Changing The Ied Functionality; Defining The Setting Group; Activating A Setting Group - ABB Relion 630 Series Operation Manual

Protection and control
Hide thumbs Also See for Relion 630 Series:
Table of Contents
Section 6
Operating procedures
6.4
6.4.1
6.4.1.1
76
A071214 V3 EN
Figure 57:
Clear view
The content of the Clear menu depends on the pre-configuration or on the
functions configured with PCM600.
2.
Select the item to be cleared with
3.
Press
, select OK to confirm the selection or Cancel to cancel the selection.
4.
To clear other items, repeat the steps.

Changing the IED functionality

Defining the setting group

Do not switch off the auxiliary power supply to the IED before the
changes, for example, setting parameter or local/remote control state
changes are saved.
A mechanism for limiting the number of writings per time period is included in the
IED to prevent the flash memory from wearing out due to too many writings caused
by the application configuration. As a consequence, saving application function states
may take up to an hour. If the auxiliary power is interrupted before the states are saved,
that change is lost. Settings and configuration parameters are saved without delay.

Activating a setting group

IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.
or
.
1MRS756509 E
630 series
Operation Manual