How To Connect And Configure A Run/Stop Switch; With Forward/Reverse Selection - Bosch Rexroth EFC 3600 Easy Start Manual

Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
Easy Start Guide
Bosch Rexroth EFC 3600 Series Inverter

10. How to connect and configure a Run/Stop switch

with Forward/Reverse selection

The parameters described in Section 5 enable
Run/Stop operation via the red and green
buttons on the Inverter.
If this is unsuitable for the application, remote
switches can be used instead.
10.1 Parameters to change for remote Run/Stop
Parameter Description
b0.02
Access to additional parameters
b1.02
First RUN Command Source
E0.00
2-wire / 3-wire control
E0.01
Terminal X1 program
E0.02
Terminal X2 program
X1
3 2
EFC 3600
I/O Terminal
Blocks
3
1
Switch, 2 Position
Normally Open
"Run / Stop"
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
How to set
Default is 0 for Basic Parameters. Set at
Set to
1
Set to
1
Set to
23
Set to
24
X2
SC
1
2
1
Switch, 2 Position
Normally Open
"Forward / Reverse"
This section explains how to enable 2-wire
control with Run/Stop and Forward/Reverse
commands via separate selector switches.
Note that once this procedure is complete, the
Run/Stop buttons on the Inverter can no longer
be used.
for IO Terminals on the Inverter
for 2-wire control with Run/Stop and Forward/Reverse
for run forward command on X1
for run reverse command on X2
10.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite.
The SC terminal is a common connection for
terminals X1-X5 and has no other function.
Two suitable 2 position NO (
switches should be installed: One between
terminals SC and X1 (Run/Stop) and the other
b e t w e e n t e r m i n a l s S C a n d X 2
(Forward/Reverse).
Note that the Forward/Reverse switch only
selects the direction of rotation - it will not start
or stop the motor.
If the application only requires the motor to turn
in one direction, the Forward/Reverse switch
can be omitted.
R
©
The Inverter
2
to enable Extended Parameters.
Normally Open
)