Honeywell Gent Vigilon A3 Mimic Data And Installation

Honeywell Gent Vigilon A3 Mimic Data And Installation

Mimic panel

Quick Links

Data and Installation
Vigilon A3 Mimic panel
VIG-MIM-A3

Customised Mimic

Zonal Mimic

A Vigilon A3 Mimic panel (VIG-MIM-A3) must be
connected to a loop circuit of a Vigilon fire detection and
alarm system. It is used to provide indication of fire
events in the system. However it can also be used to
provide indication of fault and supervisory events in the
system. The panel can be mounted in landscape or
portrait orientation.
A Customised Mimic holds a pictorial overlay that
represents the protected building or an area within. A fire
event is indicated by the illumination of appropriate red
LEDs behind the overlay to show the location of the fire.
A Zonal Mimic provides a traditional zone by zone
indication of a fire. Each zone is given a location label to
identify the area within a building.
The panel illumination defaults to a Zonal Mimic but can
be reprogrammed during commissioning to be a
Customised Mimic. An array of red lights illuminates
individually or in groups. Illuminations may be applied to
include custom shapes, text and digital clock in small or
large size. A site specific 'welcome message' may be
configured for display during quiescent conditions that
can scroll if it is too long to fit the display area. First or
last fire flashing option, with in phase or anti phase flash.
The panel has its own mains derived power supply with
battery for standby power in the event of mains supply
failure.
4188-945_issue 2_05/10_pt1_A3 Mimic

Technical Data

Panel dimensions
height 403mm, width 338mm,
depth 101mm
Weight
7.9Kg without batteries
10.5Kg with batteries
Storage temperature
-10 to 55ºC
Operating temperature 0 to 45ºC
Relative humidity
Up to 90% temperature
(Non condensing)
5 - 45°C
Battery
2 x 6V 7Ah sealed lead acid
(weight 1.3Kg each)
The integral battery provides
power for 72 hours in standby
condition and a further
30 minutes in alarm.
Mains operating
230V 50Hz +10% -6%
voltage
Emission
BS EN61000-6-3 : 2001
Immunity
BS EN50130-4 : 1996 : Part 4
LVD
BS EN 60950-2006
Ingress protection
IP30 (estimated)
Colour
Door - Pantone 422
Back box - Graphite Grey
Control
Cancel fault buzzer / lamp test
button
Indicators
1536 high intensity RED LEDs.
Loop connection
3-way connection to a loop
circuit
Maximum number per
Maximum number of combined
loop
repeat and mimic panels per
(A maximum load
loop = 4
factor of 1000 allowed
load factor per panel = 3
per Vigilon loop circuit)

Typical Mimic illuminations

Customised Mimic
Flashing in phase
or anti phase
by Honeywell
(RAL 7024)
Zonal Mimic
ZONE n
Zone in fire
- steady indication
Latest zone in fire
- flashing indication
1
loading

Summary of Contents for Honeywell Gent Vigilon A3 Mimic

  • Page 1 Data and Installation Vigilon A3 Mimic panel by Honeywell VIG-MIM-A3 Customised Mimic Technical Data Panel dimensions height 403mm, width 338mm, depth 101mm Weight 7.9Kg without batteries 10.5Kg with batteries Storage temperature -10 to 55ºC Operating temperature 0 to 45ºC Relative humidity...
  • Page 2 5-off Top New Shorter Card ONLY ³ means equal to or greater than As a Customised Mimic panel the system control panel must have the latest card software. by Honeywell VIGILON FIRE SYSTEM NOT YET IN SERVICE Installation AWAITING COMMISSIONING...
  • Page 3 A3 Mimic Panel Data and installation External wiring Loop OUT Loop COM From Loop IN Mains fused spur 3.15A(T) mains fuse Master Repeat Card 0C LC 01 L1 02 L2 0C LC 01 L1 02 L2 RESET WRITE PROTECT DANGER The external cables are routed into the back box using the cable entry points on the back box.
  • Page 4 Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.