Honeywell NOTIFIER AM-8200 Installation Manual

Honeywell NOTIFIER AM-8200 Installation Manual

Fire detection system
Hide thumbs Also See for NOTIFIER AM-8200:
AM-8200
Installation
MANUAL
Rev A.01
Fire Detection System
Table of Contents
loading

Summary of Contents for Honeywell NOTIFIER AM-8200

  • Page 1 AM-8200 Installation MANUAL Rev A.01 Fire Detection System...
  • Page 2 INDEX Limits of Fire Detection Systems EN 54: Informations – Option with Requirements General Description AM-8200 dimensions AM-8200 and AM-8200-BB Installation Front Panel indications ELECTRICAL FEATURES Earthing Main power supply (AM-8200) Power Supply Battery Charger section Batteries Main power supply (AM-8200BB) Power Supply Battery Charger section Batteries...
  • Page 3: Table Of Contents

    LIB-8200 (Expansion Board) Lines connection on AM-8200 BOARDS AND INTERCONNECTION AM-8200-BB BOARDS ASSEMBLY AM-8200-BB AM-82-BB MB (AM-8200-BB CPU Board) CNU terminal block Lines connection on AM-8200-BB OPTION CARDS AM82-2S2C INTERFACE RS232/485/CAN-BUS Summary of all Cards Connection AM82-BST-C AMPLIFIER BOARD CAN-BUS Board Assembly AM82-BST-C AM-8200 NETWORK System Wiring Example...
  • Page 4 NOTE: Do not try to install the control unit and devices connected without reading this manual. DETECTION SYSTEM LIMITS An alarm or fire detection system can be very useful for the prompt warning of any dangerous event, such as fire, a robbery or a simple burglary, in some cases it can automatically manage events (transmission of messages for room evacuation, automatic fire-extinguishing, TVCC system interface, access route or door blockage, automatic warning to authorities, etc.), but in any case, it does not ensure protection against damages to propriety or...
  • Page 5 Nazional Rules Compliants This device must be installed and must operate in accordance with these instructions and to the rules in force in the installation place. This product must be disposed of using the appropriate bins for electrical and electronic products. This product must not be placed in bins for collection of other waste types.
  • Page 6 GENERAL DESCRIPTION control unit is a fire detection control unit manufactured in conformity with the EN.54.2 and EN.54.4 rules. AM-8200 Technical features :  Multi-microprocessor system with 7” TFT display (800 x 480 with backlit ), 256 colors touch-screen with keyboard simulation to program and configure the system and the following specific functions : Reset Delay, Silence Buzzer , Silence/Restart Sounders, Reset, Evacuation.
  • Page 7 AM-8200 dimensions Top view Back view BACK view Botton view PAGE - 4 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc. M-162.2-AM8200-ENG Rev A.2 AM8200_manu-inst...
  • Page 8 AM-8200 and AM-8200-BB Installation Sequence for wall mounting AM-8200 Installation Manual PAGE - 5 AM8200_manu-inst Doc. M-162.2-AM8200-ENG Rev A.2 NOTIFIER ITALIA...
  • Page 9 AM-8200 front panel Warning: Drill into the lower part of the panel of the AM-8200 with a 10mm diameter drill bit for the passage of the 230Vac power cable of the AM-8200BB. PAGE - 6 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc.
  • Page 10 Moreover, if the control unit must The control unit must be installed to the wall so as to be installed to the wall beside a allow a clear view of the display and easy access by corner wall, the minimum the operator.
  • Page 11 Extractable labels on the front panel AM-8200-EU control panel is provided with extractable labels to indicate the functions Status via LED. A set of some different languages labels are provided in each EU panel PAGE - 8 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc.
  • Page 12 ELECTRICAL FEATURES  Operation temperature: - 5° C ÷ + 40°C.  Relative humidity: 10 % ÷ 93 % (without condensation).  Storage temperature: - 10°C÷ + 50°C. Earthing The earthling system must be performed in conformity with CEI and ISPELS rules or rules valid in the country where the panel is installed.
  • Page 13 Main power supply (AM-8200BB) The control unit is powered by the mains voltage and, in case of mains fault it can continue to normally operate due to the re-chargeable battery contained in the same control unit. The required features for the mains supply are: Voltage: 100-240 Vac single-phase -15% ÷...
  • Page 14 Batteries Installation Place the Bi-adhesive pads on the metal chassis and place the batteries on it. Bi-adhesive pads Bi-adhesive pads Power supply and battery operation The main microprocessor of the control unit periodically checks the state of the main AC power supply source, batteries and the recharging circuit.
  • Page 15 Mains and Batteries connection MAINS INPUT 230Vac (CN1) MAINS 230Vac GROUND FUSE 2AL Toroid In protection to AM-8200 AM-8200 Plastic Band FUSE 2AL In protection to AM-8200BB NTC Probe Adhesive tape for temperature probe locking AM-8200-BB Adhesive tape for probe locking NTC Probe Batteries 2x12V Batteries 2x12V...
  • Page 16: Lib-8200 (Expansion Board)

