GE C60 Instruction Manual

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents
GE Industrial Systems
C60 Breaker Management Relay
UR Series Instruction Manual
C60 Revision: 2.9X
Manual P/N: 1601-0100-B8 (GEK-106376)
Copyright © 2004 GE Multilin
E200431
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
LISTED
MEASURING EQUIP.
Tel: (905) 294-6222 Fax: (905) 201-2098
36GN
Internet: http://www.GEindustrial.com/multilin
Manufactured under an
ISO9000 Registered system.
Table of Contents
loading

Summary of Contents for GE C60

  • Page 1 GE Industrial Systems C60 Breaker Management Relay UR Series Instruction Manual C60 Revision: 2.9X Manual P/N: 1601-0100-B8 (GEK-106376) Copyright © 2004 GE Multilin E200431 GE Multilin 215 Anderson Avenue, Markham, Ontario Canada L6E 1B3 LISTED MEASURING EQUIP. Tel: (905) 294-6222 Fax: (905) 201-2098 36GN Internet: http://www.GEindustrial.com/multilin...
  • Page 3 GE Industrial Systems ADDENDUM This Addendum contains information that relates to the C60 relay, version 2.9X. This addendum lists a number of information items that appear in the instruction manual GEK-106376 (1601-0100-B8) but are not included in the cur- rent C60 operations.
  • Page 5: Table Of Contents

    1.3 URPC SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-5 1.3.2 SOFTWARE INSTALLATION ................1-5 ® 1.3.3 CONNECTING URPC WITH THE C60............1-6 1.4 UR HARDWARE 1.4.1 MOUNTING AND WIRING................. 1-8 1.4.2 COMMUNICATIONS..................1-8 1.4.3 FACEPLATE DISPLAY ..................1-8 1.5 USING THE RELAY 1.5.1...
  • Page 6 FLEXLOGIC™ TIMERS ...................5-43 5.4.7 FLEXELEMENTS™ ..................5-44 5.5 GROUPED ELEMENTS 5.5.1 OVERVIEW ......................5-48 5.5.2 SETTING GROUP ....................5-48 5.5.3 BREAKER FAILURE ..................5-48 5.5.4 VOLTAGE ELEMENTS ..................5-58 5.6 CONTROL ELEMENTS 5.6.1 OVERVIEW ......................5-62 5.6.2 SETTING GROUPS..................5-62 5.6.3 SYNCHROCHECK ...................5-63 C60 Breaker Management Relay GE Multilin...
  • Page 7 DATA LOGGER ....................6-16 6.4.6 MAINTENANCE ....................6-17 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION .................. 6-18 6.5.2 FIRMWARE REVISIONS ................. 6-18 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ..................7-1 7.1.2 VIRTUAL INPUTS....................7-1 GE Multilin C60 Breaker Management Relay...
  • Page 8 FUNCTION CODE 10H: STORE MULTIPLE SETTINGS ......... B-6 B.1.10 EXCEPTION RESPONSES................B-6 B.2 FILE TRANSFERS ® B.2.1 OBTAINING UR FILES USING MODBUS PROTOCOL ......... B-7 ® B.2.2 MODBUS PASSWORD OPERATION............. B-8 B.3 MEMORY MAPPING ® B.3.1 MODBUS MEMORY MAP ................B-9 C60 Breaker Management Relay GE Multilin...
  • Page 9 COUNTERS .....................E-14 E.3.4 ANALOG INPUTS ....................E-15 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO C60 MANUAL................F-1 F.2 TABLES AND FIGURES F.2.1 LIST OF TABLES....................F-3 F.2.2 LIST OF FIGURES..................... F-4 F.3 ABBREVIATIONS F.3.1 STANDARD ABBREVIATIONS ................. F-6 F.4 WARRANTY...
  • Page 10 TABLE OF CONTENTS C60 Breaker Management Relay GE Multilin...
  • Page 11: Getting Started

    • registration card (attached as the last page of the manual) • Fill out the registration form and mail it back to GE Multilin (include the serial number located on the rear nameplate). • For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin Home Page at http://www.GEindustrial.com/multilin.
  • Page 12: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. C60 Breaker Management Relay...
  • Page 13: Ur Hardware Architecture

    The remote outputs interface to the remote inputs of other UR devices. Remote outputs are FlexLogic™ operands inserted into UCA2 GOOSE messages and are of two assignment types: DNA standard functions and USER defined functions. GE Multilin C60 Breaker Management Relay...
  • Page 14: Ur Software Architecture

    MENU section. An explanation of the use of inputs from CTs and VTs is in the INTRODUCTION TO AC SOURCES section. A description of how digital signals are used and routed within the relay is contained in the INTRODUCTION TO FLEX- LOGIC™ section. C60 Breaker Management Relay GE Multilin...
  • Page 15: Urpc ® Software

    10. Subsequently, double click on the URPC software icon to activate the application. Refer to the HUMAN INTERFACES chapter in this manual and the URPC Software Help program for more information about the URPC software interface. NOTE GE Multilin C60 Breaker Management Relay...
  • Page 16: Connecting Urpc ® With The C60

    Click the "OK" button then click "Finish". The new Site List tree will be added to the Site List window (or Online window) located in the top left corner of the main URPC window. The Site Device has now been configured for RS232 communications. Proceed to Section c) CONNECTING TO THE RELAY below to begin communications. C60 Breaker Management Relay GE Multilin...
  • Page 17 In a few moments, the flashing light should turn green, indicating that URPC is communicating with the relay. Refer to the HUMAN INTERFACES chapter in this manual and the URPC Software Help program for more information about the URPC software interface. NOTE GE Multilin C60 Breaker Management Relay...
  • Page 18: Ur Hardware

    This device (catalog number F485) connects to the computer using a "straight-through" serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C60 rear communications port. The con- verter terminals (+, –, GND) are connected to the C60 communication module (+, –, COM) terminals. Refer to the CPU COMMUNICATION PORTS section in the HARDWARE chapter for option details.
  • Page 19: Using The Relay

    MESSAGE key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE) ## SETTINGS # PASSWORD ACCESS LEVEL: ## PRODUCT SETUP # SECURITY Restricted ## SETTINGS ## SYSTEM SETUP GE Multilin C60 Breaker Management Relay...
  • Page 20: Relay Activation

    1.5.5 BATTERY TAB The battery tab is installed in the power supply module before the C60 shipped from the factory. The battery tab prolongs battery life in the event the relay is powered down for long periods of time before installation. The battery is responsible for backing up event records, oscillography, data logger, and real-time clock information when the relay is powered off.
  • Page 21: Product Description

    2 PRODUCT DESCRIPTION 2.1 INTRODUCTION 2.1.1 OVERVIEW The C60 Breaker Management Relay is a microprocessor based relay designed for breaker monitoring, control and protec- tion. Voltage and current metering is built into the relay as a standard feature. Current parameters are available as total wave- form RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
  • Page 22 Digital Elements (16) Oscillography Disturbance Detection Setting Groups (8) Event Recorder Transducer I/O Fault Detector and Fault Report User Definable Displays FlexElements™ (16) User Programmable LEDs FlexLogic™ Equations Virtual Inputs (32) Virtual Outputs (64) C60 Breaker Management Relay GE Multilin...
  • Page 23: Ordering

    HARDWARE chapter). Table 2–3: ORDER CODES C60 - * 00 - H C * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal Mount...
  • Page 24 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703, Channel 2 - 1550 nm, single -mode, LASER TRANSDUCER I/O 8 RTD Inputs 4 dcmA Inputs, 4 RTD Inputs 8 dcmA Inputs C60 Breaker Management Relay GE Multilin...
  • Page 25: Specifications

    ±0.5% of reading from 10 to 208 V Curve Shapes: GE IAV Inverse Definite Time Curve Multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Timing Accuracy: ±3% of operate time or ±4 ms (whichever is greater) GE Multilin C60 Breaker Management Relay...
  • Page 26: User-Programmable Elements

    1 sec.; 1, 5, 10, 15, 20, 30, 60 min. Storage Capacity: (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days ↓ ↓ 60-minute rate: 01 channel for NN days 16 channels for NN days C60 Breaker Management Relay GE Multilin...
  • Page 27: Metering

    ±0.2% of full scale Relay Burden: < 0.25 VA at 120 V Type: Passive Conversion Range: 1 to 275 V Voltage Withstand: cont. at 260 V to neutral 1 min./hr at 420 V to neutral GE Multilin C60 Breaker Management Relay...
  • Page 28 2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION RTD INPUTS 100 Ω Platinum, 100 & 120 Ω Nickel, 10 Types (3-wire): Ω Copper Sensing Current: 5 mA Range: –50 to +250°C Accuracy: ±2°C Isolation: 36 V pk-pk C60 Breaker Management Relay GE Multilin...
  • Page 29: Power Supply

    2.2.9 ENVIRONMENTAL Operating Temperatures: Humidity (noncondensing): IEC 60068-2-30, 95%, Variant 1, 6 Cold: IEC 60028-2-1, 16 h at –40°C days Dry Heat: IEC 60028-2-2, 16 h at 85°C Altitude: Up to 2000 m Installation Category: GE Multilin C60 Breaker Management Relay...
  • Page 30: Type Tests

    IEC 1010-1 EMC 81/336/EEC: EN 50081-2 EN 50082-2 2.2.13 MAINTENANCE Cleaning: Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. 2-10 C60 Breaker Management Relay GE Multilin...
  • Page 31: Hardware

    RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. UR SERIES UR SERIES Figure 3–1: C60 VERTICAL MOUNTING AND DIMENSIONS GE Multilin C60 Breaker Management Relay...
  • Page 32 3.1 DESCRIPTION 3 HARDWARE Figure 3–2: C60 VERTICAL SIDE MOUNTING INSTALLATION C60 Breaker Management Relay GE Multilin...
  • Page 33 3 HARDWARE 3.1 DESCRIPTION Figure 3–3: C60 VERTICAL SIDE MOUNTING REAR DIMENSIONS REMOTE MOUNTING HORIZONTAL (19" 4RU) BEZEL OUTLINE 8x0.156 %%c TOP VIEW 10.90" 8.97" (276.8) (227.8) 9.80" (248.9) 0.375 (9.5) 5.000 0.375 (127.0) (9.5) 9.520 (241.8) Brackets repositioned for switchgear mtg.
  • Page 34: Module Withdrawal/Insertion

    Type 9C and 9D CPU modules are equipped with 10BaseT and 10BaseF Ethernet connectors for communications. These connectors must be individually disconnected from the module before the it can be removed from the chas- sis. NOTE C60 Breaker Management Relay GE Multilin...
  • Page 35: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–7: EXAMPLE OF MODULES IN F & H SLOTS GE Multilin C60 Breaker Management Relay...
  • Page 36: Wiring

    PROVIDED Supply (Rear View) This diagram is based on the following order code: C60-A00-HCL-F8A-H6B-M6K-P5F. The purpose of this diagram is to provide an example of how the relay is typically wired, not specifi- CAUTION cally how to wire your own relay. Please refer to the following pages for examples to help you wire your relay correctly based on your own relay configuration and order code.
  • Page 37: Dielectric Strength Ratings And Testing

