Active Faults & Alert; Reset Of The Anomalies; Anomalies Codes List - Siemens S120 PM240-2 Manual

For hi power units by omar lift
Table of Contents
12 ACTIVE FAULTS & ALERT
SIEMENS inverters emit warnings type A (ALERT) or F (FAULT).
Errors are identified by the letter of the type (A/F), followed by a digit code that allows you to trace the
causes that have generated and their possible solutions.
The errors are displayed: on the BOP operator panel.
A description of the error, the possible causes and solutions, is available in the following chapter.
The list of all possible errors and their solutions can be found in the standard manual SIEMENS V20, to
which you could refer.
To reset an error, select the error and follow the following procedure through the BOP (see below).
In general, facing to a non-compliance detected, the inverter behaves as follows:
Errors Type A (Alarm) are minor errors that, in principle, have no influence on the behavior of the
inverter / LIFT.
The error A remains active, until is existing the cause that has determined it, then it reset.
Errors TYPE F (Fault) are serious flaws that lead to the immediate arrest of the inverter and the lift
that is placed safely via simultaneous closing of the valve.
The error F remains active even after the disappearance of the cause that determines it and has to be
resetted manually.
Note:
If there are multiple active faults and alarms, the BOP first displays all faults one after another. Once
all faults are displayed, it displays all alarms in succession and the display continues to repeat.

12.1 RESET OF THE ANOMALIES

Acknowledging / clearing faults (FAULT)
To navigate through the current list of faults, press ▲ or ▼ on the BOP panel.
To clear / acknowledge the fault, press FN.
After you acknowledge or ignore the fault, the screen returns to the previous display. The fault icon remains
active until the fault is cleared / acknowledged.
Note: the anomalies screen displays again if the fault has not been cleared and if any button is not pressed

12.2 ANOMALIES CODES LIST

WARNING: To understand the causes, after having acquired the error code it may be necessary
to read the error index in the parameter r0949
Anomaly
F01042
Parameter error during project
download
F01043
Fatal error at project download
F01072
Memory card restored from the
backup copy
Siemens PM240-2_EN_rev00-30082019.docx
Cause
An error was detected when
downloading (upload or update) a
project using the commissioning
software (e.g. incorrect parameter
value)
A fatal error was detected when
downloading (upload or update) a
project using the commissioning
software
The Control Unit was switched-off
while writing to the memory card.
This is why the visible partition
became defective
After switching on, the data from
the non-visible partition (backup
copy) were written to the visible
partition
Solution
Enter the correct value in the
specified parameter
Identify the parameter that
restricts the limits of the specified
parameter (when it dependent by
another parameter)
Carefully note any other
messages/signals and remove
their cause.
Boot from previously saved files
(power off/ power on)
Contact OMARLIFT Support
Check that the firmware and
parameterization is up-to-date
Contact OMARLIFT Support if the
problem persist