    Current consumption from Power Supply  Current from power supply in Normal Condition :  AM-8200-KLCD (CPU-AM-8200) Board at nominal voltage (29Vdc): 179mA  AM-82-BBMB (CPU-AM8200BB) Board at nominal voltage (29Vdc): 135mA  LIB-8200 (LIB) Board at nominal voltage (29Vdc): 50mA ...
  • Page 17: Boards And Interconnection Am-8200-Bb

    SYSTEM COMPONENTS AM-8200  AM-8200 Box is equipped with: AM-82-MB + AM-8200-KLCD  AM-8200 Box can contain up to 2 Loop Interface cards LIB-8200  Each LIB-8200 card can drive up to 2 ADV detection loops  Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol. ...
  • Page 18 Boards Assembly AM82-2S2C Assembly Flat cable 2 x screw 3 x screw AM82-2S2C-A AM82-2S2C-B 2 x spacer 3 x spacer AM82-2S2C-A AM-8200-KLCD AM-8200-KLCD front AM-82-MB AM82-2S2C-B back AM-8200 Installation Manual PAGE - 15 AM8200_manu-inst Doc. M-162.2-AM8200-ENG Rev A.2 NOTIFIER ITALIA...
  • Page 19 LIB-8200 Assembly 1 x screw 2 x spacer LIB-8200 AM-82-MB AM-8200-KLCD (AM-8200 CPU Board) PAGE - 16 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc. M-162.2-AM8200-ENG Rev A.2 AM8200_manu-inst...
  • Page 20 DIP SWITCH SW401 on CPU Board Dip switch Note Normal Operating setting Copy the configuration in the USB memory key Firmware updating Restore factory configuration from USB memory key loads configuration previously prepared by PK-8200 SW Tool AM-82-MB Terminal Board Flat cable for interconnection with AM-82-BBMB Flat cable for interconnection with LIB-8200 User terminal block...
  • Page 21 Relay outputs FUNCTION CHARACTERISTICS 1 contact controlled by 24Vcc / 2A resistive Siren Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JUSR2 USR2 (refer to basic board topography) Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JUSR1 USR1 (refer to basic board topography) Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JALL...
  • Page 22 General Alarm relay The main Alarm relay is available in free voltage contacts or as supervised output. Contact range: max 30 VAC/DC, 2A, Non-inductive loads. 11 12 COM NO/NC Main Alarm output Setting of the general Setting of the general Alarm output with N.O.
  • Page 23 USR1 and USR2 relays The USR1 and USR2 relays are available in free voltage contacts as supervised outputs. USR1 USR2 Contact range: max 30 VAC/DC, 2A, Non-inductive loads 13 14 15 16 Selection of type of contact (Normally open , COM NO/NC COM NO/NC Normally closed or supervised outputs ) see page 15.
  • Page 24 USR2 Output Setting of the USR2 output Setting of the USR2 output with N.C. contact with N.O. contact (Jumper JALL). (Jumper JALL). Supervised output (resettable fuse 0.3A) with EOL resistor 47KΩ Setting of the USR2 output as supervised output (Jumper JALL). Polarized devices (electronic sirens, etc.) NOTE: 47 K...
  • Page 25 Sounder connection - controlled output Sounder output connections (refer to basic board topography) 1A resettable fuse Polarized devices (electronic sirens, etc.) NOTE: 47 K Connect the , ¼ W EOL 47KΩ ¼ W resistor only on last sounder of the line ATTENTION: Non-polarized devices (Bells, relays, etc.) Polarity...
  • Page 26 LIB-8200 (Expansion Board ) TX-RX Line 4 Dip-switch LIB Address User terminal block Alarm Led Led Fault TX-RX Line 3 Connector for interconnections with AM-82-MB AM-82-BBMB CNU terminal block N° Description Characteristics Note Line 2 B- Line 2 B+ Detection LINE 4 ( if the board is mounted on AM-8200 ) Detection LINE 8 ( if the board is mounted on AM-8200-BB )
  • Page 27 AM-8200-BB  AM-8200BB Box is equipped of one CPU Board (AM-82-BBMB) and can contain up to 2 Loop Interface cards (LIB-8200)  Each LIB card can drive up to 2 ADV loop  Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol. BOARDS AND INTERCONNECTION AM-8200BB POWER SUPPLY AM-82-BBMB...
  • Page 28: Am-82-Bb Mb (Am-8200Bb Cpu Board)