    Table 3–2: CONTROL POWER VOLTAGE RANGE RANGE NOMINAL VOLTAGE 24 to 48 V (DC only) 125 to 250 V The power supply module provides power to the relay and supplies power for dry contact input connections. GE Multilin C60 Breaker Management Relay...
  • Page 38: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the TYPICAL WIRING DIAGRAM. The exact placement of a zero sequence CT so that ground fault current will be detected is shown below. Twisted pair cabling on the zero sequence CT is recommended. C60 Breaker Management Relay GE Multilin...
  • Page 39 Figure 3–11: CT/VT MODULE WIRING CURRENT INPUTS 8C / 8D / 8Z CTMDL8CD.cdr (P/O 827831A1.CDR) Figure 3–12: CT MODULE WIRING Wherever a tilde “~” symbol appears, substitute with the Slot Position of the module. NOTE GE Multilin C60 Breaker Management Relay...
  • Page 40: Contact Inputs/Outputs

    Cont Op x Ioff Load b) Current with optional voltage monitoring Current monitoring only Both voltage and current monitoring (external jumper a-b is required) Load c) No monitoring 827821A4.CDR Figure 3–13: FORM-A CONTACT FUNCTIONS 3-10 C60 Breaker Management Relay GE Multilin...
  • Page 41 2 Inputs Fast Form-C ~6a, ~6c 2 Inputs ~6a, ~6c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs Fast Form-C GE Multilin C60 Breaker Management Relay 3-11...
  • Page 42 Form-A Form-A Form-A Form-A Form-A Form-A Form-A ~5a, ~5c 2 Inputs Form-A ~6a, ~6c 2 Inputs Form-A ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-12 C60 Breaker Management Relay GE Multilin...
  • Page 43 CONTACT IN CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON COMMON SURGE CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE Figure 3–14: DIGITAL I/O MODULE WIRING (SHEET 1 OF 2) GE Multilin C60 Breaker Management Relay 3-13...
  • Page 44 SURGE 827719AR.CDR Sheet 2 of 2 Figure 3–15: DIGITAL I/O MODULE WIRING (SHEET 2 OF 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT CONNECTIONS OR EQUIP- MENT DAMAGE MAY RESULT. CAUTION 3-14 C60 Breaker Management Relay GE Multilin...
  • Page 45 DC current flowing through the contacts when the Form-A contact closes. If enabled, the cur- rent monitoring can be used as a seal-in signal to ensure that the Form-A contact does not attempt to break the energized inductive coil circuit and weld the output contacts. GE Multilin C60 Breaker Management Relay 3-15...
  • Page 46: Transducer Inputs/Outputs

    5 & Comp dcmA In Comp Comp dcmA In Return for RTD 7 & Comp SURGE Return for RTD 7 & Comp SURGE Comp ANALOGIO.CDR SURGE FROM 827831A6.CDR Figure 3–17: TRANSDUCER I/O MODULE WIRING 3-16 C60 Breaker Management Relay GE Multilin...
  • Page 47: Rs232 Faceplate Program Port

    COM 1 10BaseT TEST ONLY 10BaseT TEST ONLY RS485 RS485 RS485 COM 2 COM 2 COM 2 IRIG-B IRIG-B IRIG-B SURGE GROUND SURGE SURGE COMMOD.CDR P/O 827719C2.CDR Figure 3–19: CPU MODULE COMMUNICATIONS WIRING GE Multilin C60 Breaker Management Relay 3-17...
  • Page 48 EACH END (TYPICALLY 120 Ohms and 1 nF) 485 - SURGE COMP 485COM UP TO 32 DEVICES, RELAY MAXIMUM 4000 FEET 485 + 485 - SURGE COMP 485COM LAST DEVICE 827757A5.DWG Figure 3–20: RS485 SERIAL CONNECTION 3-18 C60 Breaker Management Relay GE Multilin...
  • Page 49: Irig-B

    (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized. GE Multilin C60 Breaker Management Relay 3-19...
  • Page 50 3.2 WIRING 3 HARDWARE 3-20 C60 Breaker Management Relay GE Multilin...
  • Page 51: Human Interfaces

    ® The URPC software, provided with every C60 relay, can be run from any computer supporting Microsoft Windows 95, 98, or NT. This chapter provides a summary of the basic URPC software interface features. The URPC Help file provides details for getting started and using the URPC software interface.
  • Page 52 “EEPROM DATA ERROR” message displayed after upgrading/downgrading the firmware is a resettable, self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This message does not signal any problems when appearing after firmware upgrades. C60 Breaker Management Relay GE Multilin...
  • Page 53: Urpc Software Main Window

    Settings List control bar window Device data view window(s), with common tool bar Settings File data view window(s), with common tool bar Workspace area with data view tabs Status bar Figure 4–1: URPC SOFTWARE MAIN WINDOW GE Multilin C60 Breaker Management Relay...
  • Page 54: Faceplate Interface

    IN SERVICE VOLTAGE TROUBLE CURRENT RESET TEST MODE FREQUENCY LED PANEL 1 TRIP OTHER USER 1 ALARM PHASE A PICKUP PHASE B USER 2 PHASE C NEUTRAL/GROUND USER 3 Figure 4–3: UR VERTICAL FACEPLATE PANELS C60 Breaker Management Relay GE Multilin...
  • Page 55: Led Indicators

    OTHER: Indicates a composite function was involved. • PHASE A: Indicates Phase A was involved. • PHASE B: Indicates Phase B was involved. • PHASE C: Indicates Phase C was involved. • NEUTRAL/GROUND: Indicates neutral or ground was involved. GE Multilin C60 Breaker Management Relay...
  • Page 56 LED settings must be entered as shown in the USER-PROGRAMMABLE LEDs section of the SET- TINGS chapter. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both LED panels 2 and 3 as explained in the next section. C60 Breaker Management Relay GE Multilin...
  • Page 57: Custom Labeling Of Leds

    For Position and Size enable the "Center image" and "Maintain aspect ratio" check boxes and press "OK", then "OK" once more to print. From the printout, cut-out the BACKGROUND TEMPLATE from the three windows (use the cropmarks as a guide). GE Multilin C60 Breaker Management Relay...
  • Page 58: Display

    The key may be pressed at any time for context sensitive help messages. The key stores altered setting values. MENU HELP MESSAGE ESCAPE VALUE ENTER Figure 4–8: KEYPAD C60 Breaker Management Relay GE Multilin...
  • Page 59: Breaker Control

    4.2.7 BREAKER CONTROL The C60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
  • Page 60: Menus

    MESSAGE key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE) ## SETTINGS # PASSWORD ACCESS LEVEL: ## PRODUCT SETUP # SECURITY Restricted ## SETTINGS ## SYSTEM SETUP 4-10 C60 Breaker Management Relay GE Multilin...
  • Page 61: Changing Settings

    While at the maximum value, pressing the VALUE key again will allow the setting selection to continue upward from the minimum value. The VALUE key decrements the displayed value by the step value, down to the GE Multilin C60 Breaker Management Relay 4-11...
  • Page 62 Flash messages will sequentially appear for several seconds each. For the case of a text setting message, the key displays how to edit and store a new value. 4-12 C60 Breaker Management Relay GE Multilin...
  • Page 63 Press the key until the 'SETTINGS' header flashes momentarily and the ‘SETTINGS PRODUCT SETUP’ mes- sage appears on the display. Press the MESSAGE key until the ‘ACCESS LEVEL:’ message appears on the display. GE Multilin C60 Breaker Management Relay 4-13...
  • Page 64 (for each security level) before a new password can be entered. In the event that a password has been lost (forgotten), submit the corresponding Encrypted Password from the PASS- WORD SECURITY menu to the Factory for decoding. 4-14 C60 Breaker Management Relay GE Multilin...
  • Page 65: Overview

    # LINE See page 5-28. # BREAKERS See page 5-29. ## SETTINGS # FLEXLOGIC See page 5-43. ## FLEXLOGIC # EQUATION EDITOR # FLEXLOGIC See page 5-43. # TIMERS # FLEXELEMENTS See page 5-44. GE Multilin C60 Breaker Management Relay...
  • Page 66 # CONTACT OUTPUTS See page 5-88. # VIRTUAL OUTPUTS See page 5-89. # REMOTE DEVICES See page 5-89. # REMOTE INPUTS See page 5-90. # REMOTE OUTPUTS See page 5-91. # DNA BIT PAIRS C60 Breaker Management Relay GE Multilin...
  • Page 67: Introduction To Elements

    This setting programs the element to be operational when selected as "Enabled". The factory default is "Disabled". Once programmed to "Enabled", any element associated with the Function becomes active and all options become available. NAME Setting This setting is used to uniquely identify the element. GE Multilin C60 Breaker Management Relay...
  • Page 68: Introduction To Ac Sources

    BACKGROUND The C60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail- ure element.
  • Page 69 Source as 'Wdg 1 Current'. Once the Sources have been configured, the user has them available as selections for the choice of input signal for the pro- tection elements and as metered quantities. GE Multilin C60 Breaker Management Relay...
  • Page 70 Source is a transformer winding, on which a three phase voltage is mea- sured, and the sum of the currents from CTs on each of two breakers is required to measure the winding current flow. C60 Breaker Management Relay GE Multilin...
  • Page 71: Product Setup

    If an entered password is lost (or forgotten), consult the factory service department with the corresponding ENCRYPTED PASSWORD If the password and password are set the same, the one password will allow access to SETTING COMMAND commands and settings. NOTE GE Multilin C60 Breaker Management Relay...
  • Page 72: Display Properties

    0 ms The C60 is equipped with up to 3 independent serial communication ports. The faceplate RS232 port is intended for local use and has fixed parameters of 19200 baud and no parity. The rear COM1 port type will depend on the CPU ordered: it may be either an Ethernet or an RS485 port.
  • Page 73 When the NSAP address, any TCP/UDP Port Number, or any User Map setting (when used with DNP) is changed, it will not become active until power to the relay has been cycled (OFF/ON). NOTE GE Multilin C60 Breaker Management Relay...
  • Page 74 MODBUS SLAVE ADDRESS ports each C60 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
  • Page 75 The C60 supports the Distributed Network Protocol (DNP) version 3.0. The C60 can be used as a DNP slave device con- nected to a single DNP master (usually either an RTU or a SCADA master station). Since the C60 maintains one set of DNP data change buffers and connection information, only one DNP master should actively communicate with the C60 at one time.
  • Page 76 DNP VOLTAGE SCALE FACTOR Input points that are voltages will be returned with values 1000 times smaller (e.g. a value of 72000 V on the C60 will be returned as 72). These settings are useful when Analog Input values must be adjusted to fit within certain ranges in DNP masters.
  • Page 77 The web pages can be accessed by connecting the UR and a computer to an ethernet network. The Main Menu will be dis- played in the web browser on the computer simply by entering the IP address of the C60 into the "Address" box on the web browser.
  • Page 78 The C60 supports the IEC 60870-5-104 protocol. The C60 can be used as an IEC 60870-5-104 slave device connected to a single master (usually either an RTU or a SCADA master station). Since the C60 maintains one set of IEC 60870-5-104 data change buffers, only one master should actively communicate with the C60 at one time.
  • Page 79: Modbus User Map

    Pre-fault current and voltage phasors (one-quarter cycle before the trigger) • Fault current and voltage phasors (three-quarter cycle after the trigger) • Target Messages that are set at the time of triggering • Events (9 before trigger and 7 after trigger) GE Multilin C60 Breaker Management Relay 5-15...
  • Page 80: Oscillography

    # DIGITAL CHANNELS Range: FlexLogic™ operand DIGITAL CHANNEL 2: ↓ Range: FlexLogic™ operand DIGITAL CHANNEL 63: Range: 1 to 16 channels # ANALOG CHANNELS Range: Off, any analog Actual Value parameter ANALOG CHANNEL 1: ↓ 5-16 C60 Breaker Management Relay GE Multilin...
  • Page 81 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and Analog Input modules, no analog traces will appear in the file; only the digital traces will appear. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. WARNING GE Multilin C60 Breaker Management Relay 5-17...
  • Page 82: Data Logger

