water. Figure 1-9: Mounting the Transmitter in Steam Applications Coplanar In-line Flow Mounting options Coplanar flange Panel mount Pipe mount Emerson.com/Rosemount...
  • Page 7 February 2019 Quick Start Guide Traditional flange Panel mount Pipe mount Rosemount 3051T Panel mount Pipe mount Panel bolts are customer supplied. Panel bolts are customer supplied. Panel bolts are customer supplied. Quick Start Guide...
  • Page 8 Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1-10 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 9 February 2019 Quick Start Guide 4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1-1 for final torque value. 5. Verify the flange bolts are protruding through the isolator plate before applying pressure. Example Table 1-1: Torque Values for the Coplanar Flange and Flange Adapter Bolts...
  • Page 10 For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met. In-line gage transmitter orientation The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing. The Emerson.com/Rosemount...
  • Page 11 February 2019 Quick Start Guide vent path is between the housing and sensor of the transmitter (see Figure 1-12). Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
  • Page 12 (up to 360° from thread limit). 3. Re-tighten the housing rotation screw (see Figure 2-1). Figure 2-1: Housing Rotation A. Housing rotation screw ( /64-in. hex wrench required) Emerson.com/Rosemount...
  • Page 13 February 2019 Quick Start Guide Set jumpers and switches Security After the transmitter is configured, you may want to protect the configuration data from unwarranted changes. Each transmitter is equipped with a security jumper that can be positioned ON to prevent the accidental or deliberate change of configuration data.
  • Page 14 Be connected to a good earth ground at the power supply end 5. Plug and seal unused conduit connections. 6. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing. 7. Replace the housing cover. Emerson.com/Rosemount...
  • Page 15 February 2019 Quick Start Guide Example Figure 4-1: Terminals A. Power terminals B. Ground terminal Note “NC” is a No Connect terminal (do not use) Quick Start Guide...
  • Page 16 1. Remove the Field Terminals housing cover. 2. Connect the wiring pair and ground as indicated in Figure 4-3. The cable shield should: 3. Be trimmed close and insulated from touching the transmitter housing. 4. Continuously connect to the termination point. Emerson.com/Rosemount...
  • Page 17: Power Supply

    February 2019 Quick Start Guide 5. Be connected to a good earth ground at the power supply end. Figure 4-3: Wiring A. Minimize distance B. Trim shield and insulate C. Ground for transient protection D. Connect shield back to the power supply ground E.
  • Page 18: Basic Configuration

