Honeywell LT-32 Quick Start Manual
Honeywell LT-32 Quick Start Manual

Honeywell LT-32 Quick Start Manual

Hide thumbs Also See for LT-32:

Quick Links

Morley LT-32
Morley LT-159
Power supply and batteries are required for commissioning!
Alarm and Fault Relay
Sounder circuit
Move the Jumper to Setup NO or
End of line diode cathode marker on
NC relay functionality.
positive terminal.
Additional and updated Informations
The described features, specifications and product related informations in this manual correspond to the date of issue (refer to date on the front page) and may differ due to modifications and/or amended Standards and
Regulations of the System design, Installation and Commissioning.
For further Informations refer to documentation M-168.1-SERIE-LT-EN.
Fire Alarm Control Panel LT-32 / LT-159
Quick Start Guide
M-168.2-EN / 07.2022
Panel Installation - Three Steps Process
STEP 2
All fixing point must be used.
STEP 1
Use 50 mm long x 5 mm diameter
According to the figure, mark
screws to secure the backbox on the
the required hole on the wall.
wall.
STEP 3
Align the screws on the cover with the keyhole on the back box and lock
the cover onto the backbox.
System Setup and Cabling
LT-32
Ref.
Description
1
Fault NO/NC
2
Fault C
3
Alarm NO/NC
4
Alarm C
5
Loop A +
6
Loop A -
7
Sounder 2 +
8
Sounder 2 -
9
Sounder 1 +
10
Sounder 1 -
11
Power +
12
Power -
Panel Connection
Highlighted the differences between panel LT-32 and LT-159.
Cable Entries
Upper and lower cable entry for 15 mm gland
Side entry: 3 on each side (21 x 21 mm easy access)
Central entry prepared for 60 mm universal flush box
LT-159
Ref.
Description
1
Fault NO/NC
2
Fault C
3
Alarm NO/NC
4
Alarm C
5
Loop A +
6
Loop A -
7
Loop B +
Loop B -
8
9
Sounder 1 +
10
Sounder 1 -
11
Power +
12
Power -
Honeywell
MORLEY IAS Fire Systems
www.honeywell.com
Technical changes reserved!
© 2022 Honeywell International Inc.
Field Cable Entry
2
1
Remove the keyholes  and pass
the cables  through them.
+
+
3
3
-
-
Battery Connection
Batteries connected in two rows 
with polarity as shown.
loading

Summary of Contents for Honeywell LT-32

  • Page 1 Batteries connected in two rows  NC relay functionality. positive terminal. Highlighted the differences between panel LT-32 and LT-159. with polarity as shown. Additional and updated Informations The described features, specifications and product related informations in this manual correspond to the date of issue (refer to date on the front page) and may differ due to modifications and/or amended Standards and Regulations of the System design, Installation and Commissioning.
  • Page 2 Panels Display Controls, Buttons and Password Quick Programming Procedure with Default General Alarm Functionality CONDITION / STATUS ICON COLOR DESCRIPTION CONTROL Red (blinking) A fire condition has been detected (buzzer active) FIRE Red (fixed) The user has acknowledged the event by buzzer silence SYSTEM FAULT Yellow (fixed) System fault...

This manual is also suitable for:

Lt-159