Sinusoidal interference
The following table shows the EMC behavior of the modules with respect to sinusoidal
interference. This requires the HMI device to meet the specifications and directives for
electrical installation.
Sinusoidal interfer-
ence
HF radiation (elec-
tromagnetic fields)
according to
IEC 61000-4-3
HF power applied to
lines and line shields
according
IEC 61000-4-6
Emission of radio interference
The following table shows the emitted interference from electromagnetic fields according to
EN 61000-6-4, measured at a distance of 10 m.
Radiated emission (emitted interference)
1 GHz to 3 GHz
3 GHz to 6 GHz
30 MHz to 230 MHz
230 MHz to 1000 MHz
Emission of radio interference voltages
0.150 MHz to 0.5 MHz
0.5 MHz to 30 MHz
See also
Notes about usage (Page 14)
Industrial support (https://support.industry.siemens.com)
IFP Basic
Operating Instructions, 03/2019, A5E46178354 - AB
Test values
80% amplitude modulation at 1 kHz
with 10 V/m in the range of 80 MHz to 1 GHz
with 3 V/m in the range 1.4 GHz to 2 GHz
with 3 V/m in the range 2 GHz to 6 GHz
Test voltage 10 V, with 80% amplitude modulation of 1 kHz
in the 150 kHz to 80 MHz range
< 76 dB peak and < 56 dB average
< 80 dB peak and < 60 dB average
< 40 dB (μV/m) quasi-peak
< 47 dB (μV/m) quasi-peak
< 79 dB quasi-peak and < 66 dB average
< 73 dB quasi-peak and < 60 dB average
Technical information