    POWER DEMAND METHOD: MESSAGE Rolling Demand Thermal Exponential Range: 5, 10, 15, 20, 30, 60 minutes DEMAND INTERVAL: MESSAGE 15 MIN Range: FlexLogic™ operand DEMAND TRIGGER: MESSAGE Note: for calculation using Method 2a 5-18 C60 Breaker Management Relay GE Multilin...
  • Page 83 This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and indicates the demand over the time interval just preceding the time of update. GE Multilin C60 Breaker Management Relay 5-19...
  • Page 84: User-Programmable Leds

    LED 11 Operand BREAKER 1 TROUBLE LED 23 Operand AR RIP LED 12 Operand LED 24 Operand AR LO Refer to the CONTROL OF SETTINGS GROUPS example in the CONTROL ELEMENTS section for group activation. 5-20 C60 Breaker Management Relay GE Multilin...
  • Page 85: Flex State Parameters

    Range: 0 to 65535 in steps of 1 DISP 1 ITEM 4 MESSAGE Range: 0 to 65535 in steps of 1 DISP 1 ITEM 5: MESSAGE # USER DISPLAY 2 ↓ # USER DISPLAY 8 GE Multilin C60 Breaker Management Relay 5-21...
  • Page 86 This item is not being used - there is no corresponding DISP 1 ITEM 5: MESSAGE Tilde marker in Top or Bottom lines. Shows the resultant display content. USER DISPLAYS Current X 0.850 A → Current Y 0.327 A 5-22 C60 Breaker Management Relay GE Multilin...
  • Page 87: Installation

    This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the UCA2/MMS protocol. GE Multilin C60 Breaker Management Relay 5-23...
  • Page 88: System Setup

    SRC1 currents, then PKP level of 1 pu will operate on 1000 A primary. The same rule will apply for sums of currents from CTs with different secondary taps (5 A and 1 A). 5-24 C60 Breaker Management Relay GE Multilin...
  • Page 89: Power System

    GE Multilin C60 Breaker Management Relay 5-25...
  • Page 90: Signal Sources

    CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each Source is entered, including specifying which CTs will be summed together. 5-26 C60 Breaker Management Relay GE Multilin...
  • Page 91 An example of the use of Sources, with a relay with three CT/VT modules, is shown in the diagram below. A relay could have the following hardware configuration: INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 GE Multilin C60 Breaker Management Relay 5-27...
  • Page 92: Line

    These settings specify the characteristics of the line. The line impedance value should be entered as secondary ohms. This data is used for fault location calculations. See the !" menu for assigning SETTINGS PRODUCT SETUP FAULT REPORT the Source and Trigger for fault calculations. 5-28 C60 Breaker Management Relay GE Multilin...
  • Page 93: Breakers

    No. 1. BREAKER 1 FUNCTION: Set to "Enable" to allow the operation of any breaker control feature. BREAKER1 PUSH BUTTON CONTROL: Set to "Enable" to allow faceplate push button operations. BREAKER 1 NAME: GE Multilin C60 Breaker Management Relay 5-29...
  • Page 94 USER 1 on the relay faceplate) until the automatic de-selection of the breaker, so that the breaker does not remain selected indefinitely. This setting is active only if is "Enabled". BREAKER PUSHBUTTON CONTROL 5-30 C60 Breaker Management Relay GE Multilin...
  • Page 95 5 SETTINGS 5.3 SYSTEM SETUP Figure 5–5: DUAL BREAKER CONTROL SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-31...
  • Page 96: Introduction To Flexlogic

    Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. 5-32 C60 Breaker Management Relay GE Multilin...
  • Page 97 The virtual input is presently in the ON state. Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1"). GE Multilin C60 Breaker Management Relay 5-33...
  • Page 98 5.4 FLEXLOGIC™ 5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 1 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: AR ENABLED Autoreclosure is enabled and ready to perform...
  • Page 99 5 SETTINGS 5.4 FLEXLOGIC™ Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 2 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: FLEXELEMENT 1 PKP FlexElement 1 has picked up FlexElements™ FLEXELEMENT 1 OP FlexElement 1 has operated FLEXELEMENT 1 DPO FlexElement 1 has dropped out ↓...
  • Page 100 5.4 FLEXLOGIC™ 5 SETTINGS Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 3 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION RESETTING RESET OP Reset command is operated (set by all 3 operands below) RESET OP (COMMS) Communications source of the reset command...
  • Page 101: Flexlogic™ Rules

    Assigning the output of an operator to a Virtual Output terminates the equation. A timer operator (e.g. "TIMER 1") or virtual output assignment (e.g. " = Virt Op 1") may only be used once. If this rule is broken, a syntax error will be declared. GE Multilin C60 Breaker Management Relay 5-37...
  • Page 102: Flexlogic™ Evaluation

    Virtual Output and assigned the next available number (i.e. Virtual Output 3). The final output must also be assigned to a Virtual Output as Virtual Output 4, which will be programmed in the contact output section to operate relay H1 (i.e. Output Contact H1). 5-38 C60 Breaker Management Relay GE Multilin...
  • Page 103 Until accustomed to using FlexLogic™, it is suggested that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below. GE Multilin C60 Breaker Management Relay 5-39...
  • Page 104 FLEXLOGIC ENTRY n: =Virt Op 3 827030A2.VSD Figure 5–12: FLEXLOGIC™ EQUATION & LOGIC FOR VIRTUAL OUTPUT 3 Repeating the process described for VIRTUAL OUTPUT 3, select the FlexLogic™ parameters for Virtual Output 4. 5-40 C60 Breaker Management Relay GE Multilin...
  • Page 105 It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame- ters into a logic diagram. The result of this process is shown below, which is compared to figure: LOGIC FOR VIRTUAL OUTPUT 4, as a check. GE Multilin C60 Breaker Management Relay 5-41...
  • Page 106 Virt Op 1 On Virt Op 2 On Virt Ip 1 On DIG ELEM 1 PKP XOR(2) Virt Op 3 On OR(4) LATCH (S,R) Virt Op 3 On TIMER 1 Cont Ip H1c On OR(3) 5-42 C60 Breaker Management Relay GE Multilin...
  • Page 107: Flexlogic Equation Editor

    This setting is used to set the time delay to pickup. If a pickup delay is not required, set this function to "0". TIMER 1 DROPOUT DELAY: This setting is used to set the time delay to dropout. If a dropout delay is not required, set this function to "0". GE Multilin C60 Breaker Management Relay 5-43...
  • Page 108: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-44 C60 Breaker Management Relay GE Multilin...
  • Page 109 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin C60 Breaker Management Relay 5-45...
  • Page 110 DIRECTION = Under; FLEXELEMENT COMP MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT COMP MODE = Absolute; FlexElement 1 OpSig 842706A1.CDR Figure 5–16: FLEXELEMENT™ INPUT MODE SETTING 5-46 C60 Breaker Management Relay GE Multilin...
  • Page 111 "Delta". FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin C60 Breaker Management Relay 5-47...
  • Page 112: Grouped Elements

    BF1 TIMER 1 PICKUP MESSAGE DELAY: 0.000 s Range: Yes, No BF1 USE TIMER 2: MESSAGE Range: 0.000 to 65.535 s in steps of 0.001 BF1 TIMER 2 PICKUP MESSAGE DELAY: 0.000 s 5-48 C60 Breaker Management Relay GE Multilin...
  • Page 113 Because breaker failure can result in tripping a large number of breakers and this affects system safety and stability, a very high level of security is required. GE Multilin C60 Breaker Management Relay 5-49...
  • Page 114 FlexLogic™ operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an adjustable period. • Target message indicating a failed breaker has been declared • Illumination of the faceplate TRIP LED (and the PHASE A, B or C LED, if applicable) 5-50 C60 Breaker Management Relay GE Multilin...
  • Page 115 Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be signifi- cantly longer than the normal interrupting time. GE Multilin C60 Breaker Management Relay 5-51...
  • Page 116 BF1 BKR POS2 B (valid only for 1-pole breaker failure schemes): Selects the FlexLogic™ operand that represents the protected breaker normal-type auxiliary switch contact on pole B (52/ a). This may be a multiplied contact. 5-52 C60 Breaker Management Relay GE Multilin...
  • Page 117 The overcurrent detectors have ganged settings. Upon operation of the breaker failure element for a single pole trip command, a 3-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin C60 Breaker Management Relay 5-53...
  • Page 118 BF1 SOURCE : Initiated Ph C PICKUP : TO SHEET 2 OF 2 PICKUP PICKUP PICKUP TO SHEET 2 OF 2 (827070.CDR) 827069A5.CDR Figure 5–18: BREAKER FAILURE 1-POLE [INITIATE] (Sheet 1 of 2) 5-54 C60 Breaker Management Relay GE Multilin...
  • Page 119 BF1 BKR POS2 FLEXLOGIC OPERAND Off=0 BKR FAIL 1 T3 OP SETTING BF1 BKR POS2 Off=0 SETTING BF1 BREAKER TEST ON: Off=0 827070A3.CDR Figure 5–19: BREAKER FAILURE 1-POLE (TIMERS) [Sheet 2 of 2] GE Multilin C60 Breaker Management Relay 5-55...
  • Page 120 5.5 GROUPED ELEMENTS 5 SETTINGS Figure 5–20: BREAKER FAILURE 3-POLE [INITIATE] (Sheet 1 of 2) 5-56 C60 Breaker Management Relay GE Multilin...
  • Page 121 5 SETTINGS 5.5 GROUPED ELEMENTS Figure 5–21: BREAKER FAILURE 3-POLE [TIMERS] (Sheet 2 of 2) GE Multilin C60 Breaker Management Relay 5-57...
  • Page 122: Voltage Elements

    = Pickup Level pickup At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE 20 30 80 90 100 110 % of V pickup Figure 5–22: INVERSE TIME UNDERVOLTAGE CURVES 5-58 C60 Breaker Management Relay GE Multilin...
  • Page 123 Source VT = Wye VCG or VCA Minimum FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP 827039A9.CDR Figure 5–23: PHASE UV1 SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-59...
  • Page 124 Vx Pickup AUX UV1 PKP AUX UV1 DPO SETTING SETTING AUX UV1 OP AUX UV1 MINIMUM AUX UV1 SIGNAL VOLTAGE: SOURCE: < AUX VOLT Vx Vx Minimum 827849A2.CDR Figure 5–24: AUXILIARY UNDERVOLTAGE SCHEME LOGIC 5-60 C60 Breaker Management Relay GE Multilin...
  • Page 125 AUX OV1 RESET Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–25: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-61...
  • Page 126: Control Elements

    The assigned VIRTUAL OUTPUT 1 operand is used to control the ON state of a particular settings group. Figure 5–26: EXAMPLE FLEXLOGIC™ CONTROL OF A SETTINGS GROUP 5-62 C60 Breaker Management Relay GE Multilin...
  • Page 127: Synchrocheck

    SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in ‘Hz’ between the two sources. A frequency difference between the two input voltage systems below this value is within the permissible limit for synchronism. GE Multilin C60 Breaker Management Relay 5-63...
  • Page 128 If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage is programmed in one of the Sources to be used for synchrocheck. Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye connected auxiliary voltage. 5-64 C60 Breaker Management Relay GE Multilin...
  • Page 129 ∆Φ × 2 30° If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using undervoltage control to by-pass the synchrocheck measurements (Dead Source function). GE Multilin C60 Breaker Management Relay 5-65...
  • Page 130 5.6 CONTROL ELEMENTS 5 SETTINGS Figure 5–27: SYNCHROCHECK SCHEME LOGIC 5-66 C60 Breaker Management Relay GE Multilin...
  • Page 131: Autoreclose

    Range: FlexLogic™ operand AR RESET: MESSAGE Range: 0 to 655.35 s in steps of 0.01 AR RESET TIME: MESSAGE 60.00 s Range: FlexLogic™ operand AR BKR CLOSED: MESSAGE Range: FlexLogic™ operand AR BLOCK: MESSAGE GE Multilin C60 Breaker Management Relay 5-67...
  • Page 132 Scheme is permitted to operate and shot count is reset to 0 Reclose In Progress Scheme has been initiated but the reclose cycle is not finished (successful or not) Lockout Scheme is not permitted to operate until reset received 5-68 C60 Breaker Management Relay GE Multilin...
  • Page 133 The pause signal blocks all three dead timers. When the "pause" signal disappears the autoreclose cycle is resumed by initiating the AR 3-P DEAD TIME 2 GE Multilin C60 Breaker Management Relay 5-69...
  • Page 134 (there is no initiating signal and the breakers are closed) the reset timer will time out, returning the scheme to the reset state, with the shot counter set to 0, making it ready for a new reclose cycle. 5-70 C60 Breaker Management Relay GE Multilin...
  • Page 135 During a reclose cycle, "Extended Zone 1" goes to 0 as soon as the first CLOSE BREAKER signal is issued (AR SHOT COUNT > 0) and remains 0 until the recloser goes back to Reset. GE Multilin C60 Breaker Management Relay 5-71...
  • Page 136 AR BKR CLOSED: This setting selects an operand that indicates that the breaker(s) are closed at the end of the reset time and the scheme can reset. 5-72 C60 Breaker Management Relay GE Multilin...
  • Page 137 This setting will prevent the autoreclose scheme from transferring the close signal to the second breaker unless a successful reclose of the first breaker occurs. GE Multilin C60 Breaker Management Relay 5-73...
  • Page 138 (breaker No. 2 for sequence 1-2 and breaker No. 1 for sequence 2-1) must be configured to trip NOTE three-pole for any type of fault Figure 5–28: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 1 OF 3) 5-74 C60 Breaker Management Relay GE Multilin...
  • Page 139 5 SETTINGS 5.6 CONTROL ELEMENTS Figure 5–29: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 2 OF 3) GE Multilin C60 Breaker Management Relay 5-75...
  • Page 140 (To sheet 1) FLEXLOGIC OPERAND BREAKER 1 ONE P OPEN FLEXLOGIC OPERAND BREAKER 2 ONE P OPEN BKR ONE POLE OPEN (To sheet 1) 827833A8.CDR Figure 5–30: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 3 OF 3) 5-76 C60 Breaker Management Relay GE Multilin...
  • Page 141 5 SETTINGS 5.6 CONTROL ELEMENTS Figure 5–31: EXAMPLE RECLOSING SEQUENCE GE Multilin C60 Breaker Management Relay 5-77...
  • Page 142: Digital Elements

    DIGITAL ELEMENT 01 INPUT: DIG ELEM 01 PKP Off = 0 DIG ELEM 01 OP INPUT = 1 SETTING DIGITAL ELEMENT 01 BLOCK: 827042A1.VSD Off = 0 Figure 5–32: DIGITAL ELEMENT SCHEME LOGIC 5-78 C60 Breaker Management Relay GE Multilin...
  • Page 143 DIG ELEM 1 INPUT: MESSAGE Cont Op 1 VOff DIG ELEM 1 PICKUP MESSAGE DELAY: 0.200 s DIG ELEM 1 RESET MESSAGE DELAY: 0.100 s DIG ELEM 1 BLOCK: MESSAGE Cont Ip 1 Off GE Multilin C60 Breaker Management Relay 5-79...
  • Page 144 RESISTANCE POWER SUPPLY (V DC) (OHMS) (WATTS) I = Current Monitor 1000 5000 V = Voltage Monitor 10000 25000 By-pass 25000 Resistor 50000 Trip Coil 827074A1.vsd DC– Figure 5–34: TRIP CIRCUIT EXAMPLE 2 5-80 C60 Breaker Management Relay GE Multilin...
  • Page 145: Digital Counters

    Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is received when the accumu- lated value is at the limit of –2,147,483,648 counts, the counter will rollover to +2,147,483,647. GE Multilin C60 Breaker Management Relay 5-81...
  • Page 146 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–35: DIGITAL COUNTER SCHEME LOGIC 5-82 C60 Breaker Management Relay GE Multilin...
  • Page 147: Monitoring Elements

    This setting is used to program the delay interval between the time the tripping sequence is initiated and the time the breaker contacts are expected to part, starting the integration of the measured current. BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. GE Multilin C60 Breaker Management Relay 5-83...
  • Page 148 COMMAND ACTUAL VALUE CLEAR BREAKER 1 ARCING AMPS: BKR 1 ARCING AMP A NO=0 BKR 1 ARCING AMP B YES=1 BKR 1 ARCING AMP C 827071A2.CDR Figure 5–37: BREAKER ARCING CURRENT SCHEME LOGIC 5-84 C60 Breaker Management Relay GE Multilin...
  • Page 149: Inputs / Outputs 5.7.1 Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the C60 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 150 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-86 C60 Breaker Management Relay GE Multilin...
  • Page 151: Virtual Inputs

    SETTING “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–39: VIRTUAL INPUTS SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-87...
  • Page 152: Uca Sbo Timer

    This can be realized in the UR using the ‘Cont Op 1 IOn’ FlexLogic™ operand to seal-in the Contact Output. For example, # CONTACT OUTPUT H1 CONTACT OUTPUT H1 ID Cont Op 1 OUTPUT H1 OPERATE: MESSAGE OUTPUT H1 SEAL-IN: MESSAGE Cont Op 1 CONTACT OUTPUT H1 MESSAGE EVENTS: Enabled 5-88 C60 Breaker Management Relay GE Multilin...
  • Page 153: Virtual Outputs

    The status of a remote device, where ‘Offline’ indicates ‘non-communicat- ing’, can be displayed. The GOOSE facility provides for 64 remote inputs and 32 remote outputs. GE Multilin C60 Breaker Management Relay 5-89...
  • Page 154: Remote Inputs

    For more information on GOOSE specifications, see REMOTE INPUTS/OUTPUTS OVERVIEW in the REMOTE DEVICES section. NOTE 5-90 C60 Breaker Management Relay GE Multilin...
  • Page 155: Remote Outputs: Dna Bit Pairs

    DownedOn Sync Closing SyncClsOff SyncClsOn Mode Report mode status of local GOOSE device Normal Test 28→32 Reserved For more information on GOOSE specifications, see REMOTE INPUTS/OUTPUTS OVERVIEW in the REMOTE DEVICES section. NOTE GE Multilin C60 Breaker Management Relay 5-91...
  • Page 156: Remote Outputs: Userst Bit Pairs

    RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting shown above selects the operand that will create the RESET OP (OPERAND) operand. 5-92 C60 Breaker Management Relay GE Multilin...
  • Page 157: Transducer I/O 5.8.1 Dcma Inputs

    Another example would be a Watt transducer with a span from –20 to +180 MW; in this case the MIN value would be –20 and the MAX value 180. Intermediate values between the MIN and MAX are scaled linearly. GE Multilin C60 Breaker Management Relay 5-93...
  • Page 158: Rtd Inputs

    This ID is also used to reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of RTD connected to the channel configures the channel. 5-94 C60 Breaker Management Relay GE Multilin...
  • Page 159: Testing 5.9.1 Test Mode

    ON. The state of each contact output may be programmed as Disabled, Energized, De-energized, or Freeze. The Freeze option maintains the output contact in the state at which it was frozen. All contact output operations return to normal when all the settings for this feature are disabled. GE Multilin C60 Breaker Management Relay 5-95...
  • Page 160 5.9 TESTING 5 SETTINGS 5-96 C60 Breaker Management Relay GE Multilin...
  • Page 161: Actual Values Main Menu

    # SOURCE SRC 4 # SOURCE SRC 5 # SOURCE SRC 6 # SYNCHROCHECK See page 6-12. # TRACKING FREQUENCY See page 6-13. # FLEXELEMENTS See page 6-13. # TRANSDUCER I/O See page 6-13. # DCMA INPUTS GE Multilin C60 Breaker Management Relay...
  • Page 162 # OSCILLOGRAPHY See page 6-16. # DATA LOGGER See page 6-16. # MAINTENANCE See page 6-17. ## ACTUAL VALUES # MODEL INFORMATION See page 6-18. ## PRODUCT INFO # FIRMWARE REVISIONS See page 6-18. C60 Breaker Management Relay GE Multilin...
  • Page 163: Virtual Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be "Offline" in which case the value shown is the programmed default state for the remote input. GE Multilin C60 Breaker Management Relay...
  • Page 164: Contact Outputs

    The present state of up to 16 programmed Remote Devices is shown here. The message indi- ALL REMOTE DEVICES ONLINE cates whether or not all programmed Remote Devices are online. If the corresponding state is "No", then at least one required Remote Device is not online. C60 Breaker Management Relay GE Multilin...
  • Page 165: Remote Devices Statistics

    There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit. 6.2.11 ETHERNET !" PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK # ETHERNET ETHERNET PRI LINK STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK GE Multilin C60 Breaker Management Relay...
  • Page 166 PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS C60 Breaker Management Relay GE Multilin...
  • Page 167 • ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. GE Multilin C60 Breaker Management Relay...
  • Page 168 POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–3: ILLUSTRATION OF THE UR CONVENTION FOR SYMMETRICAL COMPONENTS C60 Breaker Management Relay GE Multilin...
  • Page 169: Sources

    PHASOR Igd: MESSAGE 0.000 0.0° # PHASE VOLTAGE SRC 1 RMS Vag: # SRC 1 0.000 SRC 1 RMS Vbg: MESSAGE 0.000 SRC 1 RMS Vcg: MESSAGE 0.000 SRC 1 PHASOR Vag: MESSAGE 0.000 0.0° GE Multilin C60 Breaker Management Relay...
  • Page 170 REAL POWER MESSAGE φc: 0.000 SRC 1 REACTIVE PWR MESSAGE 3φ: 0.000 SRC 1 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 6-10 C60 Breaker Management Relay GE Multilin...
  • Page 171 DMD IB MAX: MESSAGE 0.000 SRC 1 DMD IB DATE: MESSAGE 200/07/31 16:30:07 SRC 1 DMD IC: MESSAGE 0.000 SRC 1 DMD IC MAX: MESSAGE 0.000 SRC 1 DMD IC DATE: MESSAGE 200/07/31 16:30:07 GE Multilin C60 Breaker Management Relay 6-11...
  • Page 172: Synchrocheck

    0.00 Hz The Actual Values menu for SYNCHROCHECK2 is identical to that of SYNCHROCHECK1. If a Synchrocheck Function setting is set to "Disabled", the corresponding Actual Values menu item will not be displayed. 6-12 C60 Breaker Management Relay GE Multilin...
  • Page 173: Tracking Frequency

    RTD INPUT xx -50 °C Actual values for each RTD input channel that is Enabled are displayed with the top line as the programmed channel "ID" and the bottom line as the value. GE Multilin C60 Breaker Management Relay 6-13...
  • Page 174: Fault Locator Operation