    3 x screw 3 x spacer LIB-8200 AM-82-BBMB AM-82-BB MB (AM-8200BB CPU Board) Alarm led Earth dispersion led Flat cables for interconnections with AM-82-MB Fault led Dip switch SW1 USB connector Mains power terminal User terminal block Battery connections Connector for interconnections with LIB-8200 AM-8200 Installation Manual PAGE - 25...
  • Page 29: Cnu Terminal Block

    CNU terminal block N° Description Characteristics Note GND USR 2 A Resettable fuse +24V USR Line 2 B- Line 2 B+ Detection LINE 5 Line 2 A- Line 2 A+ Line 1 B- Line 1 B+ Detection LINE 6 Line 1 A- Line 1 A+ ADDRESS DIP SWITCH SW1 on CPU Board Dip switch...
  • Page 30: Option Cards

    OPTION CARDS AM82-2S2C INTERFACE RS232/485/CAN-BUS AM82-2S2C-A Board Rx RS232 Led Connector for connection with AM82-2S2C-B Tx RS232 Led Rx RS485 Led Tx RS485 Led Rx-CAN-BUS side A Led Tx-CAN-BUS side A Led Tx-CAN-BUS side B Led Rx-CAN-BUS side B Led AM82-2S2C-B Board Can-Bus Terminal block RS232/RS485 Terminal block...
  • Page 31: Summary Of All Cards Connection

    Summary of all Cards Connection PAGE - 28 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc. M-162.2-AM8200-ENG Rev A.2 AM8200_manu-inst...
  • Page 32 AM82-BST-C (CAN-BUS amplifier card) This board can be installed inside a remote HLSPS25(Power supply) along the CAN-BUS Network with the aim of doubling the distance Node-to-Node. On CAN-BUS network you can install up to 8 AM82-BST-C cards. Rx-CAN A Led SW1 Dip-Switch Tx-CAN BUS side A Led Fault LED Line CAN BUS-side B...
  • Page 33: Board Assembly Am82-Bst-C

    Board Assembly AM82-BST-C 2 x screw 2 x spacer 3 x spacer HLSPS25 AM82-BST-C AM-8200 NETWORK System Wiring Example AM-8200 AM-8200 AM82-BST-C inside the HLSPS25 PSU AM-8200BB AM-8200-2S2C AM82-BST-C PAGE - 30 INSTALLATION MANUAL AM-8200 NOTIFIER ITALIA Doc. M-162.2-AM8200-ENG Rev A.2 AM8200_manu-inst...
  • Page 34: Network With Am82-2S2C Board Installed On Am-8200 Control Panel

    16 Loops Network max 500 m Node-to-Node AM-8200 CAN-BUS CAN-BUS max 500 m max 500 m CAN-BUS CAN-BUS max 500 m max 500 m AM-8200 PRINTER AM-8200-BB Network with AM82-2S2C board installed on the AM-8200 control panel 500 m Node-Node 500 m Node-Node AM82-2S2C AM82-2S2C...
  • Page 35: Network With Am82-Bst-C Board Installed On Hlsps25 En54.4

