Setting The Addresses - Honeywell Notifier FAAST LT NFXI-ASD Series Quick Installation Manual

Table of Contents
Table 2: Wiring Terminal Designations
(Note - Terminals marked CH2 will only be available on 2 channel
models)
No.
Function
1
Ext Power In +
2
Ext Power In -
3
Aux Power In +
4
Aux Power In -
5
NC Alarm Relay
6
C Alarm Relay
7
NO Alarm Relay
8
NC Alarm Relay
9
C Alarm Relay
10
NO Alarm Relay
11
NC Fault Relay
12
C Fault Relay
13
NO Fault Relay
14
NC Fault Relay (AUX)
15
C Fault Relay (AUX)
16
NO Fault Relay (AUX)
17
Sounder Output 1 -
18
Sounder Output 1 +
19
Sounder Output 2 -
20
Sounder Output 2 +
21
Configurable Input +
22
Configurable Input -
23
Not Used
24
Loop out -
25
Loop switched out +
26
Loop in -
27
Loop in +
28
Loop not switched out +
Table 3: Relays
RELAY
ALARM 1 or 2
FAULT 1 or 2
SOUNDER 1 or 2

SETTING THE ADDRESSES

Each aspiration channel uses loop communications to report its
status information to the CIE (Fire Panel). As a factory default,
the unit will report smoke alarm and sensor information at an
associated sensor address and general alerts and faults on a
different module address.
X 10
Figure 10: Address Switches
Sensor
The sensor address is set on rotary decade switches on the back
of the smoke sensing devices. The smoke sensors are located
under the sensor cover inside the unit (see Figure 9). The Smoke
Sensors section of Service - later in the manual - shows how
to remove the sensors. As supplied, the default for channel 1 is
N200-102-00
Primary PSU
Primary PSU
Not used in default
Not used in default
CH1
CH1
CH1
CH2
CH2
CH2
CH1
CH1
CH1
CH2
CH2
CH2
47 k-ohm EOL Resistor
47 k-ohm EOL Resistor
(Reset)
Default is active = short circuit
(Reset)
(unsupervised)
To use isolator
Internally connected to 27
ACTION:
Controlled by panel when it determines
alarm condition has been met.
When FAULT CONDITION on Ch1 or Ch2
or a common FAULT occurs. Fault is also
signalled when in Service Mode and when
the device is unpowered.
Set ON when a channel is in ALARM.
Sounder 1 corresponds to Ch1 and
Sounder 2 corresponds to Ch2
X 1
Address 1; in 2 channel units (or when two sensors
are fitted) the second device is set to Address 2.
Any sensor address may be used except 0, whilst
respecting the panel's rules on co-operative
Multi-Sensing* (see below) between the VIEW™
smoke sensors.
T1
Module
The module address is set by means of rotary
decade address switches located behind the door
T2
of the unit. Use a screwdriver to rotate the wheels
to the desired address. The selected address
refers to channel 1; on 2 channel units the device
T3
assigns the next (+1) module address to channel
2 automatically. Hence, address 159 is not valid
for channel 1. (Note: for control panels that use
T4
only 99 addresses, 99 is invalid for channel 1.)
Note: The module address will only respond to a
panel poll when in Normal mode.
T5
* Co-Operative Multi-Sensing
Depending upon the panel used, the rules to
T6
define the co-operative Multi-Sensing between
the VIEW™ smoke sensors differs. This mode will
T7
allow an even higher sensitivity, but is only to be
used for the sensors within a single NFXI-ASD12.
T8
How to Set this up for the NF300, NF3000,
NF500 and NF5000 Panels
T9
The co-operative Multi-Sensing is automatically
activated if the VIEW™ sensors on a loop are set
to adjacent sensor addresses and if they are also
T10
put into the same zone. Additionally, if cells are
being used, the cell numbers for the co-operative
NOTES
Set ON and OFF by panel; not latched
Fault state is not latched.
Default condition = set on in ALARM.
How to Set this up for the NF50-A, NF50, NF50-S and Pearl
Panels
The co-operative Multi-Sensing is automatically activated if the
VIEW™ sensors on a loop are put into the same cell. Setting a cell
to 0 will disable co-operative Multi-Sensing for that sensor.
If Co-operative Multi-Sensing is enabled in the panel, the two
VIEW™ sensors within an Aspirating Smoke Detector are required
to have adjacent addresses set.
If more than one Aspirating Smoke Detector is used on a loop,
ensure that the VIEW™ sensors do not have adjacent addresses
across two different Aspirating Smoke Detectors. This will cause
the panel to generate a fault message instead of a fire message
when smoke is detected by one of the Aspirated Smoke Detector
units but not the other.
To avoid problems, ensure that no VIEW™ sensors on a loop have
addresses set adjacent to the address values set in an Aspirating
Smoke Detector.
POWERING UP
Using Default Settings
1. Connect a suitable 24VDC supply (complying with European
Standard EN 54-4) to pins 1 and 2 on terminal block T1 (See
Table 2)
5
sensors must also be the same.
IMPORTANT
I56-3947-200

Hide quick links:

Table of Contents
loading

Table of Contents