Thermostat Applications | Maximum Stages Heat/Cool |
Conventional Gas, Oil, Electric (mV and 24V), Heat Only, Cool Only or Heat/ Cool Systems | 1/1 |
Heat Pump (air source or geothermal) with no Aux. Heat | 1/1 |
MERCURY NOTICE: This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash. Refer to www.thermostat-recycle.org for information on disposing of products containing mercury.
Electrical Rating: | |||||||
Battery Power | mV to 30 VAC, NEC Class II, 50/60 Hz | ||||||
Input-Hardwire | 20 to 30 VAC, NEC Class II, 50/60 Hz | ||||||
Terminal Load | 1.0 A per terminal, 1.5A maximum all terminals combined | ||||||
Setpoint Range | 45° to 99°F (7° to 37°C) | ||||||
Rated Differentials: | Fast | Med | Slow | ||||
Heat (@ 6°F/ Hr) | 0.5°F | 0.75°F | 1.9°F | ||||
Cool (@ 6°F/ Hr) | 0.9°F | 1.2°F | 1.7°F | ||||
Operating Ambient | 32°F to +105°F (0° to +41°C) | ||||||
Display Temperature Range | 32°F to +99°F (0 to 37°C) | ||||||
Operating Humidity | 90% non-condensing maximum | ||||||
Shipping Temperature Range | -20°F to + 150°F (-29° to +65°C) | ||||||
Thermostat Dimensions | 3-3/4" H x 6" W x 1-1/8" D |
Refer to equipment manufacturer's instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. Wiring table shown are for typical systems and describe the thermostat terminal functions.
Terminal Designations | Terminal Function |
RC* | Power for Cooling |
RH* | Power for Heating |
O/B | Changeover Terminal-Energized in Heat (B) or Cool (O) for Heat Pump or Damper Systems |
Y** | Cooling Relay |
G | Fan Relay |
W** | Heating Relay |
C | Common wire for 24V (optional with batteries) |
*When both RC and RH wires are present, cut RC/RH jumper (see next page).
**For heat pump systems, add a jumper wire to connect terminals Y and W
Precautions
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will burn out thermostat and could cause personal injury and/or property damage.
To prevent electrical shock and/or equipment damage, disconnect electrical power to system, at main fuse or circuit breaker box, until installation is complete.
Premium AA alkaline batteries are required when C-wire is not available. When C-wire is available, the batteries provide a back-up source of power (this will maintain the clock in the event of a power outage).
To access the INSTALLER'S MENU set the system switch to the OFF position and then press and hold the temperature and buttons for 3 seconds. The display will show item 30 in the table below. Use the temperature and buttons by pressing them simultaneously to navigate through menu items. Press or to change a menu setting.
Installer's Menu # (Hold Menu 3 Seconds) | Description | Default Setting (flashing icons) | Settings (Press or ) |
30 | Heat Cycle Rate (how often the heat will turn on) | MEd | SLO – slow MEd – medium FAS – fast |
35 | Cool Cycle Rate (how often the cooling will turn on) | MEd | SLO – slow MEd – medium FAS – fast |
50 | Compressor Lockout (protects the compressor from short cycling) | OFF | On – 5 minute display OFF – no delay |
65 | Maximum Heat Limit (maximum set point for heat mode) | 99 | 47 to 99 |
66 | Minimum Cool Limit (minimum set point for cool mode) | 45 | 45 to 97 |
74 | Schedule Type (set as either 7-Day, 5-1-1 Day or Non-Programmable) | 5 | 7 – 7 Day 5 – 5-1-1 Day 0 – Non Programmable |
76 | Early Start (starts heating or cooling early so your programmed temperature is reached by the programmed time) | OFF | On – start early OFF – start at program period time |
79 | Fahrenheit or Celsius | °F | °F – Fahrenheit °C – Celsius |
81 | Temperature Display Adjustment (adjust the displayed "Room Temperature") | 0 | -5 to +5 |
83 | Continuous Display Light (keep the backlight always on – "C" wire required) | OFF | On – always on OFF – momentarily |
86 | Change Air Filter (set up a monthly reminder) | OFF | 1 to 12 – reminder time (months) OFF – no filter reminder |
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
Heating System
Cooling System
NOTE:
If Starting Soon is shown on the display, the compressor lockout feature is operating. There will be up to a 5 minute delay before the compressor turns on.(see INSTALLER MENU, item 50)
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.
Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS AND SWITCHES | THE DISPLAY |
| |
| |
| |
| |
| |
| |
| |
| |
| |
|
Whenever " Replace " appears in the display, new premium brand AA alkaline batteries should be installed. If the house will be unoccupied for an extended period and either " " or " Replace " is displayed, install new batteries before leaving.
Set Current Time and Day
NOTE:
Time icons will flash at initial power up or after a reset.
The default program is 5-1-1 Day, but can be setup as a 7-Day or Non-Programmable thermostat (refer to the Installer Menu above)
For tips on programming your thermostat to receive optimal comfort, convenience and energy savings go to: thermostathelper.com
Energy Saving Factory Schedule
This thermostat is programmed with the energy saving settings shown in the table below for all days of the week.
P1/Wake | P2/Leave | P3/Return | P4/Sleep | |
Heating Schedule | 6:00 AM - 70°F | 8:00 AM - 62°F | 5:00 PM - 70°F | 10:00 PM - 62°F |
Cooling Schedule | 6:00 AM - 78°F | 8:00 AM - 85°F | 5:00 PM - 78°F | 10:00 PM - 82°F |
NOTE:
Thermostat can be programmed on or off the subbase
Set Current Time and Day
Enter Heating Program
Enter Cooling Program
If the outside temperature is below 50°F, disconnect power to the cooling system before programming. Energizing the air conditioner compressor during cold weather may cause personal injury or property damage.
Symptom | Possible Cause | Corrective Action |
No Heat/ No Cool/ No Fan (common problem) | | |
No Heat | | Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within five minutes the thermostat should make a soft click sound and "Heat On" should appear on display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly. |
No Cool | | Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same procedures as diagnostic for "No Heat" condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu. (see INSTALLER MENU, item 50) |
Heat, Cool or Fan Runs Constantly | Possible short in wiring, thermostat, heat, cool or fan system | Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists contact your HVAC service person. |
Thermostat Display & Thermometer Disagree | Thermostat display requires adjustment | Display can be adjusted +/-5°. |
Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing) | The location of the thermostat and/ or the size of the Heating System may be influencing the cycle rate | Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently, but runs for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30 & 35) If an acceptable cycle rate is not achieved, contact your HVAC service person. |
"Call for Service" icon appears on displayed | |
|
Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not respond to key presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset will not change the menu settings or program. If the condition persists after reinstalling the batteries, replace the thermostat.
To conveniently reset only the schedule and user settings back to factory defaults, press and Set Time buttons at the same time and hold until the display goes blank and resets.
This product contains a chemical known to the state of California to cause cancer and birth defects and other reproductive harm.
HOMEOWNER HELP LINE: 1-800-284-2925
Emerson and White-Rodgers are trademarks of Emerson Electric Co.
©2021 Emerson Electric Co.
All rights reserved
.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the 1F75C-11PR that isn't answered in the manual? Leave your question here.