    Network with AM82-BST-C board installed on HLSPS25 EN 54.4 PSU 500 m Node-Node 500 m Node-Node 500 m Node-Node 500 m Node-Node 500 m Node-Node 500 m Node-Node N.B. : On the CAN-BUS network, it’s possible to install max. 8 of AM82-BST-C cards CanBus Netwok Cable CBUS 218AWG: CAN‐BUS Cable 2x18 AWG 18 Fire Resistant PH60 EN 50200 Color Blue ...
  • Page 36: Communication Lines With Detectors/Modules

    Communication lines with Detectors / Modules The AM-8200 control unit communicates with intelligent detection and control devices which are addressable through a 2 wire line. The line can be connected to respect the specifications relevant to the signalling circuit lines of the STYLE 4 (open line) and STYLE 6 (closed line).
  • Page 37: Modules And Detectors Connection

    Modules and Detectors connection For the specific field device connections , please refer to : “Analogue system device installation manual” document : M-199.1-SCH-ITA or M-199.1-SCH-ENG by Notifier Italia. Example of closed line (style 6 Loop) “B” SIDE “A” SIDE LIB-8200 LIB-8200 The total length of the loop (from the Panel Loop output and input) SHALL NOT exceed 3.000 mt.
  • Page 38: Test Procedure For Detection Lines

    Test procedure for detection lines Before powering the control unit lines, check the following values: NOTE: A DIGITAL MULTI METER IS REQUIRED Line resistance Positive Side B Negative Side A The direct current resistance of the negative wire of the loop SHALL NOT exceed 20 Ohm. The measurement must be performed by disconnecting the channels “A”...
  • Page 39: System Test And Commissioning

    System Test and Commissioning The Control unit installation must be performed after having carefully read the instructions contained in the installation manual and the programming manual. Once mechanical installation of the control unit has been completed, perform the following operations: ...
  • Page 40: System Periodical Maintenance

    SYSTEM PERIODICAL MAINTENANCE Check that the green led “POWER OK” is on Check that all other control unit leds are off Press the function TEST key on the LCD and enter the level 2 password to access the “TEST” menu. Use the arrow keys ...
  • Page 41 POWER SUPPLY – Current calculation The power supply must be able to continuously power all the internal system devices (and all external devices) during the stand-by period, that is in NON-alarm conditions. Use the table A to calculate the load in stand-by conditions. Use the table B to calculate the additional current which is necessary in Alarm conditions A 24 Vcc internal power supply for a total of 4 Ampere is available on the power supply for the system operation Table 1...
  • Page 42 Table 2 NORMALcondition ALARM condition Item Current each Total Current each Total Current (dev Current x Q) (dev x Q) AM-8200BB AM-8200BB 135 mA 177 mA LIB-8200 50 mA 92 mA AM82-2S2C 28 mA 28 mA AM82-BST-C 39 mA 39 mA 62 mA 62 mA SIB-8200...
  • Page 43 Table 3 PERIPHERALS POWERD BY LOOPS Device type Quantity Current Total in Current Total in normal condition Alarm condition Detectors serie NFX Detectors serie 700 Single Modules serie 700 Double Modules serie 700 Modules serie MA MMX-10 N CMX-10 R Isolation modules Addressable Sounders (Power from loop)
  • Page 44 Summary of Current consumption of Loop devices ADVANCED PROTOCOL DEVICES Device Current NOTE Normal Alarm NFXI-OPT 300 μA 4 mA NFXI-TDIFF 300 μA 4 mA NFXI-TFIX 58/78 300 μA 4 mA NFXI-SMT2 300 μA 4 mA SMART 3 200 μA SMART 4 200 μA PINNACLE...
  • Page 45 CLIP PROTOCOL DEVICES Device Current NOTE Normal Alarm SDX-751ME 300 μA 6,5 mA SDX-751TEM 300 μA 7 mA FDX-551E 300 μA 7 mA FDX-551HTE 300 μA 7 mA HPX-751 300 μA 5 mA LPB-700 / 400 2 mA 8,5mA Loop Power LPB-700T 2 mA 8,5mA...
  • Page 46 E-mail: [email protected] A Honeywell company Every care has been taken in the preparation of this data sheet but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice.