Page 2
All product and brand names are the service marks, trademarks, registered trademarks, or registered service marks of their respective owners. Printed in the United States of America. Honeywell reserves the right to change any information in this document at any time without prior notice.
DO NOT ACCEPT VERBAL APPROVALS, BECAUSE THEY ARE NOT VALID. Honeywell never recommends using the PRO3200 or related products for use as a primary warning or monitoring system. Primary warning or monitoring systems should always meet local fire and safety code requirements. The installer must also test the system on a regular basis by instructing the end user in appropriate daily testing procedures.
Copyright laws of the United States protect all information in this document or in the software product itself. Any use of this product is subject to the terms and acceptance of the Honeywell, Note: Inc. Software Agreement. Please request a copy from Honeywell, Inc., and review the agreement carefully.
Customer harmless for any costs or damages including reasonable attorneys' fees which Customer may be required to pay as a result of the defective Product or the negligence of Honeywell, its agents, or its employees.
Page 8
Notices Unpacking Procedure • If any other defect is apparent, call for a return authorization. viii www.honeywell.com...
Notices Shipping Instructions Shipping Instructions To ship equipment back to Honeywell, Inc.: 1. Contact the customer service department at 800-323-4576 before returning equipment. When you call please have available: • A description of the problem or reason you are returning the equipment.
All Products sold or licensed by Honeywell include a warranty registration card which must be completed and returned to Honeywell by or on behalf of the end user in order for Honeywell to provide warranty service, repair, credit or exchange. All warranty...
Page 11
Notices Confidentiality (This page is left blank intentionally for double-sided printing.) PRO3200 Input Module, Installation Guide, Document 800-15462...
Installing the PRO3200 Input Module Description The PRO3200 Input Module provides connections for 16 supervised inputs and two relay outputs. You can either mount the board in a rack or open and flat. If you rack-mount the board, only one edge is accessible for wiring; however, a flat mount increases the amount of available I/O slightly but significantly decreases the number of boards that can be mounted in one enclosure.
0°C to +49°C, operating, -55°C to +85°C, storage Humidity 0% to 85% RHNC Set Up Table 1: PRO3200 Input Module Jumper Settings Jumper Setting Default Selected Port 1 RS-485 EOL terminator is not active Port 1 RS-485 EOL terminator is active www.honeywell.com...
LEDs on board. The input LEDs flash when there is an alarm associated with the input. When any relay or input is energized or ON, its corresponding status LED becomes ON also. The LED remains ON for as long as the relay is energized. www.honeywell.com...
Page 17
Installing the PRO3200 Input Module LED Operation The assignment for each relay status LED is shown in the following table. Table 4: Additional PRO3200 Input Module LEDs LED number Description Input 0 status Input 1 status Input 2 status Input 3 status Input 4 status Input 5 status Input 6 status...
Connect the external drain shield to the appropriate earth ground on one end. 5. When daisy-chaining RS-485 ports together, connect the TR+ wires from the upstream and downstream boards to the TR+ terminal. Likewise, connect the TR- wires from the upstream and downstream boards to the TR- terminal. www.honeywell.com...
Installing the PRO3200 Input Module Wiring By factory default J1 is set open. If this board is the last board on the RS-485 bus, install jumper J1 across both pins (closed). Closing J1 provides the bus termination required. Wiring This section presents information on alarm contact wiring and control output wiring. Alarm Contact Wiring Inputs 0 to 15 may be configured to use normally open or normally closed contacts and non-supervised or supervised (with standard ±1 tolerance 1K ohm).
Mounting Options This board can be mounted on-edge in the rack-mount enclosure provided by Honeywell or it can be mounted flat against any surface using standoffs under the mounting holes provided in each of the four corners of this board.
Installing the PRO3200 Input Module Wiring Diagram for Connectors 1 through 12 Wiring Diagram for Connectors 1 through 12 Figure 1: PRO3200 Input Module Wiring: Connectors 1-12 INPUT BOARD Powered Relay 0 NO Relay 0 C o / Visual Relay 0 NC m Indicator IN0 Common IN1 Common...
* REMOTE MOUNT CONFIGURATION For RS-485 Communication Connections, twist the blue pair together and use as the common; Note: use the orange pair as your data pair, observing polarity. Connect the external drain shield to the appropriate earth ground on one end. www.honeywell.com...
Page 23
Installing the PRO3200 Input Module Wiring Diagram for Connectors 10 through 12 (This page is left blank intentionally for double-sided printing.) PRO3200 Input Module, Installation Guide, Document 800-15462...
Page 24
Installing the PRO3200 Input Module Wiring Diagram for Connectors 10 through 12 www.honeywell.com...