Supported Modbus Functions; Overview; Function Codes 01/02: Read Relay Coil / Digital Input Status - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

6.2 SUPPORTED MODBUS FUNCTIONS

6.2 SUPPORTED MODBUS FUNCTIONS
The following functions are supported by the 469:
01 - Read Relay Coil
02 - Read Digital Input Status
03 - Read Setpoints and Actual Values
04 - Read Setpoints and Actual Values
05 - Execute Operation
06 - Store Single Setpoint
07 - Read Device Status
08 - Loopback Test
16 - Store Multiple Setpoints
Modbus implementation:
469 Implementation:
For the 469 implementation of Modbus, these commands can be used to read Relay Coil Status or Digital Input
Status.
a) FUNCTION 01
The standard implementation requires the following: slave address (one byte), function code (one byte), start-
ing relay coil (two bytes), number of coils to read (two bytes), and CRC (two bytes). The slave response is the
6
slave address (one byte), function code (one byte), relay coil mask byte count (one byte; always 01 since only
six relay coils), bit mask indicating the status of requested relay coils (one byte), and CRC (two bytes).
b) FUNCTION 02
The standard implementation requires the following: slave address (one byte), function code (one byte), start-
ing digital input (two byte), number of digital inputs to read (two bytes), and CRC (two bytes). The slave
response is the slave address (one byte), function code (one byte), byte count of digital input mask (one byte),
bit mask indicating the status of requested digital inputs (one or two bytes), and CRC (two bytes).
Note: the CRC is sent as a two byte number with the low order byte sent first.
6-4

6.2.2 FUNCTION CODES 01/02: READ RELAY COIL / DIGITAL INPUT STATUS

Read Coil and Input Status
Read Relay Coil and Digital Input Status
469 Motor Management Relay
6 COMMUNICATIONS

6.2.1 OVERVIEW

GE Power Management