    = sought pu distance to fault, Z = positive sequence impedance of the line. The currents from the local and remote systems can be parted between their fault (F) and pre-fault load (pre) components: eqn. 2 Apre 6-14 C60 Breaker Management Relay GE Multilin...
  • Page 175 FAULT REPORT # SRC X 50DD OP 1 SEC DATE TIME FAULT FAULT TYPE LOCATOR FAULT LOCATION 3 _0 FAULT# RECLOSE SHOT SHOT # FROM AUTO RECLOSURE 827094A1.CDR Figure 6–5: FAULT LOCATOR SCHEME GE Multilin C60 Breaker Management Relay 6-15...
  • Page 176: Event Records

    It counts up at the defined sampling rate. If Data Logger channels are defined, then both values are static. Refer to the !" menu for clearing data logger records. COMMANDS CLEAR RECORDS 6-16 C60 Breaker Management Relay GE Multilin...
  • Page 177: Maintenance

    There is an identical Actual Value menu for each of the 2 Breakers. The values are in units of kA BKR 1 ARCING AMP cycles. Refer to the !" menu for clearing breaker arcing current records. COMMANDS CLEAR RECORDS GE Multilin C60 Breaker Management Relay 6-17...
  • Page 178: Model Information

    BOOT DATE: MESSAGE Date and time when the boot program was built. 2000/05/11 16:41:32 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. 6-18 C60 Breaker Management Relay GE Multilin...
  • Page 179: Clear Records

    COMMANDS CLEAR RECORDS Range: No, Yes ## COMMANDS CLEAR EVENT RECORDS? ## CLEAR RECORDS Range: No, Yes CLEAR OSCILLOGRAPHY? Range: No, Yes CLEAR DATA LOGGER? Range: No, Yes CLEAR BREAKER 1 ARCING AMPS? No GE Multilin C60 Breaker Management Relay...
  • Page 180 If an update occurs, the following message is shown. UPDATING... PLEASE WAIT There is no impact if there have been no changes to the hardware modules. When an update does not occur, the following message will be shown. ORDER CODE NOT UPDATED C60 Breaker Management Relay GE Multilin...
  • Page 181: Targets Menu

    • all other output relays are de-energized and are prevented from further operation • the faceplate IN SERVICE indicator is turned off • a RELAY OUT OF SERVICE event is recorded GE Multilin C60 Breaker Management Relay...
  • Page 182 One or more GOOSE devices are Event driven. Occurs when a Check GOOSE setup OFFLINE not responding device programmed to receive GOOSE messages stops receiving message. Time is 1 to 60 sec. depending on GOOSE protocol packets. C60 Breaker Management Relay GE Multilin...
  • Page 183: Commissioning

    DNP Unsol Response Timeout Trigger Position DNP Unsol Response Max Retries Trigger Source Unsol Response Dest Address AC Input Waveforms User Map for DNP Analogs FAULT REPORT Number of Sources in Analog List Fault Report Source GE Multilin C60 Breaker Management Relay...
  • Page 184: Product Setup

    Digital Channel 39 Channel 3 Digital Channel 40 Channel 4 Digital Channel 41 Channel 5 Digital Channel 42 Channel 6 Digital Channel 43 Channel 7 Channel 8 Digital Channel 44 Digital Channel 45 Channel 9 C60 Breaker Management Relay GE Multilin...
  • Page 185 LED 14 Operand LED 37 Type LED 14 Type LED 38 Operand LED 15 Operand LED 38 Type LED 15 Type LED 39 Operand LED 16 Operand LED 39 Type LED 16 Type LED 40 Operand GE Multilin C60 Breaker Management Relay...
  • Page 186 Flex State Parameter 72 Flex State Parameter 26 Flex State Parameter 73 Flex State Parameter 27 Flex State Parameter 74 Flex State Parameter 28 Flex State Parameter 75 Flex State Parameter 29 Flex State Parameter 76 C60 Breaker Management Relay GE Multilin...
  • Page 187 Flex State Parameter 166 Flex State Parameter 120 Flex State Parameter 167 Flex State Parameter 121 Flex State Parameter 168 Flex State Parameter 122 Flex State Parameter 169 Flex State Parameter 123 Flex State Parameter 170 GE Multilin C60 Breaker Management Relay...
  • Page 188 Disp 1 Item 1 Flex State Parameter 214 Disp 1 Item 2 Flex State Parameter 215 Disp 1 Item 3 Disp 1 Item 4 Flex State Parameter 216 Flex State Parameter 217 Disp 1 Item 5 C60 Breaker Management Relay GE Multilin...
  • Page 189 Disp 6 Item 4 Disp 6 Item 5 USER DISPLAY 7 Disp 7 Top Line Disp 7 Bottom Line Disp 7 Item 1 Disp 7 Item 2 Disp 7 Item 3 Disp 7 Item 4 GE Multilin C60 Breaker Management Relay...
  • Page 190: Settings

    GSource 5 round CT Phase VT ______ Ratio Source 5 Phase VT Auxiliary VT ______ Connection Source 5 Auxiliary VT Auxiliary VT ______ Secondary SIGNAL SOURCE 6 Auxiliary VT ______ Ratio Source 6 Name C60 Breaker Management Relay GE Multilin...
  • Page 191 Breaker 2 ΦB Breaker 2 ΦC Breaker 2 Ext Alarm Breaker 2 Alarm Delay Breaker 2 Out of Sv Breaker 2 Manual Close Recall Time UCA SBO TIMER (FOR BREAKERS 1/2) UCA SBO Timeout GE Multilin C60 Breaker Management Relay...
  • Page 192 FlexLogic Entry 82 FlexLogic Entry 39 FlexLogic Entry 83 FlexLogic Entry 40 FlexLogic Entry 84 FlexLogic Entry 41 FlexLogic Entry 85 FlexLogic Entry 42 FlexLogic Entry 86 FlexLogic Entry 43 FlexLogic Entry 87 8-10 C60 Breaker Management Relay GE Multilin...
  • Page 193 FlexLogic Entry 176 FlexLogic Entry 130 FlexLogic Entry 177 FlexLogic Entry 131 FlexLogic Entry 178 FlexLogic Entry 132 FlexLogic Entry 179 FlexLogic Entry 133 FlexLogic Entry 180 FlexLogic Entry 134 FlexLogic Entry 181 GE Multilin C60 Breaker Management Relay 8-11...
  • Page 194 FlexLogic Entry 270 FlexLogic Entry 224 FlexLogic Entry 271 FlexLogic Entry 225 FlexLogic Entry 272 FlexLogic Entry 226 FlexLogic Entry 273 FlexLogic Entry 227 FlexLogic Entry 274 FlexLogic Entry 228 FlexLogic Entry 275 8-12 C60 Breaker Management Relay GE Multilin...
  • Page 195 FlexLogic Entry 364 FlexLogic Entry 318 FlexLogic Entry 365 FlexLogic Entry 319 FlexLogic Entry 366 FlexLogic Entry 320 FlexLogic Entry 367 FlexLogic Entry 321 FlexLogic Entry 368 FlexLogic Entry 322 FlexLogic Entry 369 GE Multilin C60 Breaker Management Relay 8-13...
  • Page 196 FlexLogic Entry 458 FlexLogic Entry 412 FlexLogic Entry 459 FlexLogic Entry 413 FlexLogic Entry 460 FlexLogic Entry 414 FlexLogic Entry 461 FlexLogic Entry 415 FlexLogic Entry 462 FlexLogic Entry 416 FlexLogic Entry 463 8-14 C60 Breaker Management Relay GE Multilin...
  • Page 197 FlexLogic Timer 10 Dropout Delay FlexLogic Entry 506 FLEXLOGIC TIMER 11 FlexLogic Entry 507 FlexLogic Timer 11 Type FlexLogic Entry 508 FlexLogic Timer 11 Pickup Delay FlexLogic Timer 11 Dropout Delay FlexLogic Entry 509 FlexLogic Entry 510 GE Multilin C60 Breaker Management Relay 8-15...
  • Page 198 FlexElement 1 Input Mode FlexLogic Timer 22 Dropout Delay FlexElement 1 Comp Mode FLEXLOGIC TIMER 23 FlexElement 1 Direction FlexLogic Timer 23 Type FlexElement 1 Pickup FlexLogic Timer 23 Pickup Delay FlexElement 1 Hysteresis 8-16 C60 Breaker Management Relay GE Multilin...
  • Page 199 FlexElement 6 Rst Delay FlexElement 4 Function FlexElement 6 Blk FlexElement 4 Name FlexElement 6 Target FlexElement 4 +IN FlexElement 6 Events FlexElement 4 –IN FLEXLELEMENT 7 FlexElement 4 Input Mode FlexElement 7 Function GE Multilin C60 Breaker Management Relay 8-17...
  • Page 200 FlexElement 8 Direction FlexElement 8 Pickup FlexElement 8 Hysteresis FlexElement 8 dt Unit FlexElement 8 dt FlexElement 8 Pkp Delay FlexElement 8 Rst Delay FlexElement 8 Blk FlexElement 8 Target FlexElement 8 Events 8-18 C60 Breaker Management Relay GE Multilin...
  • Page 201: Settings

    BF2 Use Amp Supv Phase UV2 Signal Source BF2 Use Seal-In Phase UV2 Mode BF2 3-Pole Initiate Phase UV2 Pickup BF2 Block Phase UV2 Curve BF2 Ph Amp Supv Pickup Phase UV2 Delay GE Multilin C60 Breaker Management Relay 8-19...
  • Page 202 Aux UV1 Events AUXILIARY OVERVOLTAGE 1 Aux OV1 Function Aux OV1 Signal Source Aux OV1 Pickup Aux OV1 Pickup Delay Aux OV1 Reset Delay Aux OV1 Block Aux OV1 Target Aux OV1 Events 8-20 C60 Breaker Management Relay GE Multilin...
  • Page 203: Settings

    Digital Element 2 Function Synchk2 Target Dig Elem 2 Name Synchk2 Events Dig Elem 2 Input AUTORECLOSE Dig Elem 2 Pickup Delay AR Function Dig Elem 2 Reset Delay AR Mode Dig Elem 2 Block GE Multilin C60 Breaker Management Relay 8-21...
  • Page 204 Dig Elem 12 Block Dig Elem 7 Reset Delay Digital Element 12 Target Dig Elem 7 Block Digital Element 12 Events Digital Element 7 Target DIGITAL ELEMENT 13 Digital Element 7 Events Digital Element 13 Function 8-22 C60 Breaker Management Relay GE Multilin...
  • Page 205 Counter 5 Name Counter 1 Block Counter 5 Units Counter 1 Set to Preset Counter 5 Preset Counter 1 Reset Counter 5 Compare Counter 1 Freeze/Reset Counter 5 Up Counter 1 Freeze/Count Counter 5 Down GE Multilin C60 Breaker Management Relay 8-23...
  • Page 206 Counter 8 Down Counter 8 Block Counter 8 Set to Preset Counter 8 Reset Counter 8 Freeze/Reset Counter 8 Freeze/Count BREAKER 1 ARCING CURRENT Bkr 1 Arc Amp Function Bkr 1 Arc Amp Source 8-24 C60 Breaker Management Relay GE Multilin...
  • Page 207: Inputs / Outputs

    8 COMMISSIONING 8.6 INPUTS / OUTPUTS 8.6 INPUTS / OUTPUTS 8.6.1 CONTACT INPUTS Table 8–6: CONTACT INPUTS CONTACT INPUT DEBNCE TIME EVENTS THRESHOLD GE Multilin C60 Breaker Management Relay 8-25...
  • Page 208: Virtual Inputs

