Appendix C - Bacnet Point Mapping For 4300; Bacnet Analog Input Point Mapping For 4300 - Toshiba RemotEye 4 User Manual

4 ups network card
Hide thumbs Also See for RemotEye 4:
Table of Contents
APPENDIX C – BACNET POINT MAPPING FOR 4300
C.1

BACNET ANALOG INPUT POINT MAPPING FOR 4300

ALL – BACnet Object: Analog Input
Access:
Read Only
Inst. ID
Object Name & Description
1
RemotEye 4 Software Version
2
RemotEye 4 Slave ID Number
3
IP Address
4
Subnet Mask
5
Gateway IP Address
6
RemotEye 4 Installation Date
7
Date on RemotEye 4
8
Time on RemotEye 4
9
UPS Manufacturer
10
UPS Typeform
11
UPS Serial Number
12
UPS Capacity
13
UPS Installation Date
14
UPS Display Firmware Version
15
Input Number of Phases
16
Input Voltage Phase AB (L-L)
17
Input Voltage Phase BC (L-L)
18
Input Voltage Phase CA (L-L)
19
Input Voltage Phase AN (L-N)
20
Input Voltage Phase BN (L-N)
21
Input Voltage Phase CN (L-N)
22
Input Voltage Percent Phase A
23
Input Voltage Percent Phase B
24
Input Voltage Percent Phase C
25
Input Rated Voltage (L-L)
26
Input Rated Voltage (L-N)
27
Input Current
28
Input Rated Current
29
Input Frequency Phase A
30
Input Frequency Phase B
31
Input Frequency Phase C
32
Voltage Input Under Voltage Detection Level
RemotEye 4 User Manual – 90988-007
BACnet Property: Present Value
Status Flags:
Normal
4300 BACnet Analog Input Point Mapping
Out of Service: FALSE
Units
Comments
Firmware
1.03
ID
IP Address
192.168.1.150
Subnet Mask
55.255.255.0
IP Address
192.168.1.1
Date
MM/DD/YYYY
Date
MM/DD/YYYY
Time
HH:MM:SS
Characters
Toshiba
Characters
4310F3F500FAXXXX
Characters
2012101234567890
kVA
Date
MM/DD/YYYY
Firmware
T43DFV01000
Phase
Volts
Volts
Volts
Volts
Volts
Volts
%
%
%
Volts
Volts
Amps
Amps
0.1Hz
0.1Hz
0.1Hz
%
171

Hide quick links:

Table of Contents
loading

Table of Contents