• IP addresses have been configured for the processor modules – use the
AADvance Discover tool installed with the Workbench
• The 9110 processor modules have been rebooted in Recovery Mode, if
the modules are rebooted into Recovery Mode at the same time a single
ControlFLASH update will be applied to all the modules
Update procedure:
• Run the ControlFLASH program
• Select the type of module from the list
• Browse to the T9110 Processor Module
• Select the version of the firmware to be installed (NOTE: it may be
necessary to tick the "Show all versions" checkbox to see the version
required)
• Update the module
• The firmware will be downloaded and stored on the module – this will
take approximately 5 minutes
• The modules will be rebooted to confirm the firmware has been updated
successfully
Refer to document
1756-UM105 ControlFLASH firmware Upgrade Kit User
Manual
in the Literature Library for detailed instructions for using
ControlFLASH.
.
NOTE When updating the firmware, it is recommended that RSWho
is not actively browsing the 9110 Processor module.

Ethernet Communication Protocols

AADvance Ethernet ports are used to support several transport layer services;
these services are listed in the following table:
Protocol
Port Number
TCP
502
TCP
1132
TCP
10001-10006
TCP
4818
TCP
N/A
UDP
1123,1124
UDP
2010
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Purpose
MODBUS Slave
ISaGRAF, application downloads, debug, SoE
Transparent Communication Interface (Serial Tunnelling)
CIP Produce & Consume
Telnet (diagnostic Interface)
IXL Bindings
Discovery and configuration Protocol