    Virtual Input 27 Virtual Input 28 Virtual Input 29 Virtual Input 30 Virtual Input 31 Virtual Input 32 8.6.3 UCA SBO TIMER Table 8–8: UCA SBO TIMER UCA SBO TIMER UCA SBO Timeout 8-26 C60 Breaker Management Relay GE Multilin...
  • Page 209: Remote Devices

    Remote Device 6 Remote Device 7 Remote Device 8 Remote Device 9 Remote Device 10 Remote Device 11 Remote Device 12 Remote Device 13 Remote Device 14 Remote Device 15 Remote Device 16 GE Multilin C60 Breaker Management Relay 8-27...
  • Page 210: Remote Inputs

    Remote Input 22 Remote Input 23 Remote Input 24 Remote Input 25 Remote Input 26 Remote Input 27 Remote Input 28 Remote Input 29 Remote Input 30 Remote Input 31 Remote Input 32 8-28 C60 Breaker Management Relay GE Multilin...
  • Page 211: Contact Outputs

    8 COMMISSIONING 8.6 INPUTS / OUTPUTS 8.6.6 CONTACT OUTPUTS Table 8–11: CONTACT OUTPUTS CONTACT OUTPUT OPERATE SEAL-IN EVENTS GE Multilin C60 Breaker Management Relay 8-29...
  • Page 212: Virtual Outputs

    8.6 INPUTS / OUTPUTS 8 COMMISSIONING 8.6.7 VIRTUAL OUTPUTS Table 8–12: VIRTUAL OUTPUTS (Sheet 1 of 2) Table 8–12: VIRTUAL OUTPUTS (Sheet 2 of 2) VIRTUAL EVENTS VIRTUAL EVENTS OUTPUT OUTPUT 8-30 C60 Breaker Management Relay GE Multilin...
  • Page 213: Remote Outputs

    Table 8–13: REMOTE OUTPUTS (Sheet 1 of 2) Table 8–13: REMOTE OUTPUTS (Sheet 2 of 2) OUTPUT # OPERAND EVENTS OUTPUT # OPERAND EVENTS REMOTE OUTPUTS – DNA REMOTE OUTPUTS – UserSt 8.6.9 RESETTING SETTING VALUE RESETTING Reset Operand GE Multilin C60 Breaker Management Relay 8-31...
  • Page 214: Transducer I/O

    8.7 TRANSDUCER I/O 8 COMMISSIONING 8.7 TRANSDUCER I/O 8.7.1 DCMA INPUTS Table 8–14: DCMA INPUTS DCMA FUNCTION UNITS RANGE VALUES INPUT 8-32 C60 Breaker Management Relay GE Multilin...
  • Page 215: Rtd Inputs

    8 COMMISSIONING 8.7 TRANSDUCER I/O 8.7.2 RTD INPUTS Table 8–15: RTD INPUTS RTD INPUT FUNCTION TYPE GE Multilin C60 Breaker Management Relay 8-33...
  • Page 216: Testing

    8.8 TESTING 8 COMMISSIONING 8.8 TESTING 8.8.1 SETTINGS Table 8–16: FORCE CONTACT INPUTS Table 8–17: FORCE CONTACT OUTPUTS FORCE CONTACT INPUT FORCE CONTACT OUTPUT 8-34 C60 Breaker Management Relay GE Multilin...
  • Page 217: Flexanalog

    SRC 2 I_2 Mag SRC 2 Negative Sequence Current Magnitude (A) 6241 SRC 2 I_2 Angle SRC 2 Negative Sequence Current Angle (°) 6242 SRC 2 Igd Mag SRC 2 Differential Ground Current Magnitude (A) GE Multilin C60 Breaker Management Relay...
  • Page 218 SRC 2 Vca Mag SRC 2 Phase CA Voltage Magnitude (V) 6749 SRC 2 Vca Angle SRC 2 Phase CA Voltage Angle (°) 6750 SRC 2 Vx RMS SRC 2 Auxiliary Voltage RMS (V) C60 Breaker Management Relay GE Multilin...
  • Page 219 SRC 1 Negative Varhour (varh) 7440 SRC 2 Pos Watthour SRC 2 Positive Watthour (Wh) 7442 SRC 2 Neg Watthour SRC 2 Negative Watthour (Wh) 7444 SRC 2 Pos varh SRC 2 Positive Varhour (varh) GE Multilin C60 Breaker Management Relay...
  • Page 220 FlexElement 13 Actual 39451 FlexElement 14 OpSig FlexElement 14 Actual 39453 FlexElement 15 OpSig FlexElement 15 Actual 39455 FlexElement 16 OpSig FlexElement 16 Actual 40960 Communications Group Communications Group 40971 Active Setting Group Current Setting Group C60 Breaker Management Relay GE Multilin...
  • Page 221: Overview

    1 to 254; see Chapter 5 for details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an exception to this rule; it will act on a message containing any slave address. GE Multilin C60 Breaker Management Relay...
  • Page 222 19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves start listening for a new packet from the master except for the addressed slave. C60 Breaker Management Relay GE Multilin...
  • Page 223: Algorithm

    Yes: G (+) A --> A and continue. Is j = 8? No: go to 5 Yes: continue i + 1 --> i Is i = N? No: go to 3 Yes: continue A --> CRC GE Multilin C60 Breaker Management Relay...
  • Page 224: Function Codes

    DATA #1 - lo NUMBER OF REGISTERS - lo DATA #2 - hi CRC - lo DATA #2 - lo CRC - hi DATA #3 - hi DATA #3 - lo CRC - lo CRC - hi C60 Breaker Management Relay GE Multilin...
  • Page 225: Function Code 05H: Execute Operation

    DATA STARTING ADDRESS - lo DATA STARTING ADDRESS - lo DATA - hi DATA - hi DATA - lo DATA - lo CRC - lo CRC - lo CRC - hi CRC - hi GE Multilin C60 Breaker Management Relay...
  • Page 226: Function Code 10H: Store Multiple Settings

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte C60 Breaker Management Relay GE Multilin...
  • Page 227: File Transfers

    To read binary COMTRADE oscillography files, read the following filenames: • OSCnnnn.CFG • OSCnnn.DAT Replace "nnn" with the desired oscillography trigger number. For ASCII format, use the following file names • OSCAnnnn.CFG • OSCAnnn.DAT GE Multilin C60 Breaker Management Relay...
  • Page 228: Modbus ® Password Operation

    COMMAND or SETTING password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP. C60 Breaker Management Relay GE Multilin...
  • Page 229: Memory Mapping

    ...Repeated for module number 24 0418 ...Repeated for module number 25 0419 ...Repeated for module number 26 041A ...Repeated for module number 27 041B ...Repeated for module number 28 041C ...Repeated for module number 29 GE Multilin C60 Breaker Management Relay...
  • Page 230 ...Repeated for module number 4 1561 ...Repeated for module number 5 1565 ...Repeated for module number 6 1569 ...Repeated for module number 7 156D ...Repeated for module number 8 1571 ...Repeated for module number 9 B-10 C60 Breaker Management Relay GE Multilin...
  • Page 231 -359.9 to 0 ° F002 1A09 Phase BG Voltage Magnitude 0 to 999999.999 0.001 F060 1A0B Phase BG Voltage Angle -359.9 to 0 ° F002 1A0C Phase CG Voltage Magnitude 0 to 999999.999 0.001 F060 GE Multilin C60 Breaker Management Relay B-11...
  • Page 232 1C1B Phase C Power Factor -0.999 to 1 0.001 F013 1C1C Reserved (4 items) F001 1C20 ...Repeated for module number 2 1C40 ...Repeated for module number 3 1C60 ...Repeated for module number 4 B-12 C60 Breaker Management Relay GE Multilin...
  • Page 233 Reserved (8 items) F001 1EA0 ...Repeated for module number 2 1EC0 ...Repeated for module number 3 1EE0 ...Repeated for module number 4 1F00 ...Repeated for module number 5 1F20 ...Repeated for module number 6 GE Multilin C60 Breaker Management Relay B-13...
  • Page 234 Number Of Fault Reports 0 to 65535 F001 Fault Reports (Read Only Non-Volatile) (10 modules) 3030 Fault Time 0 to 4294967295 F050 3032 ...Repeated for module number 2 3034 ...Repeated for module number 3 B-14 C60 Breaker Management Relay GE Multilin...
  • Page 235 ...Repeated for module number 4 34F4 ...Repeated for module number 5 34F5 ...Repeated for module number 6 34F6 ...Repeated for module number 7 34F7 ...Repeated for module number 8 34F8 ...Repeated for module number 9 GE Multilin C60 Breaker Management Relay B-15...
  • Page 236 Passwords (Read Only) 4010 Command Password Status 0 to 1 F102 0 (Disabled) 4011 Setting Password Status 0 to 1 F102 0 (Disabled) Preferences (Read/Write Setting) 4050 Flash Message Time 0.5 to 10 F001 B-16 C60 Breaker Management Relay GE Multilin...
  • Page 237 UCA Communications Reserved (16 items) 0 to 1 F001 40E0 TCP Port Number for the IEC 60870-5-104 Protocol 1 to 65535 F001 2404 40E1 IEC 60870-5-104 Protocol Function 0 to 1 F102 0 (Disabled) GE Multilin C60 Breaker Management Relay B-17...
  • Page 238 ...Repeated for module number 10 4294 ...Repeated for module number 11 4296 ...Repeated for module number 12 4298 ...Repeated for module number 13 429A ...Repeated for module number 14 429C ...Repeated for module number 15 B-18 C60 Breaker Management Relay GE Multilin...
  • Page 239 F060 4504 Auxiliary VT Connection 0 to 6 F166 1 (Vag) 4505 Auxiliary VT Secondary 50 to 240 F001 4506 Auxiliary VT Ratio 1 to 24000 F060 4508 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-19...
  • Page 240 Synchrocheck Dead Source Select 0 to 5 F176 1 (LV1 and DV2) 4788 Synchrocheck Dead V1 Max Volt 0 to 1.25 0.01 F001 4789 Synchrocheck Dead V2 Max Volt 0 to 1.25 0.01 F001 B-20 C60 Breaker Management Relay GE Multilin...
  • Page 241 ...Repeated for module number 22 58B0 ...Repeated for module number 23 58B8 ...Repeated for module number 24 58C0 ...Repeated for module number 25 58C8 ...Repeated for module number 26 58D0 ...Repeated for module number 27 GE Multilin C60 Breaker Management Relay B-21...
  • Page 242 0 to 1 F111 0 (Definite Time) 7004 Phase UV1 Delay 0 to 600 0.01 F001 7005 Phase UV1 Minimum Voltage 0 to 3 0.001 F001 7006 Phase UV1 Block 0 to 65535 F300 B-22 C60 Breaker Management Relay GE Multilin...
  • Page 243 7300 DCMA Inputs x Function 0 to 1 F102 0 (Disabled) 7301 DCMA Inputs x ID F205 "DCMA Ip 1 " 7307 DCMA Inputs x Reserved 1 (4 items) 0 to 65535 F001 GE Multilin C60 Breaker Management Relay B-23...
  • Page 244 ...Repeated for module number 16 7640 ...Repeated for module number 17 7650 ...Repeated for module number 18 7660 ...Repeated for module number 19 7670 ...Repeated for module number 20 7680 ...Repeated for module number 21 B-24 C60 Breaker Management Relay GE Multilin...
  • Page 245 0.001 F001 9011 FlexElement Block 0 to 65535 F300 9012 FlexElement Target 0 to 2 F109 0 (Self-reset) 9013 FlexElement Events 0 to 1 F102 0 (Disabled) 9014 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-25...
  • Page 246 0 (Disabled) B01D Digital Element x Reserved (3 items) F001 B020 ...Repeated for module number 2 B040 ...Repeated for module number 3 B060 ...Repeated for module number 4 B080 ...Repeated for module number 5 B-26 C60 Breaker Management Relay GE Multilin...
  • Page 247 ...Repeated for module number 13 C068 ...Repeated for module number 14 C070 ...Repeated for module number 15 C078 ...Repeated for module number 16 C080 ...Repeated for module number 17 C088 ...Repeated for module number 18 GE Multilin C60 Breaker Management Relay B-27...
  • Page 248 ...Repeated for module number 67 C218 ...Repeated for module number 68 C220 ...Repeated for module number 69 C228 ...Repeated for module number 70 C230 ...Repeated for module number 71 C238 ...Repeated for module number 72 B-28 C60 Breaker Management Relay GE Multilin...
  • Page 249 ...Repeated for module number 14 C770 ...Repeated for module number 15 C780 ...Repeated for module number 16 C790 ...Repeated for module number 17 C7A0 ...Repeated for module number 18 C7B0 ...Repeated for module number 19 GE Multilin C60 Breaker Management Relay B-29...
  • Page 250 ...Repeated for module number 33 CEA0 ...Repeated for module number 34 CEB0 ...Repeated for module number 35 CEC0 ...Repeated for module number 36 CED0 ...Repeated for module number 37 CEE0 ...Repeated for module number 38 B-30 C60 Breaker Management Relay GE Multilin...
  • Page 251 ...Repeated for module number 15 D380 ...Repeated for module number 16 D390 ...Repeated for module number 17 D3A0 ...Repeated for module number 18 D3B0 ...Repeated for module number 19 D3C0 ...Repeated for module number 20 GE Multilin C60 Breaker Management Relay B-31...
  • Page 252 0 to 3 F131 0 (Disabled) Remote Devices (Read/Write Setting) (16 modules) E000 Remote Device x ID F202 "Remote Device 1 " E00A ...Repeated for module number 2 E014 ...Repeated for module number 3 B-32 C60 Breaker Management Relay GE Multilin...
  • Page 253 0 to 65535 F300 E601 Remote Output DNA x Events 0 to 1 F102 0 (Disabled) E602 Remote Output DNA x Reserved (2 items) 0 to 1 F001 E604 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-33...
  • Page 254 ...Repeated for module number 16 E6C0 ...Repeated for module number 17 E6C4 ...Repeated for module number 18 E6C8 ...Repeated for module number 19 E6CC ...Repeated for module number 20 E6D0 ...Repeated for module number 21 B-34 C60 Breaker Management Relay GE Multilin...
  • Page 255 -4096 to 4095 F002 F0A7 Transducer Channel to Calibrate Value -1.1 to 366.5 0.001 F004 F0A9 Transducer Channel to Calibrate Gain 0.8 to 1.2 0.0001 F060 F0AB Transducer Calibration Date 0 to 4294967295 F050 GE Multilin C60 Breaker Management Relay B-35...
  • Page 256 0.001 F001 FC33 Auxiliary OV X Pickup Delay 0 to 600 0.01 F001 FC34 Auxiliary OV X Reset Delay 0 to 600 0.01 F001 FC35 Auxiliary OV X Block 0 to 65535 F300 B-36 C60 Breaker Management Relay GE Multilin...
  • Page 257 Auxiliary UV X Events 0 to 1 F102 0 (Disabled) FC69 Auxiliary UV X Reserved (7 items) 0 to 65535 F001 FC70 ...Repeated for module number 2 FC80 ...Repeated for module number 3 GE Multilin C60 Breaker Management Relay B-37...
  • Page 258: Modbus ® Memory Map Data Formats