    Engineering units: inches H • Scaling: None Engineering units should be confirmed or configured before installation. Units can be configured for Pressure, Flow or Level measurement. Measurement type, Units, Scaling, and Low Flow Cutoff (when applicable) can be set via either: Emerson.com/Rosemount...
  • Page 19 February 2019 Quick Start Guide • LOI – see Table 5-1 Figure 5-1 • Class 2 master – see Table 5-2 for parameter configuration Configuration tools 5.4.1 Local operator interface (LOI) When ordered, the LOI can be used for commissioning the device. To activate the LOI, push either configuration button located under the top tag of the transmitter.
  • Page 20 3051 specific (rmt4444.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be found on EmersonProcess.com/Rosemount or Profibus.com. Configuration host (Class 2) The appropriate DD or DTM file must be installed in the configuration host. These files can be found at EmersonProcess.com/Rosemount. Emerson.com/Rosemount...
  • Page 21 February 2019 Quick Start Guide Trim the transmitter Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on the sensor to eliminate error due to mounting position or static pressure effects. This can be done by performing a zero trim via: •...
  • Page 22 A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 23 February 2019 Quick Start Guide 2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1) will not pass the 500Vrms dielectric strength test and this must be taken into account during installation. IE USA FISCO Certificate: 1Q4A4.AX Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005 Markings:...
  • Page 24 I1 ATEX Intrinsic Safety and Dust Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-11:2012, EN60079-31:2009 Markings: HART: II 1 G Ex ia IIC Ga T4(–60 °C ≤ T ≤ +60 °C) Fieldbus/PROFIBUS: II 1 G Ex ia IIC Ga T4(–60 °C ≤ T ≤ +60 °C) Emerson.com/Rosemount...
  • Page 25 February 2019 Quick Start Guide DUST: II 1 D Ex ta IIIC T95 °C T 105 °C Da (–20 °C ≤ T ≤ +85 °C) Table 7-2: Input Parameters Parameter HART Fieldbus/PROFIBUS Voltage U 30 V 30 V Current I 200 mA 300 mA Power P...
  • Page 26 –50 °C to +80 °C Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for Emerson.com/Rosemount...
  • Page 27 February 2019 Quick Start Guide installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted. 3. Some variants of the equipment have reduced markings on the nameplate.
  • Page 28 IEC60079-15. This must be taken into account when installing the apparatus. Brazil E2 INMETRO Flameproof Certificate: UL-BR 13.0643X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-1:2009 + Errata 1:2011, ABNT NBR IEC60079-26:2008 + Errata 1:2008 Emerson.com/Rosemount...
  • Page 29 February 2019 Quick Start Guide Markings: Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ T ≤ +65 °C), T5(–50 °C ≤ T ≤ +80 °C) Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected.
  • Page 30 Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ Ta ≤ +65 °C), T5(-50 °C ≤ Ta ≤ +80 °C) Special Conditions for Safe Use (X): 1. The relation between ambient temperature arrange and temperature class is as follows: When used in a combustible dust environment, the maximum ambient temperature is 80 °C. Emerson.com/Rosemount...
  • Page 31 February 2019 Quick Start Guide Temperature class –50 °C ≤ T ≤ +80 °C –50 °C ≤ T ≤ +65 °C When used in a combustible dust environment, the maximum ambient temperature is 80 °C. 2. The earth connection facility in the enclosure should be connected reliably.
  • Page 32 6. The cables between this product and associated apparatus should be shielded cables (the cables must have insulated shield). The shielded cable has to be grounded reliably in a non-hazardous area. Emerson.com/Rosemount...
  • Page 33 February 2019 Quick Start Guide 7. End users are not permitted to change any intern components but to settle the problem in conjunction with the manufacturer to avoid damage to the product. 8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-1997, GB3836.15-2000, GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007 N3 China Type n...
  • Page 34 II 2 G Ex de IIC Gb Table 7-9: Conduit Plug Thread Sizes Thread Identification mark M20 × 1.5 1/2–14 NPT 1/2 NPT Table 7-10: Thread Adapter Thread Sizes Male thread Identification mark M20 × 1.5– 6H 1/2–14 NPT 1/2–14 NPT Emerson.com/Rosemount...
  • Page 35 February 2019 Quick Start Guide Table 7-10: Thread Adapter Thread Sizes (continued) Male thread Identification mark 3/4–14 NPT 3/4–14 NPT Female thread Identification mark M20 × 1.5–6H 1/2–14 NPT 1/2–14 NPT G1/2 G1/2 Special Conditions for Safe Use (X): 1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e”...
  • Page 36 Quick Start Guide February 2019 Application: Location classes Temperature Humidity Vibration Enclosure SLL Lloyds Register (LR) Type Approval Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5 C5 Custody Transfer - Measurement Canada Accuracy Approval Certificate: AG-0226; AG-0454; AG-0477 Emerson.com/Rosemount...
  • Page 37: Eu Declaration Of Conformity

    February 2019 Quick Start Guide 7.13 Rosemount 3051 Declaration of Conformity Figure 7-1: Rosemount 3051 Declaration of Conformity EU Declaration of Conformity No: RMD 1017 Rev. AC Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount 3051 Pressure Transmitters manufactured by, Rosemount, Inc.
  • Page 38 Note – previous PED Certificate No. 59552-2009-CE-HOU-DNV All other Rosemount 3051 Pressure Transmitters Sound Engineering Practice Transmitter Attachments: Diaphragm Seal, Process Flange, or Manifold Sound Engineering Practice Rosemount 3051CFx DP Flowmeters See DSI 1000 Declaration of Conformity Page 2 of 4 Emerson.com/Rosemount...
  • Page 39 February 2019 Quick Start Guide EU Declaration of Conformity No: RMD 1017 Rev. AC ATEX Directive (2014/34/EU) BAS97ATEX1089X - Intrinsic Safety Equipment Group II Category 1 G Ex ia IIC T5/T4 Ga Harmonized Standards Used: EN60079-0:2012 + A11:2013, EN60079-11:2012 BAS00ATEX3105X - Type n Equipment Group II Category 3 G Ex nA IIC T5 Gc Harmonized Standards Used:...
  • Page 40 SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland Page 4 of 4 Emerson.com/Rosemount...
  • Page 41 February 2019 Quick Start Guide Quick Start Guide...
  • Page 42 Quick Start Guide February 2019 Emerson.com/Rosemount...
  • Page 43 February 2019 Quick Start Guide Quick Start Guide...
  • Page 44 The Emerson logo is a Facebook.com/Rosemount trademark and service mark of Emerson Electric Youtube.com/user/ Co. Rosemount is mark of one of the Emerson RosemountMeasurement family of companies. All other marks are the Google.com/+RosemountMeasurement property of their respective owners.