INSTALLATION AND OPERATING MANUAL
ATS Controller
ATyS C35
www.socomec.com
To download, brochures,
catalogues and technical manuals.
EN
Table of Contents
loading

Summary of Contents for socomec ATyS C35

  • Page 1 INSTALLATION AND OPERATING MANUAL ATS Controller ATyS C35 www.socomec.com To download, brochures, catalogues and technical manuals.
  • Page 2: Table Of Contents

    6.4. ATyS C35 accessories and compatible products ........
  • Page 3 Annex II - 6. Product configuration ............52 ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 4: General Safety Instructions

    • This manual provides instructions on safety, connections instructions on the SOCOMEC ATyS C35 ATS controller • Whether the ATyS C35 is sold as a loose product, as a spare, in a kit or as part of an enclosed solution or in any other...
  • Page 5: Standards

    2. STANDARDS • As a minimum the ATyS C35 comply with the following international standards: - IEC/EN 60947-6-1* - IEC/EN 60947-1 - IEC/EN 61010-2-201 - IEC/EN 61010-2-030 - IEC/EN 61010-1 - GB/T 14048.11* - GB/T 14048.11 Annex C • The Electromagnetic compatibility (EMC) directive 2004/30/UE •...
  • Page 6: Introduction

    IEC 60947-6-1, GB 14048-11 and other international standards as listed. As a standalone product the ATyS C35 is compliant with IEC 61010-2-201 and is compatible with use with PC and CC type RTSE. This version of instruction sheet is based on C35 products with firmware version 1.25 ATyS C35 “ATS Controller”...
  • Page 7: The Atys Family Product Range

    ATyS will be installed. This instruction manual includes details and instructions specific to the “ATyS C35” ATS controller only. For all other ATyS family of products please refer to the specific instruction manual related to that product.
  • Page 8: Quick Start

    5. QUICK START 301 302 (0/+0,8) ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 9: General Overview

    6.1. Product identification 1. AUTO/ Manual /PROG selector 2. Controller state LED 3. ATSE Synoptic 4. Remote position order selector / Menu scroll 5. Screen selection / Test button / Return 6. LCD screen ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 10: Controller Hmi

    10. COM LED (Yellow blinking when RS communication is ongoing). 11. Fault LED (Red blinking – Long blink when fault or product is inhibited). 12. Fire (Red when fire input is activated). See Annex I for more details on the LED indicators. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 11: Environmental

    • Volume LxWxH (mm): 172x128x154.5 • Weight : 1090 g 6.3.9. Lead free process The ATyS C35 complies with : • The UE directive for RoHS 2 2011/65/UE • The UE directive RoHS 3 2015/863/UE • China RoHS 2 SJ/T 11364-2014...
  • Page 12: Weee

    • Pollution degree 2 according to IEC 61010-1 6.3.12. Other compliances and marking 6.4. ATyS C35 accessories and compatible products The ATyS C35 is compatible and compliant according to IEC 60947-6-1 when used with the following IEC 60947-6-1 SOCOMEC RTSE: • ATyS S (from 40-125A) •...
  • Page 13: Installation

    Door cut-out of 92(+0.8) x138(+1) mm, door thickness 1.5- 3mm. Remove all connectors and clip before inserting the controller in the cut-out then fix the controller in place using all 4 fixations clips (cf. image below): Dimensions in mm. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 14: Din Rail Mounting

    Install on IEC 60715 Standard Din RAIL. When mounting make sure both clips are pushed up, then clip on the DIN Rail. To remove from the DIN Rail, drag the two mounting clips down before removing the product. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 15: Connections

    9. CONNECTIONS DANGER ! When using the ATyS C35 without the Socomec Harness, gG 4A fuse protection is required on the voltage sensing inputs cf connection diagrams. When using the C35 with ATyS R and the Socomec harness gG fuses are not mandatory.
  • Page 16: Metering And Sensing Detail

    (Cf chapter "12. Programming", page 27). CAUTION ! When using 3P network without neutral, the controller must be powered using 184-300 VAC between L1 and N. User may use a transformer between two phases to create this voltage. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 17: Connections

    4. RS485 connections 5. Genset Start relay / Programmable output 6. RTSE position control outputs 7. Source 1 and 2 voltage inputs 8. 24 V.d.c Aux supply 9. External DPS – Input / output ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 18: Connection Diagrams With Atys R

    104 105 106 203 204 205 206 Aux supply S1 IN S2 IN 102 101 302 301 202 201 15 16 17 DPS OUT *Using a Socomec cable harness kit excludes the need for fuses ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 19: Terminal Denomination, Description And Characteristics