    12.35 kA. F100 F013 ENUMERATION: VT CONNECTION TYPE POWER_FACTOR PWR FACTOR (SIGNED 16 BIT INTEGER) 0 = Wye; 1 = Delta Positive values indicate lagging power factor; negative values indi- cate leading. B-38 C60 Breaker Management Relay GE Multilin...
  • Page 259 F118 ENUMERATION: OFF/ON ENUMERATION: OSCILLOGRAPHY MODE 0 = Off, 1 = On 0 = Automatic Overwrite, 1 = Protected F109 ENUMERATION: CONTACT OUTPUT OPERATION 0 = Self-reset, 1 = Latched, 2 = Disabled GE Multilin C60 Breaker Management Relay B-39...
  • Page 260 OVERFREQ 3 OVERFREQ 4 0 = 1 A, 1 = 5 A UNDERFREQ 1 UNDERFREQ 2 F124 UNDERFREQ 3 ENUMERATION: LIST OF ELEMENTS UNDERFREQ 4 UNDERFREQ 5 bitmask element UNDERFREQ 6 AUX UV1 B-40 C60 Breaker Management Relay GE Multilin...
  • Page 261 0 = Fail, 1 = OK, 2 = n/a F125 F135 ENUMERATION: ACCESS LEVEL ENUMERATION: GAIN CALIBRATION 0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service 0 = 0x1, 1 = 1x16 GE Multilin C60 Breaker Management Relay B-41...
  • Page 262 POWER ON SRAM DATA ERROR POWER OFF PROGRAM MEMORY RELAY IN SERVICE WATCHDOG ERROR RELAY OUT OF SERVICE LOW ON MEMORY WATCHDOG RESET REMOTE DEVICE OFF OSCILLOGRAPHY CLEAR ANY MINOR ERROR REBOOT COMMAND B-42 C60 Breaker Management Relay GE Multilin...
  • Page 263 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6 F168 ENUMERATION: INRUSH INHIBIT FUNCTION 0 = Disabled, 1 = 2nd GE Multilin C60 Breaker Management Relay B-43...
  • Page 264 0 = A, 1 = B, 2 = C 0 = A, 1 = B, 2 = C, 3 = G F186 ENUMERATION MEASUREMENT MODE 0 = Phase to Ground, 1 = Phase to Phase B-44 C60 Breaker Management Relay GE Multilin...
  • Page 265 Contact Inputs 81 to 96 F200 Contact Outputs 1 to 16 TEXT40 40 CHARACTER ASCII TEXT Contact Outputs 17 to 32 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB Contact Outputs 33 to 48 GE Multilin C60 Breaker Management Relay B-45...
  • Page 266 IDs. The operate bit for element ID [6] VIRTUAL OUTPUTS (1-64) X is bit [X mod 16] in register [X/16]. [10] CONTACT OUTPUTS VOLTAGE DETECTED (1-64) [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64) B-46 C60 Breaker Management Relay GE Multilin...
  • Page 267 Password types for display in password prompts 0 = LEVEL, 1 = DELTA bitmask password type MASTER F518 ENUMERATION FlexElement Units SETTING COMMAND 0 = Milliseconds, 1 = Seconds, 2 = Minutes FACTORY GE Multilin C60 Breaker Management Relay B-47...
  • Page 268 B.3 MEMORY MAPPING APPENDIX B bitmask Setting Type MMI_SETTING_TYPE ENUMERATION Setting Setting types for display in web pages Command bitmask Setting Type Factory Setting Unrestricted Setting Master-accessed Setting B-48 C60 Breaker Management Relay GE Multilin...
  • Page 269: Uca/Mms

    PDIS (distance) • RREC (reclosing relay) • PDOC (directional overcurrent) • RSYN (synchronizing or synchronism-check relay) • PFRQ (frequency relay) • XCBR (circuit breaker) UCA data can be accessed through the "UCADevice" MMS domain. GE Multilin C60 Breaker Management Relay...
  • Page 270 VARIABLE ACCESS SERVICES: • Read • Write • InformationReport • GetVariableAccessAttributes • GetNamedVariableListAttributes OPERATOR COMMUNICATION SERVICES: (none) SEMAPHORE MANAGEMENT SERVICES: (none) DOMAIN MANAGEMENT SERVICES: • GetDomainAttributes PROGRAM INVOCATION MANAGEMENT SERVICES: (none) EVENT MANAGEMENT SERVICES: (none) C60 Breaker Management Relay GE Multilin...
  • Page 271 SBOCF SBO Configuration Description for brick BO Description for each point Actual instantiation of GCTL objects is as follows: GCTL1 = Virtual Inputs (32 total points – SI1 to SI32); includes SBO functionality. NOTE GE Multilin C60 Breaker Management Relay...
  • Page 272 Description for brick All MMXU.MX Description of ALL included MMXU.MX BrcbMX BasRCB Controls reporting of measurements Actual instantiation of MMXU objects is as follows: 1 MMXU per Source (as determined from the ‘product order code’) NOTE C60 Breaker Management Relay GE Multilin...
  • Page 273 DESCRIPTION PhsARat RATIO Primary/secondary winding ratio NeutARat RATIO Primary/secondary winding ratio Description for brick Actual instantiation of ctRATO objects is as follows: 1 ctRATO per Source (as determined from the ‘product order code’). NOTE GE Multilin C60 Breaker Management Relay...
  • Page 274: Uca Reporting

    2 minutes (120000 ms). This ensures that the UR will not abort the con- nection. If other MMS data is being polled on the same connection at least once every 2 minutes, this timeout will not apply. C60 Breaker Management Relay GE Multilin...
  • Page 275: Iec 60870-5-104 Protocol

    Address Field of the Link: Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin C60 Breaker Management Relay...
  • Page 276 <18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 Ë <20> := Packed single-point information with status change detection M_SP_NA_1 C60 Breaker Management Relay GE Multilin...
  • Page 277 <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 Ë <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 Ë <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin C60 Breaker Management Relay...
  • Page 278 Blank boxes indicate functions or ASDU not used. • ‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 C60 Breaker Management Relay GE Multilin...
  • Page 279 <21> M_ME_ND_1 <30> M_SP_TB_1 <31> M_DP_TB_1 <32> M_ST_TB_1 <33> M_BO_TB_1 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 GE Multilin C60 Breaker Management Relay...
  • Page 280 <102> C_RD_NA_1 <103> C_CS_NA_1 <104> C_TS_NA_1 <105> C_RP_NA_1 <106> C_CD_NA_1 <107> C_TS_TA_1 <110> P_ME_NA_1 <111> P_ME_NB_1 <112> P_ME_NC_1 <113> P_AC_NA_1 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) C60 Breaker Management Relay GE Multilin...
  • Page 281 Long pulse duration (duration determined by a system parameter in the outstation) Ë Persistent output Ë Supervision of maximum delay in command direction of commands and setpoint commands Ë Maximum allowable delay of commands and setpoint commands: 10 s GE Multilin C60 Breaker Management Relay...
  • Page 282 Transmission of sequences of events Transmission of sequences of recorded analog values Ë File transfer in control direction: Transparent file Ë Background scan: Background scan Ë Acquisition of transmission delay: Acquisition of transmission delay C60 Breaker Management Relay GE Multilin...
  • Page 283 The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard. Ethernet 802.3 Ë Serial X.21 interface Ë Ë Other selection(s) from RFC 2200 (list below if selected) GE Multilin C60 Breaker Management Relay...
  • Page 284: Points List

