Appendix H - - Bacnet Point Mapping For T1000 (1-3Kva); Bacnet Analog Input Point Mapping For T1000 (1-3Kva) - Toshiba RemotEye 4 User Manual

4 ups network card
Hide thumbs Also See for RemotEye 4:
Table of Contents
APPENDIX H – – BACNET POINT MAPPING FOR T1000 (1-3KVA)
H.1

BACNET ANALOG INPUT POINT MAPPING FOR T1000 (1-3KVA)

ALL – BACnet Object: Analog Input
Access:
Read Only
Instance
Object Name & Description
1
RemotEye 4 Software Version
ID
2
RemotEye 4 Slave ID Number
3
IP Address
4
Subnet Mask First Byte
5
Gateway IP Address First Byte
6
RemotEye 4 Installation Date
7
Date on RemotEye 4
8
Time on RemotEye 4
9
UPS Manufacturer
10
UPS Typeform
11
UPS Serial Number
12
UPS Capacity
13
UPS Installation Date
14
UPS Firmware Version
15
UPS System Temperature
16
UPS System Temperature
17
Input Voltage
18
Input Voltage Percent
19
Input Rated Voltage (V)
20
Input Frequency
21
Output Voltage
22
Output Voltage Percent
23
Output Rated Voltage
24
Output Load Percentage
25
Output Rated Frequency
206
BACnet Property: Present Value
Status Flags:
Normal
T1000 (1-3kVA) BACnet Analog Point Mapping
Units
Firmware
ID
IP Address
Subnet Mask
IP Address
Date
Date
Time
Characters
Characters
Characters
kVA
Date
Firmware
°C
°F
Volts
%
Volts
Hz
Volts
%
Volts
%
Hz
Out of Service: FALSE
Comments
1.03
192.168.1.150
55.255.255.0
192.168.1.1
MM/DD/YYYY
MM/DD/YYYY
HH:MM:SS
TOSHIBA
RX03
MM/DD/YYYY
RemotEye 4 User Manual – 90988-007