3.15 BLINDS CONTROL

TR80 can control up to 2 blinds, curtains or shutters. General blind parameters are as
shown below.
Register
type
Holding
Holding
Holding

3. 15. 1 Blind 1 configuration parameters

Register
type
Holding
Holding
Holding
Holding
Holding
Blind type setting detail:
Bit 0 - Angle Control:
0 = up/down positioning only – no slat angle control
1 = up/down positioning + slat angle control
Bit 1 – Position direct/reverse
0: reverse (up is 0%. Up button changes value 100->0%)
1: direct (up is 100%. Up button changes value 0->100%)
TR80 - Installation and Operation Guide
Relative
Absolute
Address
Address
2400
42401
2401
42402
2402
42403
Relative
Absolute
Dir
Address
Address
2403
42404
R/W
2404
42405
R/W
2405
42406
R/W
2406
42407
R/W
2407
42408
R/W
Dir
Name
Blind Group
R/W
Count
Blind adjustment
R/W
step size
Blinds angle
R/W
adjustment step
size
Config
Name
parameter
Blind 1 type
403
Blind 1 min pos
404
Blind 1 max pos
405
Blind 1 min
406
angle
Blind 1 max
407
angle
Config
Unit
Range
parameter
400
int
0...2
0: 1%
1: 2%
401
enum
2: 5%
3: 10%
4: 20%
0: 1°
1: 2°
402
enum
2: 5°
3: 10°
4: 15°
Unit
Range
Bit 0: angle
control
bitwise
Bit 1: position
direct/reverse
%
0...100%
%
0...100%
°
-180°...180°
°
-180°...180°
Default
value
1
3
3
Default
value
1
0%
100%
-80°
+80°