    SRC 1 Auxiliary Voltage Magnitude 2088 Synchrocheck 2 Delta Phase degrees 2043 SRC 1 Auxiliary Voltage Angle degrees 2089 Tracking Frequency 2044 SRC 1 Zero Sequence Voltage Magnitude 2090 FlexElement 1 Actual none D-10 C60 Breaker Management Relay GE Multilin...
  • Page 285 388-403 Remote Device x States 404-419 LED Column x State[0] 420-435 LED Column x State[1] C_SC_NA_1Points 1100- Virtual Input States[0] - No Select Required 1115 1116- Virtual Input States[1] - Select Required 1131 GE Multilin C60 Breaker Management Relay D-11...
  • Page 286 D.1 IEC 60870-5-104 PROTOCOL APPENDIX D D-12 C60 Breaker Management Relay GE Multilin...
  • Page 287: Dnp E.1 Dnp Device Profile

    2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Ë Ë Fixed at 2 Configurable Ë Ë Ë Configurable Requires Data Link Layer Confirmation: Never Ë Always Ë Sometimes Ë Configurable Ë GE Multilin C60 Breaker Management Relay...
  • Page 288 FlexLogic™. The On/Off times and Count value are ignored. "Pulse Off" and "Latch Off" operations put the appropriate Virtual Input into the "Off" state. "Trip" and "Close" operations both put the appropriate Virtual Input into the "On" state. C60 Breaker Management Relay GE Multilin...
  • Page 289 Default Object: Ë 16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Ë Point-by-point list attached Ë Other Value: _____ Ë Point-by-point list attached Ë Sends Multi-Fragment Responses: Ë Ë GE Multilin C60 Breaker Management Relay...
  • Page 290: E.2.1 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. C60 Breaker Management Relay GE Multilin...
  • Page 291 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. GE Multilin C60 Breaker Management Relay...
  • Page 292 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. C60 Breaker Management Relay GE Multilin...
  • Page 293 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. GE Multilin C60 Breaker Management Relay...
  • Page 294 Virtual Input 27 Virtual Output 27 Virtual Input 28 Virtual Output 28 Virtual Input 29 Virtual Output 29 Virtual Input 30 Virtual Output 30 Virtual Input 31 Virtual Output 31 Virtual Input 32 Virtual Output 32 C60 Breaker Management Relay GE Multilin...
  • Page 295 Contact Input 14 Contact Input 65 Contact Input 15 Contact Input 66 Contact Input 16 Contact Input 67 Contact Input 17 Contact Input 68 Contact Input 18 Contact Input 69 Contact Input 19 Contact Input 70 GE Multilin C60 Breaker Management Relay...
  • Page 296 Remote Input 7 Contact Output 21 Remote Input 8 Contact Output 22 Remote Input 9 Contact Output 23 Remote Input 10 Contact Output 24 Remote Input 11 Contact Output 25 Remote Input 12 E-10 C60 Breaker Management Relay GE Multilin...
  • Page 297 LED State 13 (PHASE A) AR 3 Element OP LED State 14 (PHASE B) AR 4 Element OP LED State 15 (PHASE C) AR 5 Element OP LED State 16 (NTL/GROUND) AR 6 Element OP BATTERY FAIL GE Multilin C60 Breaker Management Relay E-11...
  • Page 298 REMOTE DEVICE OFF ANY MINOR ERROR ANY MAJOR ERROR ANY SELF-TESTS IRIG-B FAILURE DSP ERROR NOT USED NO DSP INTERUPTS UNIT NOT CALIBRATED PROTOTYPE FIRMWARE FLEXLOGIC ERR TOKEN EQUIPMENT MISMATCH UNIT NOT PROGRAMMED SYSTEM EXCEPTION E-12 C60 Breaker Management Relay GE Multilin...
  • Page 299: E.3.2 Binary Output And Control Relay Output

    Virtual Input 22 Virtual Input 23 Virtual Input 24 Virtual Input 25 Virtual Input 26 Virtual Input 27 Virtual Input 28 Virtual Input 29 Virtual Input 30 Virtual Input 31 Virtual Input 32 GE Multilin C60 Breaker Management Relay E-13...
  • Page 300: E.3.3 Counters

    Digital Counter 5 Digital Counter 6 Digital Counter 7 Digital Counter 8 Oscillography Trigger Count Events Since Last Clear Note that a counter freeze command has no meaning for counters 8 and 9. E-14 C60 Breaker Management Relay GE Multilin...
  • Page 301: E.3.4 Analog Inputs

    SRC 1 Phase B Current RMS SRC 1 Phase C Current RMS SRC 1 Neutral Current RMS SRC 1 Phase A Current Magnitude SRC 1 Phase A Current Angle SRC 1 Phase B Current Magnitude GE Multilin C60 Breaker Management Relay E-15...
  • Page 302 SRC 1 Negative Sequence Voltage Magnitude SRC 1 Negative Sequence Voltage Angle SRC 1 Three Phase Real Power SRC 1 Phase A Real Power SRC 1 Phase B Real Power SRC 1 Phase C Real Power E-16 C60 Breaker Management Relay GE Multilin...
  • Page 303 FlexElement 1 Actual FlexElement 2 Actual FlexElement 3 Actual FlexElement 4 Actual FlexElement 5 Actual FlexElement 6 Actual FlexElement 7 Actual FlexElement 8 Actual FlexElement 9 Actual FlexElement 10 Actual FlexElement 11 Actual GE Multilin C60 Breaker Management Relay E-17...
  • Page 304 E.3 DNP POINT LISTS APPENDIX E Table E–6: ANALOG INPUT POINTS (Sheet 4 of 4) POINT DESCRIPTION FlexElement 12 Actual FlexElement 13 Actual FlexElement 14 Actual FlexElement 15 Actual FlexElement 16 Actual Current Setting Group E-18 C60 Breaker Management Relay GE Multilin...
  • Page 305: Change Notes

    1601-0093-B5 2.9X 03 December 2001 URC-025 1601-0093-B8 2.9X 10 September 2004 URX-162 F.1.2 CHANGES TO C60 MANUAL Table F–2: MAJOR UPDATES FOR C60 MANUAL-B8 PAGE CHANGE DESCRIPTION (B5) Title Update Manual part number from B5 to B8 Update Updated BINARY INPUTS table Table F–3: MAJOR UPDATES FOR C60 MANUAL-B5...
  • Page 306 F.1 CHANGE NOTES APPENDIX F Table F–4: MAJOR UPDATES FOR C60 MANUAL-B4 PAGE (B3) CHANGE DESCRIPTION Title Update Manual part number from B3 to B4 Update Updated SINGLE LINE DIAGRAM from 813710A8 to 813710A9 Update Updated DEVICE NUMBERS AND FUNCTIONS table...
  • Page 307: Tables And Figures

    Table: 5–1 OSCILLOGRAPHY CYCLES/RECORD EXAMPLE ....................... 5-17 Table: 5–4 RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS ..................5-20 Table: 5–9 UR FLEXLOGIC™ OPERAND TYPES ......................... 5-33 Table: 5–10 C60 FLEXLOGIC™ OPERANDS..........................5-34 Table: 5–11 FLEXLOGIC™ GATE CHARACTERISTICS......................... 5-36 Table: 5–12 FLEXLOGIC™ OPERATORS ............................. 5-37 Table: 5–13 FLEXELEMENT™...
  • Page 308: List Of Figures

    Figure 3–1: C60 VERTICAL MOUNTING AND DIMENSIONS ......................3-1 Figure 3–2: C60 VERTICAL SIDE MOUNTING INSTALLATION ....................... 3-2 Figure 3–3: C60 VERTICAL SIDE MOUNTING REAR DIMENSIONS ....................3-3 Figure 3–4: C60 HORIZONTAL MOUNTING AND DIMENSIONS ..................... 3-3 Figure 3–5: UR MODULE WITHDRAWAL/INSERTION ........................3-4 Figure 3–6: REAR TERMINAL VIEW..............................
  • Page 309 Figure 6–2: UR PHASE ANGLE MEASUREMENT CONVENTION ....................6-7 Figure 6–3: ILLUSTRATION OF THE UR CONVENTION FOR SYMMETRICAL COMPONENTS ........... 6-8 Figure 6–4: EQUIVALENT SYSTEM FOR FAULT LOCATION ......................6-14 Figure 6–5: FAULT LOCATOR SCHEME............................6-15 GE Multilin C60 Breaker Management Relay...
  • Page 310: Abbreviations

    FSK ....frequency-shift keying NTR ....neutral FWD ....forward O ....over G ....generator OC, O/C ..overcurrent GE ....General Electric O/P, Op ..output GND ....ground OP....operate GNTR ..... generator C60 Breaker Management Relay GE Multilin...
  • Page 311 ....with option SEQ....sequence WRT....with respect to SIR ....source impedance ratio SRC....source X .....reactance SSB ....single side band XDUCER..transducer SSEL ....session selector XFMR....transformer STATS .... statistics SUPN ..... supervision Z......impedance GE Multilin C60 Breaker Management Relay...
  • Page 312: Warranty

    24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory.
  • Page 313: Index

    UCA/MMS ....5-12, 5-29, 5-88, 5-89, 5-90, 5-91, C-1 BATTERY TAB ..............1-10 web server ..............5-13 BINARY INPUT POINTS ............. E-8 COMTRADE ............... B-7, B-8 BINARY OUTPUT POINTS ..........E-13 CONDUCTED RFI ............2-10 BLOCK DIAGRAM .............. 1-3 GE Multilin C60 Breaker Management Relay...
  • Page 314 Modbus registers ..........B-15, B-23 actual values ..............6-5 settings ................. 5-93 configuration ..............1-6 specifications ..............2-7 Modbus registers ............B-11 DEFINITE TIME CURVE ........... 5-58 settings ................5-9 DEMAND METERING specifications ..............2-9 C60 Breaker Management Relay GE Multilin...
  • Page 315 ............5-89, 5-90 Modbus registers ............B-21 RTD inputs ............ 2-8, 3-16, 5-94 operands ...............5-33, 5-34 virtual ................5-87 operators ..............5-37 INSPECTION CHECKLIST ..........1-1 rules ................5-37 INSTALLATION specifications ..............2-6 commissioning ..............8-7 GE Multilin C60 Breaker Management Relay...
  • Page 316 03/04h ............B-4 function code 05h ............B-5 function code 06h ............B-5 function code 10h ............B-6 PANEL CUTOUT ............... 3-1 introduction ..............B-1 PASSWORD SECURITY ..........5-7, 8-1 memory map data formats ..........B-38 PASSWORDS C60 Breaker Management Relay GE Multilin...
  • Page 317 ................6-9 settings ................. 5-89 Modbus registers ............B-11 statistics ................. 6-5 settings ................. 5-27 REMOTE INPUTS SPECIFICATIONS .............. 2-5 actual values ..............6-3 ST TYPE CONNECTORS ..........3-19 commissioning .............. 8-28 STANDARD ABBREVIATIONS ..........F-6 GE Multilin C60 Breaker Management Relay...
  • Page 318 ..............5-90 reporting ................. C-6 SBO timeout ............5-29, 5-88 settings ................. 5-12 WARRANTY ..............F-8 UserSt-1 bit pair ............5-92 WATT-HOURS ............2-7, 6-11 UL APPROVAL ..............2-10 WEB SERVER PROTOCOL ........5-13, 8-1 C60 Breaker Management Relay GE Multilin...
  • Page 319 INDEX WEBSITE ................1-1 WIRING DIAGRAM ............3-6 ZERO SEQUENCE CORE BALANCE ........3-9 GE Multilin C60 Breaker Management Relay...
  • Page 320 INDEX viii C60 Breaker Management Relay GE Multilin...