Mitsubishi Electric MELIPC MI5A1P User Manual page 132

Table of Contents
■CC-Link IE Field device access time (when this product is a mater station)
A CC-Link IE Field Network configuration when this product is a master station is as follows.
MELIPC
Function name
CCPU_ReadLinkDevice_ISR
CCPU_WriteLinkDevice_ISR
APPX
130
Appendix 3 Product Specifications
Master station(Station No.0)
Device name
Remote input (RX)
Remote output (RY)
Remote register (RWr)
Remote register (RWw)
Remote output (RY)
Remote register (RWw)
RJ71GF11-T2
Local station(Station No.1)
Device size
(Unit: Word)
1
64
512
1024
1
64
512
1024
1
64
512
1024
1
64
512
1024
1
64
512
1024
1
64
512
1024
VxWorks part
(Unit: Microsecond)
2.6
2.6
2.6
3.9
3.9
41.6
232.7
468
2.6
2.6
2.6
3.9
3.9
32.5
232.7
466.7
2.6
5.2
28.6
55.9
2.6
5.2
28.6
55.9