Warning Messages - Honeywell XNX-AM Series Technical Manual

Hide thumbs Also See for XNX-AM Series:
Table of Contents
XNX Universal Transmitter

Warning Messages

Applicable
Warning
Description
Sensors
XNX
24 VDC
®
W001
All
Supply Bad
XNX Tempera-
W002
All
ture Error
Simulated
W003
All
Warning/Fault
Sensor Tem-
Optima
perature Error
W005
Sensor Tem-
Excel
perature Error
Sensor Tem-
ECC
perature Error
Negative Drift
ECC, mV
W006
Optima,
Negative Drift
Excel
Calibration
W007
All
Required
Warnings/Faults
Frequency of Diag-
Latching / Non-Latching
nostic
Non-latching
2 seconds
Non-latching
2 seconds
Non-latching
Enabled by user
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
Non-latching
2 seconds
Non-latching
2 seconds
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
Non-latching
2 seconds
Event History Data
XNX supply
Check wire of 24V power supply to XNX as well as power supply opera-
voltage x1000
tion.
Check location for heat sources. Fit with sunshade or other protection.
XNX tempera-
Change location of XNX. Check temperature in Info->Transmitter Status
ture (Celsius)
to ensure temperature is being measured properly.
0
Performing an alarm/fault reset will clear all simulation.
Sensor fault or
Check location for heat sources. Fit with sunshade or other protection.
warning code
Change location of XNX. Check temperature in Info->Sensor Status to
(Note 4)
ensure temperature is being measured properly.
Sensor fault or
Check location for heat sources. Fit with sunshade or other protection.
warning code
Change location of XNX. Check temperature in Info->Sensor Status to
(Note 4)
ensure temperature is being measured properly.
Check location for heat sources. Fit with sunshade or other protection.
Sensor temper-
Change location of XNX. Check temperature in Info->Sensor Status to
ature (Celsius)
ensure temperature is being measured properly.
Raw gas con-
Check sensor location for external interference. Perform zero calibra-
centration of
tion. If problem persists after zero calibration and no interference exists,
sensor
replace sensor.
Check sensor location for external interference. Perform zero calibra-
Sensor fault or
tion. If problem persists after zero calibration and no interference exists,
warning code
replace sensor.
Number of days
remaining until
Time since the last span calibration has exceeded a defined limit. Per-
calibration ex-
forming a successful span calibration will clear the condition. The limit is
pires, negative
the user-defined calibration interval. W007 can be disabled by setting the
= number of
calibration interval to 0.
days expired
121
Action For Resolution