Emerson 1F83H-21PR - Programmable 80 Series Heat Pump Thermostat Manual

Emerson 1F83H-21PR - Programmable 80 Series Heat Pump Thermostat Manual

Also See for 80 Series:
Emerson 1F83H-21PR - Programmable 80 Series Heat Pump Thermostat Manual

Thermostat Applications Maximum
Stages
Heat/ Cool
Single Stage Compressor, Heat Pump
Systems (air source or geothermal) – 1 Stage Aux/Emergency Heat
2/1

MERCURY NOTICE: This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash.
Refer to www.thermostat-recycle.org for information on disposing of products containing mercury.

SPECIFICATIONS

Electrical Rating:
Battery Power 20 to 30 VAC, NEC Class II, 50/60 Hz
Input-Hardwire 20 to 30 VAC, NEC Class II, 50/60 Hz
Terminal Load 1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range 45° to 99°F (7° to 37°C)
Rated Differentials (@ 6°F/ Hr): Fast Med Slow
Heat Pump (Heat) 0.9°F 1.2°F 1.7°F
Heat Pump (Cool) 0.9°F 1.2°F 1.7°F
Auxiliary Heat 0.5°F 0.75°F 1.9°F
Operating Ambient 32°F to +105°F (0° to +41°C)
Display Temperature Range 32°F to +99°F (0 to 37°C)
Operating Humidity 90% non-condensing maximum
Shipping Temperature Range -20°F to + 150°F (-29° to +65°C)
Thermostat Dimensions 3-3/4" H x 6" W x 1-1/8" D

THERMOSTAT INSTALLATION

WIRING

Refer to equipment manufacturer's instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. Wiring table shown are for typical systems and describe the thermostat terminal functions.

Terminal Designations Terminal Function
R Power (24V)
O/B Changeover Terminal-Energized in Cool (O) or Heat (B) for Heat Pump or Damper Systems
Y Heat and Cool Mode 1st Stage Compressor
G Fan Relay
E* Auxiliary only Heat Mode (Emergency Heat)
C Common wire for 24V (optional with batteries)
L Heat Pump malfunction / Diagnostic terminal (input signal requires common)
W2* Heat Mode – 2nd stage

*Cut W2/E jumper when separate heat sources are used for W2and E.


For Dual Fuel Heat Pump applications, be sure to turn on the Duel Fuel Logic option (found in the Installer's Menu)

THERMOSTAT INSTALLATION

Precautions

  • Do not exceed the specification ratings.
  • All wiring must conform to local and national electrical codes and ordinances.
  • This control is a precision instrument, and should be handled carefully. Rough handing or distorting components could cause the control to malfunction.


Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will burn out thermostat and could cause personal injury and/or property damage.


To prevent electrical shock and/or equipment damage, disconnect electrical power to system, at main fuse or circuit breaker box, until installation is complete.

Battery location
Premium AA alkaline batteries are required when C-wire is not available. When C-wire is available, the batteries provide a back-up source of power (this will maintain the clock in the event of a power outage).

  1. W2/E Jumper Wire
    This thermostat electrically connect the W2 and E terminals so that you do not need to do this with a jumper wire. If your system has separate W2 and E wires, clip the W2/E jumper located on the back of the thermostat. This will isolate both terminals so they can be used independently.
  2. O/B Terminal Switch
    The O/B switch on this thermostat is factory set to the O position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in Cool. If the heat pump being installed requires a B terminal to energize the changeover relay in Heat, the O/B switch must be moved to the B position.

INSTALLER MENU

To prevent changes that may affect system performance, this thermostat has an INSTALLER'S MENU and a USER MENU. The INSTALLER'S MENU provides access to every option, while the USER MENU provides access to items that will not affect system performance. To access the INSTALLER'S MENU press the Menu button for 8 seconds. The display will show item 30 in the table below. Use Next and Back to navigate through menu items. Press or to change a menu setting.

