Figure 7: Ups Control Panel, Configuration - Emerson SDU AC Series Instruction Manual

Table of Contents
10 | 7.0 Operating Instructions
7.5 Green Mode continued
UPSMON Software: If UPS is connected to a computer with UPSMON software running, the user can change the Green Mode setting.
On the UPSMON software screen, "UPS Control Panel" (see Figure 7 below), you can to enable and disable Green Mode Control by
clicking the appropriate box highlighted in the figure.
7.6 STANDBY MODE
This feature is only available during back-up mode. Standby mode can be executed remotely using the COMM CARDs. This feature puts
the UPS on standby in 3 minutes and auto-recovers once AC power returns. This 3 minute window (or maximum run time depending
on loading) allows the user to shut off or place equipment into safe mode.
7.7 REMOTE ON/OFF
Allows the user to perform remote power ON/OFF functions using a switch on terminals (non-polarized) to toggle ON/OFF state.
To Enable the UPS, close the switch that is connected to the terminals.
To Disable the UPS, open the switch that is connected to the terminals.

Figure 7: UPS Control Panel, Configuration

Remote Enable/Disable of UPS
SDU-A Remote
ON/OFF Switch Wired
UPS-A
UPS-A
Remote ON/OFF Terminals : Shorted (closed) for ON, Open for OFF
UPS Condition/State
ON
OFF
Switch or Terminal
Condition