    - use 7mm as stripping length for the controller terminals. - use 90°C copper wire for installations with ambient temperature from 35-60°C. - when the ambient temperature is above 60°C, Use 105°C copper wire ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 20: Atys C35 Operating Modes

    10. ATYS C35 OPERATING MODES 10.1. Operating modes The ATyS C35 has 4 distinct working modes, the working modes are selected using the HMI button or by using the "NOT IN AUTO" (default 91-92 input). 1. Auto LED, led on if the controller is in automatic mode.
  • Page 21: Visualisation Screens

    S1 50.1Hz U1n=232V S2 50.2Hz U1n=234V Sceen 2: voltage threshold and hysteresis settings. A global view of all the hysteresis and thresholds set on the product: S1=OVth=116% S1=OVhy=110% S1=UVth=85% S1=UVhy=95% S2=OVth=112% S2=OVhy=110% S2=UVth=85% S2=UVhy=95% ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 22 14 POS 0 Screen 7: counter on the number transfers on switch positons II and I. POS. I COUNT 00016 POS. II COUNT 00010 Screen 8: phase angle between sources S1-S2 Phase angle -10° ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 23 CT=0180s ST=0030s POS. I COUNT OUTPUTS INPUTS 00016 16 POS I 71 POS I S1-S2 15 POS II 72 POS II Phase angle POS. II COUNT 14 POS 0 73 POS 0 -10° 00010 ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 24: Connections

    11.2. Voltage sensing inputs The ATyS C35 includes dual single phase and 3 phase voltage sensing (terminals 103-106 and 203-206) designed to monitor 1 Phase supplies up to 300 V.a.c (L-N) and 3 phase +N up to 520 V.a.c (L-L).
  • Page 25: Outputs

    In Main-Main mode: if “S1-Mains S2-Mains” is selected in “System”  “APP” the start-gen output can be configured for other functions in the menu I/O. see chapter "12. Programming", page 27 for possible output functions. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 26: Inputs

    The RS485 connector provides the Modbus communication allowing to read values from the controller (eg: Voltage values, settings, switch position etc...) for details on the values that can be read through communication (see Annex II). ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 27: Programming

    WARNING ! When in programming mode the controller will not be in automatic. DANGER ! When leaving automatic mode, if previous mode was automatic the RTSE might transfer directly. Therefore it is recommended to place the C35 in manual mode before programming. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 28: Programing Menu Architecture

    2 (must be inferior to threshold setting). S2-UFth 98-90% Under frequency threshold for loss of source 2 (must be inferior to hysteresis setting). S2-UFhy 99-91% Under frequency hysteresis for return of source 2 (must be greater than to threshold setting). ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 29 (2) % of Frequency set in “NOM FREQ”. (3) Only configurable when “APP” is set to S1-Mains S2-Mains. (4) If voltage is set to 1PH+N the default value for NOM. VOLT. Will automatically be set to 230Vph-n. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 30: Input/Output Functions

    BaudRate 9600/38400/57600/115200 38400 Baud rate Data format 8N/8O/8E/7O/7E Format for serial communication Stop Bit 1, 2 Stop bit for data (1) N for no parity, O for Odd parity and E for even parity. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 31: Characteristics

    Good engineering practice is imperative whilst all necessary precautions must be taken to ensure that the intervention (whether directly or indirectly) remains safe in all aspects. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 32: Trouble Shooting Guide

    - Verify that there are no ongoing faults. COM LED is on fixed - Verify that Communication settings are set according to your specification. - Contact Socomec for other information. Parameters are not taken into - Check that the buzzer sounds twice after pressing save.
  • Page 33: Associated Products

    24/48 VDC 9506 4010 9594 9012 100 A 12 VDC 9505 4010 230 VAC 9503 4010 9599 4001 24/48 VDC 9506 4012 125 A 12 VDC 9505 4012 230 VAC 9503 4012 9599 4001 ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 34 To shroud front switch top and bottom 2 references required (Whenever a bridging beam is fitted, it is then only possible to fit 3 times the reference for the terminal cover). (3) Factory mounting only. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 35: Annex I - 1. Hmi Reminder

    9. Run LED (Green when product is powered). 10. COM LED (Yellow blinking when RS communication is ongoing). 11. Fault LED (Red blinking – Long blink when fault or product is inhibited). 12. Fire (Red when fire input is activated). ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 36: Annex I - 2. Led Functioning Modes

    Inhibit is not active / no faults active Inhibit input is active or and dip switch configuration has been fault is active saved. *Considering that the controller is powered. **Considering that lamp TEST has not been initiated ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 37: Annex I - 3. Connection Diagrams

