7.4 Response upon voltage failure

The UPS response upon voltage failure is described in the following.
NOTICE
After the UPS has been issued the shutdown command, wait until the UPS buf-
fer time elapses before disconnecting the connecting cable to the PC or restart-
ing the PC.
Normal
Time between voltage
mode
failure and issuing
shutdown command
Default: 30 s
24 V In
24 V Out
24 V In
24 V Out
24 V In
24 V Out
Time of
voltage failure
0 s
The connection between PC and UPS may neither be disconnected nor established again
during this period! If the connection is restored, the PC restarts and there is an uncon-
trolled switch-off when the UPS buffer time elapses.
The period between the voltage failure and the shutdown can be set between 10 and 180
seconds in the dashboard; "Time to Shutdown after Power Outage"
Fig. 7-1: Pulse diagram of the UPS

8 Standards

Standard
EN 61000-6-4
EN 61000-6-2
PC failure due to faulty operation!
Time between shutdown command
and UPS switch-off: 120 s
PC shutdown
PC shutdown
2
10 to 180 s
completed
Description
Generic standards - Emission standard (industrial environments)
Generic standards – Noise immunity (industrial environments)
1
UPS switch-off 150 s
after voltage failure
+120 s
R911384727_Edition 03 Bosch Rexroth AG
11/31
Standards
UPS switch-off 150 s
after voltage failure
No UPS switch-off, as
voltage failure <30 s