Setting method [G] [WG]
When [Pr. PC19.4 Output open-phase detection selection] is set to "1" (enabled), the output open-phase detection function
will be enabled.
Servo
Symbol
parameter
PC19.4
*COP6
PC19.6
*COP6
Setting method [A]
When [Pr. PC26.4 Output open-phase detection selection] is set to "1" (enabled), the output open-phase detection function
will be enabled.
Servo
Symbol
parameter
PC26.4
*COP5
PC26.6
*COP5
4 APPLICABLE FUNCTIONS
300
4.18 Disconnection/incorrect wiring detection function
Name
Output open-phase detection
selection
Output open phase - Judgment
speed selection
Name
Output open-phase detection
selection
Output open phase - Judgment
speed selection
Outline
Enable or disable the detection of output open-phase detection function.
0: Disabled (initial value)
1: Enabled
Select the judgment speed of the output open phase detection function.
0: Servo motor speed (initial value)
1: Speed command
In the torque control, set "0" (Servo motor speed). When "1" (speed command) is set,
[AL. 139.2 Output open-phase error] does not occur.
Outline
Enable or disable the detection of output open-phase detection function.
0: Disabled (initial value)
1: Enabled
Select the judgment speed of the output open phase detection function.
0: Servo motor speed (initial value)
1: Speed command
In the torque control, set "0" (Servo motor speed). When "1" (speed command) is set,
[AL. 139.2 Output open-phase error] does not occur.