    + - 0 I I SOURCE 1 SOURCE 2 104 105 106 203 204 205 206 Aux supply S1 IN S2 IN 102 101 302 301 202 201 14 15 16 17 DPS OUT ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 38: Annexe I - 3.2. Connections With Atys Dm

    + - 0 I I SOURCE 1 SOURCE 2 104 105 106 203 204 205 206 Aux supply S1 IN S2 IN 102 101 302 301 202 201 14 15 16 17 DPS OUT ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 39: Annexe I - 3.3. Connections With Standard Cc Type Based Tse

    RTSE supply. CAUTION ! Due to the numerous types of RTSE type CC (contactors) available on the market, compatibility and specific wiring designs must be carried out and qualified by others. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 40: Annexe I - 3.4. Connections With Standard Cb Type Based Tse

    WARNING ! Before using the internal DPS on the CB aux input make sure that the the characteristics do not go beyond maximum capacity of the DPS output (cf Chapter "9.4. Terminal denomination, description and characteristics", page 19). ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 41: Annex I - 4. Phase Rotation Check

    “return timer” RT. OVth/OFth OVhy/OFhy Unom/Fnom UVhy/UFhy UVth/UFth Source available Settings configured can be seen in the navigation screens 2 and 3: ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 42: Annex I - 6. Timers

    If the auxiliary supply is not present and no sources are available the fail timers will automatically be set to zero, and the start-gen contact will be active immediately after loss of supply (51-52 closed). ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 43: Annex I - 7. Priority Settings & Retransfer

    3 seconds, the controller will return to the last working mode. In Main-Main mode the genset start output will not be activated. Sequence for TEST ON LOAD: Allows user to test the full genset + ATS function ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 44: Annex I - 9. C35 Dps Operating Sequences

    Allows users to test the genset function without transfer, in Main-Main mode this test will not be functional. Annex I - 9. C35 DPS Operating sequences Controller operating sequence with source 1 priority and 24 V.d.c power supply. DPS Output operating sequence: ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 45: Annex I - 10. C35 Standard Operating Sequence

    Annex I - 10. C35 standard operating sequence The following diagrams describe the standard C35 sequence in Main-Gen mode with Source 1 as priority the Main-Main sequence is identical with the exception that there is no Start-Gen signal. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 46 Logic diagram: ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 47 ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 48: Annex Ii. Modbus Communication Address And Designation Details

    0: Output not activated 1: Output activated 10120 Position I input state (70-71) 0: OFF 1: ON 10121 Position II input state (70-72) 0: OFF 1: ON 10123 Position 0 input state (70-73) 0: OFF 1: ON ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 49: Annex Ii - 2. Status

    Source 1 power status 10125 Source 2 power status 40005 ATyS C35 operating mode 2: Manual 3: Automatic Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Status Normal Missing phase Overvoltage Undervoltage Overfrequency Underfrequency ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 50: Annex Ii - 3. Voltage Sensing

    Once the configuration is done, write data 1 at address Dec. 40565. After changing the parameters the product buzzer will sound twice and the Com LED will stay on. To reset to default parameters press the RES button for 15 seconds, the product will reboot and the standard communication settings will be set. ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 51: Annex Ii - 5. Maintenance

    0 - 60 000 10132 Position II operation counter in Manual mode 0 - 60 000 10170-10179 Serial number (1 word per address to convert to 2 caracters of ASCII) ASCII 10186 Hardware version 10187 Software version ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 52: Annex Ii - 6. Product Configuration

    S1 Over frequency hysteresis (Ofhy) 101-119 40089 0DT S1 to S2 0-20 (s) 40091 Signaltime 1-200 (0.1s) 40095 0DT S2 to S1 0-20 (s) 40106 Generator start delay 0-6000 (s) 40107 Generator cooldown timer 0-3600 (s) ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 53 8: Fire alarm 9: Generator start 40241 Output Type 1: NO 2: NC 40565 Save parameters 1: Save parameters 2: Restore factory default 40579 Language 1: Chinese 2: English 40601 Generator start timeout 0-3600 (s) ATyS Controller C35 - 549781A - SOCOMEC...
  • Page 54 Imported in the U.K. by: Socomec U.K. Limited, Unit 7-9 Lakeside Business Park, Broadway Lane, South Cerney, Cirencester, Glos, GL7 5XL. wwww.socomec.co.uk CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE 67235 BENFELD, FRANCE www.socomec.com Non contractual document. © 2022, Socomec SAS. All rights reserved.