Installer's Menu #
(Hold Menu 8 Seconds)
Description Default Setting
(flashing icons)

Settings

(Press or )

30 Heat Cycle Rate (how often the heat will turn on) MEd

SLO – slow

MEd – medium

FAS – fast

32 Aux Cycle Rate (how often the auxiliary heat will turn on) MEd

SLO – slow

MEd – medium

FAS – fast

35 Cool Cycle Rate (how often the cooling will turn on) MEd

SLO – slow

MEd – medium

FAS – fast

50 Compressor Lockout
(protects the compressor from short cycling)
OFF On – 5 minute delay OFF – no delay
60 Duel Fuel Logic (turn On when using gas as the auxiliary heat source) OFF

On- gas auxiliary heat

OFF- electric auxiliary heat

65 Maximum Heat Limit
(maximum set point for heat mode)
99 47 to 99
66 Minimum Cool Limit
(minimum set point for cool mode)
45 45 to 97
74 Schedule Type (set as either 7-Day, 5-1-1 Day or Non-Programmable) 5

7 – 7 Day

5 – 5-1-1 Day

0 – Non Programmable

76 Early Start (starts heating or cooling early so your programmed temperature is reached by the programmed time) OFF On – start early OFF – start at program period time
79 Fahrenheit or Celsius °F

°F – Fahrenheit

°C – Celsius

81

Temperature Display Adjustment

(adjust the displayed "Room

Temperature")

0 -5 to +5
83 Continuous Display Light (keep the backlight always on – "C" wire required) OFF

On – always on

OFF – momentarily

86 Change Air Filter (set up a monthly reminder) OFF

1 to 12 – reminder time

(months)

OFF – no filter reminder

99 Keypad Lock (prevent unwanted changes to the thermostat) OFF

On – disable buttons

OFF – all buttons are active

TEST EQUIPMENT

Turn on power to the system.

Fan Operation

If your system does not have a G terminal connection, skip to Heating System.

Heating System

  1. Move System Switch to Heat position. If the auxiliary heating system has a standing pilot, be sure to light it.
  2. Press to adjust thermostat setting to 1° above room temperature. The heat pump system should begin to operate and the thermostat will indicate Heat On.
  3. Press to adjust thermostat setting to 3° above room temperature. The auxiliary heat should begin to operate and the thermostat will indicate Heat On Auxiliary.
  4. Press to adjust thermostat setting 1° below room temperature. The heating system should stop operating and the thermostat should indicate Heat.

Auxiliary System

  1. Move System Switch to Aux position. If the auxiliary heating system has a standing pilot, be sure to light it.
  2. Press to adjust thermostat setting to 1° above room temperature. The auxiliary heating system should begin to operate and the thermostat will indicate Heat On Auxiliary.
  3. Press to adjust thermostat setting 1° below room temperature. The auxiliary heating system should stop operating and the thermostat should indicate Heat Auxiliary.

Cooling System

  1. Move System Switch to Cool position.
  2. Press to adjust thermostat setting 1° below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
  3. Press to adjust thermostat setting to 1° above room temperature. The cooling system should stop operating and the thermostat will indicate Cool.

NOTE:
If Starting Soon is shown on the display, the compressor lockout feature is operating. There will be up to a
5 minute delay before the compressor turns on.(see INSTALLER MENU, item 50)


To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational for
6 hours and the system has not been operational for at least 5 minutes.

THERMOSTAT OVERVIEW

Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.

THERMOSTAT BUTTONS AND SWITCHES THE DISPLAY
  1. Next (Menu button) is used to navigate within a menu
  1. Back (Run button) is used to navigate within a menu
  1. Exit (Hold button) returns to the home screen
  1. SEE TROUBLESHOOTING

THERMOSTAT OVERVIEW

Whenever " Replace " appears in the display, new premium brand AA alkaline batteries should be installed. If the house will be unoccupied for an extended period and either " " or " Replace " is displayed, install new batteries before leaving.

USER MENU

To customize thermostat settings, press the Menu button from the home screen. Use the or buttons to highlight Settings and press Next. Use Next and Back to navigate through menu items. Press or to change the setting.

User's Menu # (Press Menu button and release) Description Default Setting (flashing icons) Settings (Press or )
01 Schedule Type (set as either 7-Day, 5-1-1 Day or Non Programmable) 5 7 – 7 Day
5 – 5-1-1 Day
0 – Non-Programmable
02 Early Start (starts heating or cooling early so your programmed temperature is reached by the programmed time) OFF On – start early
OFF – start at program period time
03 Fahrenheit or Celsius °F °F – Fahrenheit
°C – Celsius
04 Temperature Display Adjustment (adjust the Room Temperature) 0 -5 to +5
05 Continuous Display Light (keep the backlight always on – "C" wire required) OFF On – always on
OFF – momentarily
06 Change Air Filter (set up a monthly reminder) OFF 1 to 12 – reminder time (months)
OFF – no filter reminder
07 Keypad Lock (prevent unwanted changes to the thermostat) OFF On – disable buttons
OFF – all buttons are active

THERMOSTAT OPERATION

Set Current Time and Day

NOTE:
Time icons will flash at initial power up or after a reset.

  1. Use or to adjust the hour
  2. Press Next to advance to set the minutes and day of the week
  3. Press Exit when finished.

The default program is5-1-1 Day, but can be setup as a 7-Day or Non-Programmable thermostat (refer to the User Menu above)

  • Hold Temperature (bypassing the schedule) – With the System Switch set to Heat or Cool, momentarily press the Hold button. Hold will be displayed. Use or to adjust the temperature. The thermostat will hold the room temperature at the selected setting until you press Run to start program operation again.
  • Program Override (Temporary Hold) – Press or until the desired temperature is displayed. The thermostat will override the schedule until the next programmed time period with a minimum override of 2 hours. Then the thermostat will automatically revert to the program.
  • Keypad Lockout – To prevent unwanted changes, the buttons can be disabled.
    To turn this feature On, press and hold and the Menu button until the icon appears (this can also be turned on in the menu). To turn Off, press and hold and the Menu button for 3 seconds.

THERMOSTAT SCHEDULE

Energy Saving Factory Schedule

This thermostat is programmed with the energy saving settings shown in the table below for all days of the week.

Wake Leave Return Sleep
Heating Schedule 6:00 AM - 70°F 8:00 AM - 62°F 5:00 PM - 70°F 10:00 PM - 62°F
Cooling Schedule 6:00 AM - 75°F 8:00 AM - 83°F 5:00 PM - 75°F 10:00 PM - 78°F

NOTE:
Thermostat can be programmed on or off the subbase

Modify the Heating Schedule

  1. Slide the system switch to Heat
  2. Press Menu
  3. Press Next to enter the schedule
  4. The time icons will flash – use or to set the time for the start of a period
  5. Press Next – the set point icons will flash – use or to set the temperature for the current period
  6. Continue to press Next to advance through all periods (Wake, Leave, Return, Sleep) for all days of the week.

NOTE:
Press Back to return to the previous setting. Once all days of the week have been programmed the thermostat will display End. Press Exit at any time to save changes and return to home screen.

Modify the Cooling Schedule

  1. Slide the system switch to Cool

TROUBLESHOOTING

Symptom Possible Cause Corrective Action
No Heat/
No Cool/
No Fan
(common problem)
No Heat
Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within five minutes the thermostat should make a soft click sound and "Heat On" should appear on display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.
No Cool
Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same procedures as diagnostic for "No Heat" condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu. (see INSTALLER MENU, item 50)
Heat, Cool or Fan Runs Constantly Possible short in wiring, thermostat, heat, cool or fan system Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists contact your HVAC service person.
Thermostat Display &
Thermometer Disagree
Thermostat display requires adjustment Display can be adjusted +/-5°. See User Menu item 04
Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing) The location of the thermostat and/ or the size of the Heating System may be influencing the cycle rate Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently, but runs for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30 & 35) If an acceptable cycle rate is not achieved, contact your HVAC service person.
"Call for Service" icon appears on displayed
  1. Make sure keypad lockout is not turned on (deNOTEd by icon)

Resetting the Thermostat or Thermostat Settings

If the thermostat has good batteries, but has a blank display or does not respond to key presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset will not change the menu settings or program. If the condition persists after reinstalling the batteries, replace the thermostat.

To conveniently reset only the schedule and user settings back to factory defaults, press Menu and Backlight buttons at the same time and hold until the display goes blank and resets.

HOMEOWNER HELP LINE: 1-800-284-2925


White-Rodgers is a business of Emerson Electric Co.

The Emerson logo is a trademark and service mark of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com

Videos

Emerson 80 Series | How Do I Program Video

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Need Assistance?

Do you have a question about the 80 Series that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents